Page 1

Discrete Input and Output Modules (Catalog Numbers 1746-IA4, -IA8, -IA16, -IB8, -IB16, -IB32, -IC16, -IG16, -IH16, -IM4, -IM8, -IM16, -IN16, -ITB16, -ITV16, -IV8, -IV16, -IV32, -OA8, -OA16, -OAP12, -OB8, -OBP8, -OB16, -OB16E, -OBP16, -OB32, -OG16, -OV8, -OV16, -OVP16, -OV32, -OW4, -OW8, -OW16, -OX8, -IO4, -IO8, -IO12)

Product Data

91-187-39

What’s Inside...

91-187-40

Page

Discrete I/O Module Summary

2

Features and Benefits

4

I/O Module Operation

6

Enhanced Discrete I/O Modules

8 includes: 32-Point, Fast Response, High-Current Solid-State, and Electronically Protected Modules Terms and Symbols 13 Specifications, Wiring, and Circuit Diagrams Fixed I/O Chassis Module Compatibility Discrete I/O Power Dissipation

16

Environmental Specifications

47

Accessories

47

Allen-Bradley Support

48

44 46

91-187-41

Our wide variety of input, output, and combination modules makes the SLC 500t family the smart choice for all of your small PLC applications. I/O modules are available in a wide variety of densities including 4-, 8-, 16-, and 32-point and can interface to AC, DC, and TTL voltage levels. Output modules are available with solid state AC, solid state DC, and relay contact type outputs. For added flexibility, combination modules are also available in 2-input/2-output, 4-input/4-output, and 6-input/6-output versions. Designed and tested for industrial applications, our modules are of the highest quality. The modules feature input filtering, optical isolation, and built-in surge protection to enhance the reliability of operation in noisy industrial environments. Class I, Division 2 certified by UL and CSA. CE compliant. All modules are UL 508 listed and CSA 22.2 142 approved and meet Class I, Division 2 hazardous location requirements of both Underwriter’s Laboratory and the Canadian Standards Association (except for those noted in the module summary on page 2). For use within the European Union or EEA regions, most modules have been tested to meet Council Directive 89/336 Electromagnetic Compatibility (exceptions are listed on page 2).

Page 2

2

Discrete Input and Output Modules

Discrete I/O Module Summary ID Code

.A

Voltage Category

Cat. No.

