The text of a manual · part 1 of 5
Discrete Input and Output Modules Product Data, pages 1 to 10
Pages 1 to 10 of 48
The original document is the PDF (644 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1746-ITV16
Page 1
Discrete Input and Output Modules (Catalog Numbers 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IB32, -IC16, -IG16, -IH16, -IM4, -IM8, -IM16, -IN16, -ITB16, -ITV16, -IV8, -IV16, -IV32, -OA8, -OA16, -OAP12, -OB8, -OBP8, -OB16, -OB16E, -OBP16, -OB32, -OG16, -OV8, -OV16, -OVP16, -OV32, -OW4, -OW8, -OW16, -OX8, -IO4, -IO8, -IO12)
Product Data
91-187-39
What’s Inside...
91-187-40
Page
Discrete I/O Module Summary
2
Features and Benefits
4
I/O Module Operation
6
Enhanced Discrete I/O Modules
8 includes: 32-Point, Fast Response, High-Current Solid-State, and Electronically Protected Modules Terms and Symbols 13 Specifications, Wiring, and Circuit Diagrams Fixed I/O Chassis Module Compatibility Discrete I/O Power Dissipation
16
Environmental Specifications
47
Accessories
47
Allen-Bradley Support
48
44 46
91-187-41
Our wide variety of input, output, and combination modules makes the SLC 500t family the smart choice for all of your small PLC applications. I/O modules are available in a wide variety of densities including 4-, 8-, 16-, and 32-point and can interface to AC, DC, and TTL voltage levels. Output modules are available with solid state AC, solid state DC, and relay contact type outputs. For added flexibility, combination modules are also available in 2-input/2-output, 4-input/4-output, and 6-input/6-output versions. Designed and tested for industrial applications, our modules are of the highest quality. The modules feature input filtering, optical isolation, and built-in surge protection to enhance the reliability of operation in noisy industrial environments. Class I, Division 2 certified by UL and CSA. CE compliant. All modules are UL 508 listed and CSA 22.2 142 approved and meet Class I, Division 2 hazardous location requirements of both Underwriter’s Laboratory and the Canadian Standards Association (except for those noted in the module summary on page 2). For use within the European Union or EEA regions, most modules have been tested to meet Council Directive 89/336 Electromagnetic Compatibility (exceptions are listed on page 2).
Page 2
2
Discrete Input and Output Modules
Discrete I/O Module Summary ID Code
.A
Voltage Category
Cat. No.
Input/Output
I/O Points
Module Description
Page
100
100/120V ac
1746-IA4
Input
4
120V ac Input Module
16
300
100/120V ac
1746-IA8
Input
8
120V ac Input Module
16
500
100/120V ac
1746-IA16
Input
16
120V ac Input Module
16
101
200/240V ac
1746-IM4
Input
4
240V ac Input Module
16
301
200/240V ac
1746-IM8
Input
8
240V ac Input Module
16
501
200/240V ac
1746-IM16
Input
16
240V ac Input Module
16
2703
100/120V ac
1746-OA8
Output
8
120/240V ac Output Module
18
2903
100/120V ac
1746-OA16
Output
16
120/240V ac Output Module
18
2803
120/240V ac
1746-OAP12
Output
12
High Current 120/240V ac Output Module
18
AC Modules
➀
DC Modules 306
24V dc
1746-IB8
Input
8
Current Sinking DC Input Module
20
506
24V dc
1746-IB16
Input
16
Current Sinking DC Input Module
20
706
24V dc
1746-IB32
➀
Input
32
Current Sinking DC Input Module
20
519
24V dc
1746-ITB16
Input
16
Fast Response DC Sinking Input Module
20
509
48V dc
1746-IC16
Input
16
Current Sinking DC Input Module
20
507
125V dc
1746-IH16
Input
16
Current Sinking DC Input Module
20
320
24V dc
1746-IV8
Input
8
Current Sourcing DC Input Module
24
520
24V dc
1746-IV16
Input
16
Current Sourcing DC Input Module
24
720
24V dc
➀ 1746-IV32
Input
32
Current Sourcing DC Input Module
24
518
24V dc
1746-ITV16
Input
16
Fast Response DC Sourcing Input Module
24
515
5V dc/TTL
➁ 1746-IG16
Input
16
Current Sourcing TTL Input Module
28
2713
24V dc
1746-OB8
Output
8
Current Sourcing DC Output Module
29
2913
24V dc
1746-OB16
Output
16
Current Sourcing DC Output Module
29
2920
24V dc
➀➂ 1746-OB16E
Output
16
Current Sourcing DC Output Module
29
3113
24V dc
1746-OB32
➀
Output
32
Current Sourcing DC Output Module
29
2721
24V dc
➂ 1746-OBP8
Output
8
High Current Sourcing DC Output Module
32
2921
24V dc
1746-OBP16
➀
Output
16
High Current Sourcing DC Output Module
32
2714
24V dc
1746-OV8
Output
8
Current Sinking DC Output Module
34
2914
24V dc
1746-OV16
Output
16
Current Sinking DC Output Module
34
24V dc
➀ 1746-OV32
Output
32
Current Sinking DC Output Module
34
2922
24V dc
➀ 1746-OVP16
Output
16
High Current Sinking DC Output Module
37
2915
5V dc/TTL
1746-OG16
➁
Output
16
Current Sinking TTL Output Module
38
3114
Publication 1746-2.35
Page 3
Discrete Input and Output Modules
ID Code
Voltage Category
3
Cat. No.
