For the Allen-Bradley 1746-ITV16

Page 11

Discrete Input and Output Modules

11

Electronically Protected Output Module (1746-OB16E) The 1746-OB16E is designed to electronically protect the module from a short circuit or overload condition. The protection is based on a thermal cut-out principle. In the event of a short circuit or overload on an output channel, that channel limits the current within milliseconds after its thermal cut-out temperature has been reached. All other channels continue to operate as directed by the processor. The 1746-OB16E lowers maintenance costs by eliminating the need to replace damaged modules and blown fuses. After the short circuit or overload condition is corrected, restore power and the module automatically resets and resumes control of the output channel. The 1746-OB16E provides a broad voltage range of 10 to 30V dc and a current rating of 1A at 30_C and 0.5A at 60_C making it the perfect solution for controlling 12V dc and 24V dc solenoid and lamp loads. The module is also equipped with an LED indicator that illuminates when the short circuit or overload condition occurs to expedite the troubleshooting process. Inductive load turn-off time for 1746-OB16E (Series B and later), output module is reduced by 70% over standard 1746 DC output modules allowing fast application cycle times. OUTPUT E F U S E

Front View

Important:

EFUSE LED

NOTE: There is no jumper setting on this module.

The module does not provide protection against reverse polarity wiring or wiring to AC power sources. Electronic protection is not intended to replace fuses, circuit breakers, or other code-required wiring protection devices.

Publication 1746-2.35

Page 12

12

Discrete Input and Output Modules

1746-OB16E Overload Protection The chart below describes overload protection for the 1746-OB16E. The electronic protection is based on a thermal cut-out temperature, which is reached more quickly (at lower overload current) when two to four adjacent channels are operating. The adjacent channel groupings are 0–3, 4–7, 8–11, and 12–15.

ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ

6

Overload Protection (Single channel operating at maximum rated current.)

Output Current (Amps)

5

4

3

Overload Protection (Two to four channels operating at maximum rated current.)

3.5A

Recommended Operating Current

0.5A

2

1

0 0

10

20

30

40

50

60

Operating Temperature (_C)

Important:

The 1746-OB16E performs auto-reset under overload conditions. The output channel limits current once its thermal cut-out temperature is reached. Once the overload condition occurs, the channel turns off and begins to cool. If the overload condition has not been be corrected, and the channel is turned back on, it will continue to drive the load for several seconds until the cut-out temperature is reached again.

1746-OB16E Short Circuit Protection The table below describes short circuit protection characteristics for the 1746-OB16E. Module turns on with existing short circuit condition

Module is on, then short circuit condition occurs

Turn Off Time

➀ (msec)

Peak Current (A)

Turn Off Time

➀ (msec)

Peak Current (A)

30 volts, 10A

1.4

18

1.3

60

10 volts, 10A

5.9

16

1.4

16

External Power Supply Rating

➀ This determination was made at 10_C. Turn off times are estimated to be 10 to 20 percent faster at 60_C.

Publication 1746-2.35

Page 13

Discrete Input and Output Modules

Terms and Symbols Used in the Specification Tables and Wiring Diagrams

13

Terms Backplane Current Draw the amount of current the module requires from the backplane. The sum of the backplane current draw for all modules in a chassis is used to select the appropriate chassis power supply. Continuous Current Per Module the maximum current for each module. The sum of the output current for each point should not exceed this value. Continuous Current Per Point the maximum current each output is designed to continuously supply to a load. Inrush Current the temporary surge current drawn when an input is initially energized. Minimum Load Current the lowest amount of current the output is designed to operate at. Operating at or below this value is not recommended. Nominal Input Current the current drawn at nominal input voltage. Off-State Current for input circuits, the maximum amount of leakage current allowed from an input device that will keep the SLCt input circuits in their off-state. Off-State Leakage for output circuits, the maximum amount of current present at the output terminal when the output circuit is in its off-state. Off-State Voltage (max) the maximum input voltage level detected as an off condition by the input module. On-State Voltage Drop the voltage developed across the output driver circuit during the on state at maximum load current. Operating Voltage for inputs, the voltage range needed for the input to be in the on-state. For outputs, the allowable range of user-supplied voltage. Points per Common the number of input or output points connected to a single return (common) or supply (vcc). Signal Delay for inputs, the response time required to transmit the circuit status from the field logic to the digital logic. For outputs, the time required to transmit the circuit status from digital logic to the output driver.