Input/Output

I/O Points

Module Description

Page

100

100/120V ac

1746-IA4

Input

4

120V ac Input Module

16

300

100/120V ac

1746-IA8

Input

8

120V ac Input Module

16

500

100/120V ac

1746-IA16

Input

16

120V ac Input Module

16

101

200/240V ac

1746-IM4

Input

4

240V ac Input Module

16

301

200/240V ac

1746-IM8

Input

8

240V ac Input Module

16

501

200/240V ac

1746-IM16

Input

16

240V ac Input Module

16

2703

100/120V ac

1746-OA8

Output

8

120/240V ac Output Module

18

2903

100/120V ac

1746-OA16

Output

16

120/240V ac Output Module

18

2803

120/240V ac

1746-OAP12

Output

12

High Current 120/240V ac Output Module

18

AC Modules

➀

DC Modules 306

24V dc

1746-IB8

Input

8

Current Sinking DC Input Module

20

506

24V dc

1746-IB16

Input

16

Current Sinking DC Input Module

20

706

24V dc

1746-IB32

➀

Input

32

Current Sinking DC Input Module

20

519

24V dc

1746-ITB16

Input

16

Fast Response DC Sinking Input Module

20

509

48V dc

1746-IC16

Input

16

Current Sinking DC Input Module

20

507

125V dc

1746-IH16

Input

16

Current Sinking DC Input Module

20

320

24V dc

1746-IV8

Input

8

Current Sourcing DC Input Module

24

520

24V dc

1746-IV16

Input

16

Current Sourcing DC Input Module

24

720

24V dc

➀ 1746-IV32

Input

32

Current Sourcing DC Input Module

24

518

24V dc

1746-ITV16

Input

16

Fast Response DC Sourcing Input Module

24

515

5V dc/TTL

➁ 1746-IG16

Input

16

Current Sourcing TTL Input Module

28

2713

24V dc

1746-OB8

Output

8

Current Sourcing DC Output Module

29

2913

24V dc

1746-OB16

Output

16

Current Sourcing DC Output Module

29

2920

24V dc

➀➂ 1746-OB16E

Output

16

Current Sourcing DC Output Module

29

3113

24V dc

1746-OB32

➀

Output

32

Current Sourcing DC Output Module

29

2721

24V dc

➂ 1746-OBP8

Output

8

High Current Sourcing DC Output Module

32

2921

24V dc

1746-OBP16

➀

Output

16

High Current Sourcing DC Output Module

32

2714

24V dc

1746-OV8

Output

8

Current Sinking DC Output Module

34

2914

24V dc

1746-OV16

Output

16

Current Sinking DC Output Module

34

24V dc

➀ 1746-OV32

Output

32

Current Sinking DC Output Module

34

2922

24V dc

➀ 1746-OVP16

Output

16

High Current Sinking DC Output Module

37

2915

5V dc/TTL

1746-OG16

➁

Output

16

Current Sinking TTL Output Module

38

3114

Publication 1746-2.35

Page 3

Discrete Input and Output Modules

ID Code

Voltage Category

3

Cat. No.

Input/Output

I/O Points

Module Description

Page

24V ac/dc

1746-IN16

Input

16

24V ac/dc Input Module

39

AC/DC Relay

➀ 1746-OW4

Output

4

Relay (Hard Contact) Output Module

40

2700

AC/DC Relay

➀ 1746-OW8

Output

8

Relay (Hard Contact) Output Module

40

2900

AC/DC Relay

1746-OW16

➀

Output

16

Relay (Hard Contact) Output Module

40

2701

AC/DC Relay

1746-OX8

➀

Output

8

Isolated Relay Output Module

40

800

Inputs – 120V ac Outputs – AC/DC Relay

1746-IO4

➀

Input/Output

2 Inputs 2 Outputs

Combination Input/Output Module

42

1100

Inputs – 120V ac Outputs – AC/DC Relay

1746-IO8

➀

Input/Output

4 Inputs 4 Outputs

Combination Input/Output Module

42

1500

Inputs – 120V ac Outputs – AC/DC Relay

1746-IO12

➀

Input/Output

6 Inputs 6 Outputs

Combination Input/Output Module

42

AC/DC Modules 510 2500

➀ Certified for Class I, Division 2 hazardous location by CSA only. ➁ Not CE marked. ➂ These modules carry the C-UL mark and are certified by UL per CSA requirements.

Spectrum Controls, Inc. Modules ID Code

These modules are sold and supported by Spectrum Controls Inc., Bellevue, Washington. For additional information, contact Spectrum at (206) 746–9481.

Voltage Category

Cat. No.

Input/Output

I/O Points

Module Description

120/240V ac

1746sc-OAP8I

Output

8

Isolated ac Output Module

AC Modules 2705 DC Modules 324

24V dc

1746sc-IB8I

Input

8

Isolated DC Input Module

324

48V dc

1746sc-IC8I

Input

8

48V Isolated DC Input Module

303

120V ac/dc

1746sc-IA8I

Input

8

Isolated ac/dc Input Module

304

220V ac/dc

1746sc-IM8I

Input

8

Isolated ac/dc Input Module

AC/DC Modules

Publication 1746-2.35

Page 4

4

Discrete Input and Output Modules

Features and Benefits

Select I/O modules to exactly match your application. Combination modules allow you to have inputs and outputs in a single slot for efficient use of your chassis space. Expand the I/O capacity of your fixed controller system. Two discrete I/O modules can be added to the fixed controller’s 2-slot expansion chassis increasing the flexibility of the system. All relay contacts are Silver Cadmium with Gold overlay. Gold plating resists oxidation and tarnishing resulting from non-use. Silver Cadmium acts as an excellent conductor. High-density 32-Point DC I/O and fast response DC inputs are available. These modules allow you to apply the SLC 500 processors in a broader spectrum of control applications.

LEDs indicate the status of each I/O point. INPUT

IN 0 IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 AC COM AC COM

Terminal identification diagrams on each module

LEDs indicate the status of each I/O point. Assisting you in troubleshooting, LEDs illuminate when the proper signal is received at an input terminal, or when the processor applies power to an output terminal. Terminal identification diagrams on each module. Terminal identification diagrams are located on each module making terminal identification easier.

Publication 1746-2.35

Page 5

Discrete Input and Output Modules

5

Digital and field circuits are optically isolated.

Self-locking tabs secure the module in the chassis.

Removable terminal blocks are color coded for quick identification. Self-lifting field-wire pressure plates help reduce installation time.

Barrier type terminal blocks are provided on all modules.