Input/Output
I/O Points
Module Description
Page
24V ac/dc
1746-IN16
Input
16
24V ac/dc Input Module
39
AC/DC Relay
➀ 1746-OW4
Output
4
Relay (Hard Contact) Output Module
40
2700
AC/DC Relay
➀ 1746-OW8
Output
8
Relay (Hard Contact) Output Module
40
2900
AC/DC Relay
1746-OW16
➀
Output
16
Relay (Hard Contact) Output Module
40
2701
AC/DC Relay
1746-OX8
➀
Output
8
Isolated Relay Output Module
40
800
Inputs – 120V ac Outputs – AC/DC Relay
1746-IO4
➀
Input/Output
2 Inputs 2 Outputs
Combination Input/Output Module
42
1100
Inputs – 120V ac Outputs – AC/DC Relay
1746-IO8
➀
Input/Output
4 Inputs 4 Outputs
Combination Input/Output Module
42
1500
Inputs – 120V ac Outputs – AC/DC Relay
1746-IO12
➀
Input/Output
6 Inputs 6 Outputs
Combination Input/Output Module
42
AC/DC Modules 510 2500
➀ Certified for Class I, Division 2 hazardous location by CSA only. ➁ Not CE marked. ➂ These modules carry the C-UL mark and are certified by UL per CSA requirements.
Spectrum Controls, Inc. Modules ID Code
These modules are sold and supported by Spectrum Controls Inc., Bellevue, Washington. For additional information, contact Spectrum at (206) 746–9481.
Voltage Category
Cat. No.
Input/Output
I/O Points
Module Description
120/240V ac
1746sc-OAP8I
Output
8
Isolated ac Output Module
AC Modules 2705 DC Modules 324
24V dc
1746sc-IB8I
Input
8
Isolated DC Input Module
324
48V dc
1746sc-IC8I
Input
8
48V Isolated DC Input Module
303
120V ac/dc
1746sc-IA8I
Input
8
Isolated ac/dc Input Module
304
220V ac/dc
1746sc-IM8I
Input
8
Isolated ac/dc Input Module
AC/DC Modules
Publication 1746-2.35
Page 4
4
Discrete Input and Output Modules
Features and Benefits
Select I/O modules to exactly match your application. Combination modules allow you to have inputs and outputs in a single slot for efficient use of your chassis space. Expand the I/O capacity of your fixed controller system. Two discrete I/O modules can be added to the fixed controller’s 2-slot expansion chassis increasing the flexibility of the system. All relay contacts are Silver Cadmium with Gold overlay. Gold plating resists oxidation and tarnishing resulting from non-use. Silver Cadmium acts as an excellent conductor. High-density 32-Point DC I/O and fast response DC inputs are available. These modules allow you to apply the SLC 500 processors in a broader spectrum of control applications.
LEDs indicate the status of each I/O point. INPUT
IN 0 IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 AC COM AC COM
Terminal identification diagrams on each module
LEDs indicate the status of each I/O point. Assisting you in troubleshooting, LEDs illuminate when the proper signal is received at an input terminal, or when the processor applies power to an output terminal. Terminal identification diagrams on each module. Terminal identification diagrams are located on each module making terminal identification easier.
Publication 1746-2.35
Page 5
Discrete Input and Output Modules
5
Digital and field circuits are optically isolated.
Self-locking tabs secure the module in the chassis.
Removable terminal blocks are color coded for quick identification. Self-lifting field-wire pressure plates help reduce installation time.