Publication 1746-2.35

Page 14

14

Discrete Input and Output Modules

Sinking/Sourcing describes a current signal flow relationship between field input and output devices in a control system and their power supply. Sourcing I/O modules supply (or source) current to sinking field devices. Sinking I/O modules receive (or sink) current from sourcing field devices. Surge Current the temporarily large current drawn by an inductive output device when it is initially energized. Surge Current Per Point the maximum amplitude and duration (pulse) of current an output can provide to an inductive output device. Voltage Category the nominal voltage used to describe the module.

I/O Wiring Symbols Symbol

Device Name 2-wire Input Device

3-wire Input Device

Solenoid Output

CR

Contact Relay Output

L

TTL Logic Output

Related Publications: Detailed wiring diagrams for 1746 input modules and Allen-Bradley Series 9000 Photoelectric Sensors are provided in Publication 42GR-7.4. Important:

Publication 1746-2.35

The wiring diagrams in this document are examples only. It is not necessary to connect an I/O device to every terminal on an I/O module’s terminal block.

Page 15

Discrete Input and Output Modules

15

Wiring Diagrams The 16-point I/O module wiring diagrams include both decimal and octal numbers for I/O addressing and wire identification. (See figure below.) The decimal numbers in the upper left portion of each box are used to wire your 16-point I/O module to an SLC system. The octal numbers in the lower right portion of the box are used for a PLCR system. (As shipped from the factory, the I/O module has a decimal address label on the inside of its door.) An octal label kit is included with your 16-point I/O modules or you can order a separate octal conversion kit to allow you to convert your module to the octal system. Important:

PLC systems use the octal lables. (See figure below.)

Directions on how to install the labels are included in publication number 1746-5.3, Discrete I/O Modules Installation Instructions. These instructions are provided in a kit that is shipped with each discrete I/O module.

1746-IA16 100/120V ac L1 IN 0 0

IN 1

2

IN 3

1

IN 2

3

IN 4 4

IN 5

6

IN 7

10

IN 9

5

IN 6 100/120V ac

7

IN 8

11

IN 10 12

IN 11

14

IN 13

13

IN 12 IN 14

15 16 IN 15 17

L2

AC COM AC COM

COMMONS CONNECTED INTERNALLY

SLC PLC

For SLC (decimal) IN 14

16 For PLC (octal)

Publication 1746-2.35

Page 16

16

Discrete Input and Output Modules

Specifications, Wiring, and Circuit Diagrams AC Input Modules (1746-IA4, -IA8, -IA16, -IM4, -IM8, -IM16) Catalog Number Specification

1746-IA4

1746-IA16 (RTB)

1746-IA8

1746-IM4

1746-IM8

1746-IM16 (RTB)

Voltage Category

100/120V ac

Operating Voltage

85 to 132V ac at 47 to 63 Hz

Number of Inputs

4

8

16

4

8

16

4

8

16

4

8

16

0.035A 0.0A

0.050A 0.0A

0.085A 0.0A

0.035A 0.0A

0.050A 0.0A

0.085A 0.0A

Points per Common 5V 24V

Backplane Current Draw

200/240V ac 170 to 265V acat 47 to 63 Hz

Signal Delay (max.)

on = 35 ms off = 45 ms on = 35 ms off = 45 ms

Off-State Voltage (max.)

30V ac

50V ac

Off-State Current (max.)

2 mA

2 mA

Nominal Input Current

12 mA at 120V ac

12 mA at 240V ac

➀ Inrush Current (max.)

0.8A

1.6A

500 msec

500 msec

➀ Inrush Current Time Duration (max.)