Digital and field circuits are optically isolated. All modules feature isolation between digital and field circuits, resulting in increased noise immunity and limited damage to your system due to an electrical malfunction of the field wiring. Self-lifting field-wire pressure plates cut installation time. Wiring terminals have self-lifting pressure plates to secure two #14 AWG field wires. Removable terminal blocks help ease the wiring task. Removable terminal blocks allow you to replace the module without rewiring it (not available on all modules). Removable terminal blocks are color coded for quick identification. A matching color band is also provided on the front of the module to assist in matching the terminal block to the module. Barrier-type terminal blocks provided on all modules. Each terminal block features a barrier on three sides of each terminal to help prevent accidental shorting of field wiring. Self-locking tabs secure the module in the chassis. No tools are necessary to install or remove a module from the chassis. To install a module, you slide it into the chassis until it latches in place.

Publication 1746-2.35

Page 6

6

Discrete Input and Output Modules

I/O Module Operation

Power Supply Requirements Discrete modules receive power through the 1746 I/O chassis backplane from the associated chassis power supply. Refer to the individual module specifications for the current required from the power supply (in mA) to operate the module. You should total the current requirements for all the modules in the chassis to avoid overloading the power supply or the I/O chassis backplane.

Input Modules An input module responds to an input signal in the following manner: 1. Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If not filtered, voltage transients could produce false data. All input modules use input filtering. 2. Optical isolation shields backplane circuits and module logic circuits from possible damage due to electrical transients. 3. Logic circuits process the signal. 4. An input LED turns on or off indicating the status of the corresponding input device. Input Filtering

Input

Optical Isolation

Logic Circuits

Backplane

LED

Output Modules An output module controls the output signal in the following manner: 1. Logic circuits determine the output status. 2. An output LED indicates the status of the output signal. 3. Optical isolation separates module logic and backplane circuits from the field signal. 4. The output driver turns the corresponding output on or off. Backplane

Logic Circuits

Optical Isolation

LED

Publication 1746-2.35

Output Drivers

Output

Page 7

Discrete Input and Output Modules

7

Surge Suppression Most output modules have built-in surge suppression to reduce the effects of high-voltage transients. However, we recommend that you use an additional suppression device if an output module is being used to control an inductive device such as: • relays • motor starters • solenoids • motors Additional suppression is especially important if your inductive device is in series with or parallel to a hard contact such as: • pushbuttons • selector switches By adding a suppression device directly across the coil of an inductive device, you will reduce the effects of voltage transients caused by interrupting the current to that inductive device and prolong the life of the switch contacts. The diagram below shows an output module with a suppression device. + DC or L1 VAC/VDC OUT 0

Snubber

OUT 1 OUT 2

AC or DC Output Module

OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 COM

DC COM or L2

Recommended surge suppressors are provided in the specifications tables. Important:

Adding a suppression device across your load will defeat the fast turn-off feature of the 1746-OB16E Series B and later, -OBP8 Series B and later, -OBP16, and -OVP16 DC output modules. Refer to pages 29, 32, and 37 for more information about suppression when using the 1746-OB16E, -OBP8, -OBP16, and -OVP16, respectively.

Publication 1746-2.35

Page 8

8

Discrete Input and Output Modules

Enhanced Discrete I/O Modules

32-Point Modules (1746-IB32, -IV32, -OB32, -OV32) The 32-point I/O modules allow you to reduce panel space requirements by wiring 32 DC input or 32 DC output devices to a module residing in one slot. These modules can be used with both modular chassis systems or fixed controllers. The 32-point modules come equipped with a 40-pin male connector on the front instead of screw terminals. This connector is designed to accept your cable fitted with the 1746-N3 mating connector. One 1746-N3 connector and 45 crimp-type contacts are packaged with each module. The other end of the cable can be wired to a user-supplied terminal block. As an alternative, 1492 prewired cables, purchased separately, can be used to connect the 32-point modules to 1492 interface modules. For more information, refer to the Accessories section on page 47.

1492-CABLExx Connects 32-point module to DIN rail mountable terminal block

32-Point I/O Module Male MIL-C-83503 Header

ÎÎÎÎ ÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎÎÎÎÎÎÎÎÎ ÎÎÎ 1492-IFM40xx DIN rail mountable terminal block

Publication 1746-2.35

Page 9

Discrete Input and Output Modules

9

Fast Response Input Modules (1746-ITB16, -ITV16) The fast response DC input modules provide 16 input points and are designed for high-speed applications requiring fast response to input signals from DC sensing devices. When used with an SLC 5/03t or higher processor and the Discrete Input Interrupt (DII) instruction (100 msec polling), pulses can be read up to a frequency of 1K Hz. (It is 2K Hz if the input signals are from a gray code encoder.) Recommended wiring to an Allen-Bradley 845D Absolute Gray Code Encoder is provided on page 27. Both sinking and sourcing versions of the fast response input module are available.

