Discrete Input and Output Modules
41
Operating Voltage Range (For ac operation: voltage is applied between L1 and L2.) (For dc operation: voltage applied is between +VDC and DC common.)
ÉÉ ÉÉ ÉÉ
0 V 5V ac 0 V 5V dc
265V ac 125V dc Recommended Operating Range
Operation Not Guaranteed
Circuit Diagram VAC/VDC
VAC/VDC
OUT
OUT
1746-OX8
1746-OW4, OW8, OW16
VDC/VAC
OUT
OUT
Wiring Diagrams 1746-OW4
1746-OW8
RELAY OUTPUT
RELAY OUTPUT
. VAC–VDC
L1 or +DC
L1 or +DC
VAC–VDC 1
OUT 0
OUT 0 V ac/dc
V ac/dc
OUT 1
OUT 1
OUT 2
CR
OUT 3
CR
L2 or –DC
OUT 3
CR
VAC VDC 2
NOT USED
OUT 4
NOT USED
OUT 5
L2 or –DC L1 or +DC
V ac/dc
1746-OW16
OUT 6
CR
OUT 7
CR
L2 or –DC
1746-OX8
RELAY OUTPUT
ISOLATED RELAY OUTPUT
L1 or +DC
VAC–VDC OUT0 1 0 OUT 1 1 OUT 2 3 OUT 4 OUT 5 CR
4 5 OUT 6 6
OUT 7 CR
CR CR
7
L2 or –DC VAC–VDC 2 11 OUT 8 10 OUT 11 OUT 10 13 OUT 13 12 15 OUT 12 OUT 15 14 17 OUT 14 16
CR
VAC–VDC 0
VS1 L1
VAC–VDC 1
VS2 VDC
VAC–VDC 2
VS3 VDC
VAC–VDC 3
L1 or +DC
OUT 9
CR
VS0 L1
2
OUT 3
V ac/dc
PLC
CR
NOT USED
NOT USED OUT NOT7 USED
SLC
OUT 2
NOT USED VS4 L1
VAC–VDC 4
VS5 L1
VAC–VDC 5
OUT 0
CR CR L2 or –DC
VS6 VDC
VAC–VDC 6
VS7 VDC
VAC–VDC 7
VS0 L2
OUT 1
VS1 L2
OUT 2
VS2 DC COM
OUT 3
CR
VS3 DC COM
CR
VS4 L2
NOT USED OUT 4
V ac/dc
CR
OUT 5
VS5 L2
OUT 6
VS6 DC COM
OUT 7
CR
VS7 DC COM
Publication 1746-2.35
Page 42
42
Discrete Input and Output Modules
Combination Modules (1746-IO4, -IO8, -IO12) Catalog Number Specification
1746-IO4
1746-IO12 (RTB)
1746-IO8
Voltage Category inputs – 120V ac outputs – ac/dc Relay
Operating Voltage inputs – 85 to 132V ac at 47 to 63 Hz outputs – 5 to 265V ac at 47 to 63 Hz / 5 to 125V dc
Points per Common
2
4
6
2 inputs / 2 outputs
4 inputs / 4 outputs
6 inputs / 6 outputs
0.030A 0.025A
0.060A 0.045A
0.090A 0.70A
Continuous Current per Module
4.0A
8.0A
8.0A
Specification Reference input same as 1746-IA4 output same as 1746-OW4 input same as 1746-IA4 output same as 1746-OW4 input same as 1746-IA16 output same as 1746-OW16
Points per Module 5V 24V
Backplane Current Draw
RTB = Removable Terminal Block
On/Off-State Voltage Range (AC Inputs)
IN
–
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ
30V ac
0V ac
+
Off-state
85V ac
Input State Not Guaranteed
132V ac On-state
COM (Measure voltage from common terminal to input terminal.)
Operating Voltage Range (AC/DC Relay Outputs) (For ac operation: voltage is applied between L1 and L2.) (For dc operation: voltage is applied between +VDC and DC common.)