➀ An ac input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac input circuit will be affected. RTB = Removable Terminal Block.

On/Off-State Voltage Range + IN

0V ac

30V ac

0V ac

50V ac

–

Off-state COM

IA4, IA8, IA16

85V ac

IM4, IM8, IM16

170V ac

132V ac

ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ

265V ac

Input State Not Guaranteed

On-state

(Measure voltage from common terminal to input terminal.)

Circuit Diagrams 1746-IA4, IA8, IA16

1746-IM4, IM8, IM16 270

1870

AC COM 261

1µF

270

AC COM

1870 261

1µF

1M

1M

0.3µF

0.15µF IN

IN 270

270

1870 1µF

1µF

261 1M

1M

0.15µF

0.3µF IN

Publication 1746-2.35

1870

IN

261

Page 17

Discrete Input and Output Modules

17

Wiring Diagrams 1746-IA4

1746-IM4

100/120V ac

200/240V ac

NOT USED

1746-IA8

1746-IM8

100/120V ac

200/240V ac

L1

IN 0

NOT USED

IN 1

NOT USED

L1

100/120V ac (IA4) 200/240V ac (IM4)

IN 2

NOT USED

100/120V ac (IA8)

IN 3

IN 0

200/240V ac (IM8)

IN 4

IN 1

IN 5

IN 2

IN 6

IN 3

IN 7

AC COM

L2

AC COM

L2 COMMONS CONNECTED INTERNALLY

1746-IA16

1746-IM16

100/120V ac

200/240V ac

AC COM

L1 IN 0 0

IN 1

2

IN 3

4

IN 5

1

IN 2

3

IN 4

100/120V ac (IA16)

5

IN 6

200/240V ac (IM16)

6

IN 7

10

IN 9

7

IN 8

11

IN 10 12

IN 11

14

IN 13

13

IN 12

15

IN 14 16 IN 15

17 AC COM

L2

AC COM COMMONS CONNECTED INTERNALLY

SLC PLC

Publication 1746-2.35

Page 18

18

Discrete Input and Output Modules

AC Output Modules (1746-OA8, -OA16, -OAP12) Catalog Number Specification

1746-OA8

1746-OA16

➀

➀

1746-OAP12 (RTB)

(RTB)

Voltage Category

120/240V ac

Operating Voltage

85 to 265V ac at 47 to 63 Hz

Number of Outputs

8

16

12

Points per Common

4

8

6

0.185A 0.0A

0.370A 0.0A

0.370A 0.0A

5V 24V

Backplane Current Draw on = 1 ms off =11 ms

Signal Delay (max.)(Resistive Load)

➂ (max.)

Off-State Leakage

2 mA

Load Current (min.)

10 mA

➃

Per Point

Continuous Current

➀➁

(max.) Per Module On-State Voltage Drop (max.)

➄ (max.)

Surge Current per Point

1.0A at 30°C 0.50A at 60°C

0.50A at 30°C 0.25A at 60°C

8.0A at 30°C 4.0A at 60°C 1.50V at 1A

8.0A at 30°C 4.0A at 60°C 1.50V at 0.50A

10.0A for 25 ms

10.0A for 25 ms

2.0A at 30°C 1.25A at 55°C 1.0A at 60°C 9.0A at 30°C 6.0A at 60°C 1.2V at 2.0A per point – 17.0A for 25 ms per common – 35.0A for 10 ms

➀ Triac outputs turn on at any point in the ac line cycle and turn off at ac line zero cross. ➁ A fused common and blown fuse LED are provided on this module. (Fuses are designed to protect the module.) For replacement fuse, use catalog number 1746-F9 or SAN-O HQ 6.3A.

➂ To limit the effects of leakage current through triac outputs, a loading resistor can be connected in parallel with your load. For typical 120V ac applications, use a 15k ohm, 2W resistor. For typical 240V ac applications, use a 15k ohm, 5W resistor.