Barrier type terminal blocks are provided on all modules.
Digital and field circuits are optically isolated. All modules feature isolation between digital and field circuits, resulting in increased noise immunity and limited damage to your system due to an electrical malfunction of the field wiring. Self-lifting field-wire pressure plates cut installation time. Wiring terminals have self-lifting pressure plates to secure two #14 AWG field wires. Removable terminal blocks help ease the wiring task. Removable terminal blocks allow you to replace the module without rewiring it (not available on all modules). Removable terminal blocks are color coded for quick identification. A matching color band is also provided on the front of the module to assist in matching the terminal block to the module. Barrier-type terminal blocks provided on all modules. Each terminal block features a barrier on three sides of each terminal to help prevent accidental shorting of field wiring. Self-locking tabs secure the module in the chassis. No tools are necessary to install or remove a module from the chassis. To install a module, you slide it into the chassis until it latches in place.
Publication 1746-2.35
Page 6
6
Discrete Input and Output Modules
I/O Module Operation
Power Supply Requirements Discrete modules receive power through the 1746 I/O chassis backplane from the associated chassis power supply. Refer to the individual module specifications for the current required from the power supply (in mA) to operate the module. You should total the current requirements for all the modules in the chassis to avoid overloading the power supply or the I/O chassis backplane.
Input Modules An input module responds to an input signal in the following manner: 1. Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If not filtered, voltage transients could produce false data. All input modules use input filtering. 2. Optical isolation shields backplane circuits and module logic circuits from possible damage due to electrical transients. 3. Logic circuits process the signal. 4. An input LED turns on or off indicating the status of the corresponding input device. Input Filtering
Input
Optical Isolation
Logic Circuits
Backplane
LED
Output Modules An output module controls the output signal in the following manner: 1. Logic circuits determine the output status. 2. An output LED indicates the status of the output signal. 3. Optical isolation separates module logic and backplane circuits from the field signal. 4. The output driver turns the corresponding output on or off. Backplane
Logic Circuits
Optical Isolation
LED
Publication 1746-2.35
Output Drivers
Output
Page 7
Discrete Input and Output Modules
7
Surge Suppression Most output modules have built-in surge suppression to reduce the effects of high-voltage transients. However, we recommend that you use an additional suppression device if an output module is being used to control an inductive device such as: • relays • motor starters • solenoids • motors Additional suppression is especially important if your inductive device is in series with or parallel to a hard contact such as: • pushbuttons • selector switches By adding a suppression device directly across the coil of an inductive device, you will reduce the effects of voltage transients caused by interrupting the current to that inductive device and prolong the life of the switch contacts. The diagram below shows an output module with a suppression device. + DC or L1 VAC/VDC OUT 0
Snubber
OUT 1 OUT 2
AC or DC Output Module
OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 COM
DC COM or L2
Recommended surge suppressors are provided in the specifications tables. Important:
Adding a suppression device across your load will defeat the fast turn-off feature of the 1746-OB16E Series B and later, -OBP8 Series B and later, -OBP16, and -OVP16 DC output modules. Refer to pages 29, 32, and 37 for more information about suppression when using the 1746-OB16E, -OBP8, -OBP16, and -OVP16, respectively.
Publication 1746-2.35
Page 8
8
Discrete Input and Output Modules
Enhanced Discrete I/O Modules
32-Point Modules (1746-IB32, -IV32, -OB32, -OV32) The 32-point I/O modules allow you to reduce panel space requirements by wiring 32 DC input or 32 DC output devices to a module residing in one slot. These modules can be used with both modular chassis systems or fixed controllers. The 32-point modules come equipped with a 40-pin male connector on the front instead of screw terminals. This connector is designed to accept your cable fitted with the 1746-N3 mating connector. One 1746-N3 connector and 45 crimp-type contacts are packaged with each module. The other end of the cable can be wired to a user-supplied terminal block. As an alternative, 1492 prewired cables, purchased separately, can be used to connect the 32-point modules to 1492 interface modules. For more information, refer to the Accessories section on page 47.
1492-CABLExx Connects 32-point module to DIN rail mountable terminal block
32-Point I/O Module Male MIL-C-83503 Header
ÎÎÎÎ ÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎ 1492-IFM40xx DIN rail mountable terminal block
Publication 1746-2.35
Page 9
Discrete Input and Output Modules
9
Fast Response Input Modules (1746-ITB16, -ITV16) The fast response DC input modules provide 16 input points and are designed for high-speed applications requiring fast response to input signals from DC sensing devices. When used with an SLC 5/03t or higher processor and the Discrete Input Interrupt (DII) instruction (100 msec polling), pulses can be read up to a frequency of 1K Hz. (It is 2K Hz if the input signals are from a gray code encoder.) Recommended wiring to an Allen-Bradley 845D Absolute Gray Code Encoder is provided on page 27. Both sinking and sourcing versions of the fast response input module are available.