Publication 1746-2.35
0 V 5V ac 0 V 5V dc
ÉÉ ÉÉ
Operation Not Guaranteed
265V ac 125V dc Recommended Operating Range
Page 43
Discrete Input and Output Modules
43
Circuit Diagram V ac Input 270
Relay Output
1870 VAC/VDC
AC COM 261
1µF 1M
OUT 0.3µF IN
270
1870
1µF
OUT
261
1M 0.3µF IN
Wiring Diagrams 1746-IO4 100/120V AC INPUT
1746-IO8
RELAY OUTPUT
100/120V AC INPUT L1 or +DC
VAC–VDC OUT 0 OUT 1
L1
OUT 0 V ac/dc
L2 or –DC
OUT 1
NOT USED
OUT 2
CR
NOT USED
OUT 3
CR
L1
IN 0
L2
L2 or –DC
IN 0
IN 1 100/120 V ac
L1 or +DC
VAC–VDC
V ac/dc CR
RELAY OUTPUT
IN 1 100/120 V ac
NOT USED NOT USED OUT 7 AC COM
IN 2 IN 3 OUT 7 AC COM
L2
1746-IO12 100/120V AC INPUT L1 or +DC
RELAY OUTPUT
VAC–VDC OUT 0 OUT 1 OUT 2 V ac
OUT 3 OUT 4 CR
OUT 5
L2 or –DC
CR
NOT USED
L1 NOT USED
IN 0
IN 1 IN 2 100/120 V ac
IN 3 IN 4 IN 5
L2
NOT USED
NOT USED AC COM
Publication 1746-2.35
Page 44
44
Discrete Input and Output Modules
Fixed I/O Chassis Module Compatibility
The following chart depicts the range of current combinations supported by the fixed I/O expansion chassis. To use it, you must first determine the backplane current draw and operating voltage for both of the modules you plan to use in the chassis. You can get these specifications from the Power Supply Loading table on page 45. Next, plot each of the currents on the chart below. If the point of intersection falls within the operating region, your combination is valid. If not, your combination cannot be used in a 2-slot, fixed I/O chassis.
450
Example: Plot IN16 and NIO4V IN16 = 0.085A at 5V dc and 0A at 24V dc. NIO4V = 0.055A at 5V dc and 0.115A at 24V dc
400 350
2. Plot this point on the chart above (140 mA at 5V dc).
300
4. Plot current draw at 24V dc (115mA at 24V dc).
Current (mA) at 5V dc
1. Add current draws of both modules at 5V dc to get 0.14A (140 mA).
3. Add current draws of both modules at 24V dc to get 0.115A (115 mA).
OA16 and IA16 (0, 455)
250 200
OW16 and IA16 (180, 255) Valid Operating Region
150
5. Note the point of intersection on the chart above (marked x). This combination falls within the valid operating region for your fixed I/O chassis.
x
Plotted from Example Shown Below
100 50
50
100
150
200
Current (mA) at 24V dc
Important:
The NO4I and NO4V analog output modules may require an external power supply. Refer to your analog user’s manual.
Important:
There are certain conditions that affect the compatibility characteristics of the BASIC module (BAS) and the DH-485/RS-232C module (KE). When you use the BAS module or the KE module to supply power to a 1747-AIC Link Coupler, the Link Coupler draws its power through the module. The higher current drawn by the AIC at 24V dc is calculated and recorded in the tables for the modules identified as BASn (BAS networked) or KEn (KE networked). Make sure to refer to these modules if your application uses the BAS or KE module in this way.