High-Current Solid-State Output Modules (1746-OBP8, -OAP12, -OBP16, -OVP16).B High-current solid-state output modules expand application coverage for the SLC 500 by providing the following enhanced functionality: • increased current rating • fuse protection and diagnostics • high-speed switching • excellent reliability The high current solid state output modules expand application coverage in automotive, packaging, and material handling applications by allowing the SLC 500 processor to directly control solenoids, contactors, motors, and motor starter loads (up to size 5) with continuous current requirements of up to 1A at 60_C (1746-OAP12, -OBP16, -OVP16) and 2.0A at 60_C (1746-OBP8). 1746-OAP12, -OBP16, and -OVP16 modules also provide fuse protection and blown fuse diagnostics for increased up-time. The ac output module includes two replaceable fuses (one per common), which protect the module in the event of short circuits. 1746-OBP16 and -OVP16 output modules include a replaceable fuse on the common providing short circuit protection for wiring (16 AWG or larger) to external loads. A jumper can be set on these modules to provide CPU notification and system shutdown if the module fuse blows. The modules also include a blown fuse LED to assist I/O troubleshooting. Inductive load turn-off time for 1746-OBP8 (Series B and later), -OBP16 and -OVP16 DC output modules is reduced by 70% over standard 1746 DC output modules allowing fast application cycle times.

Publication 1746-2.35

Page 10

10

Discrete Input and Output Modules

Innovative heat sink design for the OAP12 allows heat to be dissipated through the chassis frame metal providing cool operation and excellent reliability. Blown Fuse LED OUTPUT

1 AMP TRIAC

FAC

OBP16 Replaceable Fuse (F1)

JP 1

SER

3 2 1

OUTPUT VOLTAGE

1.5 AMP/OUTPUT @ 30C 1.0 AMP/OUTPUT @ 60C

OUTPUT RATINGS

SA

20.4 – 26.4 –––––– –––

UL

Jumper for CPU Notification

Jumper Settings and Fuse Replacement Information:

WHEN FUSE OPENS 2

1 <–––– CPU CONTINUES 2 <––––––– CPU FAULTS

3

3

Î Î

6.4 AMP/MODULE

OBP16 & OVP16

SLC 500 OUTPUT MODULE

F U S E

CAT

8 12 9 13 10 14 11 15

SERIAL NO.

4 5 6 7

F1

0 1 2 3

2 CPU FAULTS

1 CPU CONTINUES

WHEN FUSE OPENS

2

F1

FUSE REPLACEMENT LITTLEFUSE 322010 A–B CAT. NO. 1746–F8 MADE IN U.S.A.

FUSE REPLACEMENT LITTLEFUSE 322010 A–B CAT. NO. 1746–F8

OVP16 Replaceable Fuse (F1)

Blown Fuse LED OUTPUT F U S E

1 AMP TRIAC

SER

3 2 1 JP 1

2.0A MAX @ 30 °C 1.25A MAX @ 55 °C 1.0A MAX @ 60 °C 240V MAX / 480 VA MAX 4.5A MAX/COMMON (MAX V.A. PER MODULE) 1440 VA

2 CPU FAULTS

1 CPU CONTINUES

Publication 1746-2.35

WHEN FUSE OPENS

2

Replaceable Fuse (F2)

WHEN FUSE OPENS 2

3

3 FUSE REPLACEMENT SAN–O HQ 6.3A A–B CAT. NO. 1746–F9 MADE IN U.S.A.

F2

Jumper Settings and Fuse Replacement Information:

OUTPUT RATINGS

ÎÎ ÎÎ

OAP12

OUTPUT VOLTAGE

85–265 VAC 50/60 HZ

UL SA

Replaceable Fuse (F1)

Jumper for CPU Notification

FAC

F1

SLC 500 OUTPUT MODULE

8 9 10 11

CAT

4 5 6 7

SERIAL NO.

0 1 2 3

1 <–––– CPU CONTINUES 2 <––––––– CPU FAULTS

FUSE REPLACEMENT SAN–O HQ 6.3A A–B CAT. NO. 1746–F9