➃ Recommended surge suppression for triac outputs when switching 120V ac inductive loads is Harris MOV part number V220MA2A. See page 7 for more information on surge suppression.

➄ Repeatability is once every 1 second at 30°C. Repeatability is once every 2 seconds at 60°C. RTB = Removable Terminal Block.

Operating Voltage Range

ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 85V ac

0V ac

Operation Not Guaranteed

265V ac Recommended Operating Range

(Voltage is applied between L1 and L2.)

Important:

Publication 1746-2.35

If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100V ac even though the output is off.

Page 19

Discrete Input and Output Modules

19

Circuit Diagrams 1746-OA8, -OA16

1746-OAP12 L1 VAC

OUT OUT

OUT OUT

Wiring Diagrams 1746-OA8

1746-OA16

100–240V ac TRIAC OUTPUT

100–240V ac TRIAC OUTPUT L1

VAC 1

VAC 1

L1

OUT 3

2

OUT 3 3 OUT 4

100–240V ac CR CR

CR L2

CR

4

OUT 5 CR

OUT 1 OUT 2

0 1 OUT 2

100–240V ac

OUT 0

OUT0

OUT 1

5 OUT 6 CR

6

OUT 7 7

L2 VAC 2

L1

VAC 2

OUT 9

13 OUT 10

100–240V ac OUT 5 OUT 6 OUT 7

10

OUT 11

OUT 4 CR CR CR CR

L2

L1

11 OUT 8

100–240V ac

12

OUT 13 15 OUT 12 OUT 15

CR

14 17 OUT 14

CR

16 SLC

L2

PLC

1746-OAP12 100–240V ac HIGH CURRENT TRIAC OUTPUT COMMONS CONNECTED INTERNALLY

VAC 1

L1

VAC 1

OUT 1 1 CR 100–240V ac CR

OUT 3 OUT 5

OUT 0 0

3 OUT 2 5 OUT 4

NOT USED

2 4

CR

NOT USED

L2 L2 OUT 7 CR CR

SLC PLC

7 OUT 6 6 11 OUT 8 10 OUT 11 13 OUT 10 12 VAC 2 VAC 2 OUT 9

100–240V ac

CR L1

COMMONS CONNECTED INTERNALLY

Publication 1746-2.35

Page 20

20

Discrete Input and Output Modules

Sinking DC Input Modules (1746-IB8, -IB16, -ITB16, -IB32) Catalog Number Specification

1746-IB16 (RTB)

1746-IB8

1746-ITB16 (RTB) (Fast Response)

1746-IB32

➀

Voltage Category

24V dc sink

Operating Voltage

10 to 30V dc sink

Number of Inputs

8

16

16

15 to 30V dc at 50°C sink 15 to 26.4V dc at 60°C sink 32

8

16

16

8

0.050A 0.0A

0.085A 0.0A

0.085A 0.0A

0.106A 0.0A

Signal Delay (max.)

on = 8 ms off = 8 ms on = 8 ms off = 8 ms on = 0.3 ms off = 0.5 ms on = 3 ms off = 3 ms

Off-State Voltage (max.)

5V dc

5V dc

5V dc

5V dc

Off-State Current (max.)

1 mA

1 mA

1.5 mA

1.6 mA

Nominal Input Current

8 mA at 24V dc

Points per Common 5V 24V

Backplane Current Draw

➁

➀ The 32-point input modules are fused to protect external wiring, one fuse per common. These fuses are non-replaceable and are rated at 2.5A. ➁ Typical signal delay for these modules: on=0.10 ms, off=0.25 ms at 24V dc. RTB = Removable Terminal Block.

On/Off-State Voltage Range + IN

0V dc

5V dc

10V dc

IB8, IB16, ITB16

0V dc 0V dc

5V dc 5V dc

15V dc 15V dc

IB32

– Off-state COM (Measure voltage from common terminal to input terminal.)

Publication 1746-2.35

ÉÉÉÉ ÉÉÉÉ Input State Not Guaranteed

On-state

30V dc 30V dc at 50°C 26.4V dc at 60°C