Publication 1746-2.35
Page 45
Discrete Input and Output Modules
45
Power Supply Loading
Hardware Component
Catalog Numbers
Maximum Current at 5V (Amps)
Maximum Current at 24V (Amps)
1746-IA4
0.035
1746-IA8
Maximum Current at 24V (Amps)
0
1746-OA8
0.185
0
0.050
0
1746-OA16
0.370
0
0.170
0
➀ 1746sc-IA8I
0.110
0
➀ 1746sc-OAP8I
1746-IA16
0.085
0
1746-OAP12
0.370
0
1746-IB8
0.050
0
1746-OB8
0.135
0
➀ 1746sc-IB8I
0.110
0
1746-OB16
0.280
0
1746-IB16
0.085
0
1746-OB16E
0.135
0
1746-IB32
0.106
0
1746-OB32
0.452
0
0.110
0
1746-OBP8
0.135
0
1746-IC16
0.085
0
1746-OBP16
0.250
0
1746-IG16
0.140
0
1746-OG16
0.180
0
1746-IH16
0.085
0
1746-OV8
0.135
0
1746-IM4
0.035
0
1746-OV16
0.270
0
1746-IM8
0.050
0
1746-OV32
0.452
0
➀ 1746sc-IM8I
0.110
0
1746-OVP16
0.250
0
1746-IM16
0.085
0
1746-OW4
0.045
0.045
1746-IN16
0.085
0
1746-OW8
0.085
0.090
1746-ITB16
0.085
0
1746-OW16
0.170
0.180
1746-ITV16
0.085
0
1746-OX8
0.085
0.090
1746-IV8
0.050
0
1746-IO4
0.030
0.025
1746-IO8
0.060
0.045
1746-IO12
0.090
0.070
1746sc-IC8I Discrete Input Modules
Catalog Numbers
Maximum Current at 5V (Amps)
Hardware Component
➀
1746-IV16
0.085
0
1746-IV32
0.106
0
Discrete Output Modules
Discrete Input & Output Modules
➀ Sold and supported by Spectrum Controls, Inc., Bellevue, WA. For additional information contact Spectrum at (206)746-9481.
Publication 1746-2.35
Page 46
46
Discrete Input and Output Modules
Discrete I/O Power Dissipation
The table below lists the power dissipation for the discrete I/O modules operating at nominal voltage. The following terms are used in the Power Dissipation table: Watts per Point
Minimum Watts
Total Watts
The heat dissipation that can occur in each field wiring point when energized at nominal voltage.
The amount of heat dissipation that can occur when there is no field power present.
The watts per point plus the minimum watts (with all points energized).
For examples on calculating system heat dissipation, refer to the SLC 500 Modular Hardware Style Installation and Operation User Manual (Publication 1747-6.2) or the SLC 500 Fixed Hardware Style Installation and Operation User Manual (Publication 1747-6.21).
Power Dissipation Catalog Numbers
Watts per Point
Minimum Watts
1746-IA4
0.27
0.175
1.30
1746-OA8
1.000
0.925
9.00
1746-IA8
0.27
0.250
2.40
1746-OA16
0.462
1.850
9.30
0.43
0.550
4.00
1746sc-OAP8I
1.125
0.850
9.85
1746-IA16
0.27
0.425
4.80
1746-OAP12
1.000
1.850
10.85
1746-IB8
0.20
0.250
1.90
1746-OB8
0.775
0.675
6.90
0.31
0.550
3.00
1746-OB16
0.338
1.40
7.60
1746-IB16
0.20
0.425
3.60
1746-OB16E
0.150
0.675
3.07
1746-IB32
0.20
0.530
6.90
1746-OB32
0.078
2.26
4.80
0.49
0.550
4.50
1746-OBP8
0.300
0.675
3.08
1746-IC16
0.22
0.425
3.95
1746-OBP16
0.310
1.250
6.26
1746-IG16
0.02
0.700
1.00
1746-OG16
0.033
0.900
1.50
1746-IH16
0.32
0.217
5.17
1746-OV8
0.775
0.675
6.90
1746-IM4
0.35
0.175
1.60
1746-OV16
0.388
1.400
7.60
1746-IM8
0.35
0.250
3.10
1746-OV32
0.078
2.26
4.80
➀ 1746sc-IM8I
0.76
0.550
6.60
1746-OVP16
0.310
1.250
6.26
1746-IM16
0.35
0.425
6.00
1746-OW4
0.133
1.310
1.90
1746-IN16
0.35
0.425
6.00
1746-OW8
0.138
2.590
3.70
1746-ITB16
0.20
0.425
3.60
1746-OW16
0.033
5.170
5.70
1746-ITV16
0.20
0.425
3.60
1746-OX8
0.825
2.590
8.60
0.75
1.60
1746sc-IA8I
1746sc-IB8I
➀
➀
1746sc-IC8I
➀
Total Watts
Catalog Numbers
Watts per Point
➀
Minimum Watts
Total Watts
1746-IV8
0.20
0.250
1.90
1746-IO4
0.27 per input point 0.133 per output point
1746-IV16
0.20
0.425
3.60
1746-IO8
0.27 per input point 0.133 per output point
1.38
3.00
1746-IV32
0.20
0.530
6.90
1746-IO12
0.27 per input point 0.133 per output point
2.13
4.60
➀ Sold and supported by Spectrum Controls, Inc., Bellevue, WA. For additional information, contact Spectrum at (206) 746-9481.