High-Current Solid-State Output Modules (1746-OBP8, -OAP12, -OBP16, -OVP16).B High-current solid-state output modules expand application coverage for the SLC 500 by providing the following enhanced functionality: • increased current rating • fuse protection and diagnostics • high-speed switching • excellent reliability The high current solid state output modules expand application coverage in automotive, packaging, and material handling applications by allowing the SLC 500 processor to directly control solenoids, contactors, motors, and motor starter loads (up to size 5) with continuous current requirements of up to 1A at 60_C (1746-OAP12, -OBP16, -OVP16) and 2.0A at 60_C (1746-OBP8). 1746-OAP12, -OBP16, and -OVP16 modules also provide fuse protection and blown fuse diagnostics for increased up-time. The ac output module includes two replaceable fuses (one per common), which protect the module in the event of short circuits. 1746-OBP16 and -OVP16 output modules include a replaceable fuse on the common providing short circuit protection for wiring (16 AWG or larger) to external loads. A jumper can be set on these modules to provide CPU notification and system shutdown if the module fuse blows. The modules also include a blown fuse LED to assist I/O troubleshooting. Inductive load turn-off time for 1746-OBP8 (Series B and later), -OBP16 and -OVP16 DC output modules is reduced by 70% over standard 1746 DC output modules allowing fast application cycle times.
Publication 1746-2.35
Page 10
10
Discrete Input and Output Modules
Innovative heat sink design for the OAP12 allows heat to be dissipated through the chassis frame metal providing cool operation and excellent reliability. Blown Fuse LED OUTPUT
1 AMP TRIAC
FAC
OBP16 Replaceable Fuse (F1)
JP 1
SER
3 2 1
OUTPUT VOLTAGE
1.5 AMP/OUTPUT @ 30C 1.0 AMP/OUTPUT @ 60C
OUTPUT RATINGS
SA
20.4 – 26.4 –––––– –––
UL
Jumper for CPU Notification
Jumper Settings and Fuse Replacement Information:
WHEN FUSE OPENS 2
1 <–––– CPU CONTINUES 2 <––––––– CPU FAULTS
3
3
Î Î
6.4 AMP/MODULE
OBP16 & OVP16
SLC 500 OUTPUT MODULE
F U S E
CAT
8 12 9 13 10 14 11 15
SERIAL NO.
4 5 6 7
F1
0 1 2 3
2 CPU FAULTS
1 CPU CONTINUES
WHEN FUSE OPENS
2
F1
FUSE REPLACEMENT LITTLEFUSE 322010 A–B CAT. NO. 1746–F8 MADE IN U.S.A.
FUSE REPLACEMENT LITTLEFUSE 322010 A–B CAT. NO. 1746–F8
OVP16 Replaceable Fuse (F1)
Blown Fuse LED OUTPUT F U S E
1 AMP TRIAC
SER
3 2 1 JP 1
2.0A MAX @ 30 °C 1.25A MAX @ 55 °C 1.0A MAX @ 60 °C 240V MAX / 480 VA MAX 4.5A MAX/COMMON (MAX V.A. PER MODULE) 1440 VA
2 CPU FAULTS
1 CPU CONTINUES
Publication 1746-2.35
WHEN FUSE OPENS
2
Replaceable Fuse (F2)
WHEN FUSE OPENS 2
3
3 FUSE REPLACEMENT SAN–O HQ 6.3A A–B CAT. NO. 1746–F9 MADE IN U.S.A.
F2
Jumper Settings and Fuse Replacement Information:
OUTPUT RATINGS
ÎÎ ÎÎ
OAP12
OUTPUT VOLTAGE
85–265 VAC 50/60 HZ
UL SA
Replaceable Fuse (F1)
Jumper for CPU Notification
FAC
F1
SLC 500 OUTPUT MODULE
8 9 10 11
CAT
4 5 6 7
SERIAL NO.
0 1 2 3
1 <–––– CPU CONTINUES 2 <––––––– CPU FAULTS
FUSE REPLACEMENT SAN–O HQ 6.3A A–B CAT. NO. 1746–F9