Publication 1746-2.35
Page 47
Discrete Input and Output Modules
Environmental Specifications
47
➀
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
–40°C to 85°C (–40°F to 185°F)
Operating Humidity
5% to 95% (non-condensing)
Noise Immunity
NEMA standard ICS 2–230
Vibration (Operating)
Displacement 0.015 inch peak at 5–57 Hz. Acceleration 2.5Gs at 57–2000 Hz
Shock (Operating)
30Gs (all modules except relay contact). 10Gs (relay contact modules, 1746-OW, -OX, I/O Combo).
Isolation
➁
Certification
1500 Volts
➂➃
UL listed. CSA or C-UL approved as indicated by product markings. CE compliant for all applicable directives when product or packaging is marked.
Hazardous Environment Class
➃ Class I, Division 2, Groups A, B, C, D Hazardous Environment
➀ Exceptions are indicated with certain modules. ➁ Electro-optical isolation between I/O terminals and control logic ➂ Some modules are not CE marked. See page 2. ➃ All modules meet Class I, Division 2 requirements for hazardous location. Some modules are rated Class I, Division 2 by CSA only. See page 2.
Accessories
The following accessories are available for use with discrete I/O modules: Catalog Number
Item
Description
1746-N2
Modular chassis slot filler
Helps prevent debris from entering the SLC enclosure that can cause shorts or improper operation.
1492-IFMxx
Feed-through interface modules
Connects electronic wiring (discrete I/O modules, particularly 16- and 32-point) to electric wiring (factory devices). Available with either 20 or 40 terminals.
1492-CABLExx
Cables: – 1 m. (3.3 ft.) – 2.5 m. (8.2 ft.) – 5 m. (16.4 ft.)
Connects directly to the 1492-IFMxx interface module and is available with a removable terminal block or a ready-to-wire free end.
Connector kit
This kit allows you to create your own cable (3.2 meters max.) if the Catalog Number 1746-C15 cable is not long enough. It contains one female connector and 45 crimp contacts. Note: 32-point modules are shipped with one connector kit.
1746-N3
Publication 1746-2.35
Page 48
Allen-Bradley Support
In today’s competitive environment, when you buy any product, you expect that product to meet your needs. You also expect the manufacturer of that product to back it up with the kind of customer service and product support that will prove you made a wise purchase. As the people who design, engineer and manufacture your Industrial Automation Control equipment, Allen-Bradley has a vested interest in your complete satisfaction with our products and services. Allen-Bradley offers support services worldwide, with 75 Sales/Support offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States, plus Allen-Bradley representatives in every major country in the world. Contact your local Allen-Bradley representative for:
• • • • sales and order support product technical training warranty support support service agreements
PLC, PLC-2, PLC-3, and PLC-5 are registered trademarks of Rockwell Automation. SLC, SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, SLC 5/05, Data Highway Plus, and PanelView are trademarks of Rockwell Automation. A.I. Series and RSLogix 500 are trademarks of Rockwell Software Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1746-2.35 – March 1998 Supersedes Publication 1746-2.35 – December 1996
Publication 1746-2.35
E 1998 Rockwell International Corporation. All rights reserved. Printed in USA.