Page 41
SLC 500 Digital I/O Modules
41
(8)
Fast turn-off modules (1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16) provide fast OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin 100-B110 (24Ws sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.
(9)
Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.
(10)
Surge current = 32 A per module for 10 ms.
ATTENTION: A transient pulse occurs in transistor outputs when the external DC supply voltage is applied to the output common terminals (for example, via the master control relay). This can occur regardless of the processor having power or not. For most applications, the energy of this pulse is not sufficient to energize the load. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for more information on transient pulses and guidelines to reduce inadvertent processor operation.
Specifications – 1746-OG16 Attribute
Value(1)
Voltage category
5V DC TTL Signal Input (sinking)
Number of outputs
16
Points per common
16
Voltage, operating (V DC to DC COM)
4.5...5.5V DC(2) 50 mV peak to peak ripple, max.
Backplane current consumption
5V DC
0.180 A
24V DC
0.0 A
Signal delay, max resistive load
On = 0.25 mA Off = 0.50 mA
Off-state voltage
4.5...5.5V DC
Off-state leakage, max
0.1 mA
Load current, min
0.15 mA
Continuous current per point
24 mA
(1)
Removable terminal block.
(2)
TTL outputs are inverted (0...0.4V DC = low voltage = True = ON). Use a NOT instruction in your ladder program to convert to traditional True = High logic.
Publication 1746-IN027D-EN-P - December 2012
Page 42
42
SLC 500 Digital I/O Modules
ATTENTION: To avoid potential damage to TTL modules, handle them by the ends of the module, not metallic surfaces. Electrostatic discharges can damage the module. Take care to prevent exposure of terminals or components to electrostatic charges.
Careful wire routing within the enclosure helps cut down electrical noise between I/O lines. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for recommended wiring procedures for TTL modules. Limit cable length to 3 m (10 ft) per point for outputs in standard environments. Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines, publication 1770-IN041, for complete information.
Relay Contact Modules WARNING: Exposure to some chemicals may degrade the sealing properties of materials used in the following devices: Relay Epoxy. Catalog
Relay
1746-OX8
K1…K8
1746-IO4
K1 and K2
1746-IO8
K1…K4
1746-IO12
K1…K6
1746-IO12DC
K1…K6
1746-OW4
K1…K4
1746-OW8
K1…K8
1746-OW16
K1…K16
It is recommended that the user periodically inspect these devices for any degradation of properties and replace the module if degradation is found.
Specifications – 1746-OW4, 1746-OW8, 1746-OW16, and 1746-OX8 Attribute
Value 1746-OW4(2)
1746-OW8(2)
1746-OW16(2)(3)
1746-OX8(2)(3)
Voltage category
AC/DC Relay
Number of outputs
4
8
16
8
Points per common
4
4
8
Individually isolated
Publication 1746-IN027D-EN-P - December 2012
Page 43
SLC 500 Digital I/O Modules
43
Specifications – 1746-OW4, 1746-OW8, 1746-OW16, and 1746-OX8 Attribute
Value 1746-OW4(2)
Voltage, operating
5V DC
5...125
24V DC
5...265
1746-OW8(2)
1746-OW16(2)(3)
1746-OX8(2)(3)
Signal delay, max resistive load
On = 10.0 ms Off = 10.0 ms
Backplane current consumption
0.045 A
0.085 A
0.170 A
0.085 A
0.045 A
0.090 A
0.180 A
0.090 A
16.0 A AC 8.0 A /Common
(4)
5V DC 24V DC
Off-state leakage, max
0 mA
Load current, min
10 mA @ 5V DC
Continuous current per point(1)
See Relay Contact Ratings on page 43.
Continuous current per module
8.0 A AC 8.0 A /Common
16.0 A AC 8.0 A /Common
(1)
Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication 1747-UM011. Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.
(2)
Certified for Class 1, Division 2 hazardous location by CSA.
(3)
Removable terminal block.
(4)
The continuous current per module must be limited so the module power does not exceed 1440V A.
Relay Contact Ratings Relay Contact Ratings – 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC Voltages
Amperes(1) Make
Break 1.5
Amperes(1) Continuous
Volt-Amperes Make
Break
2.5
1800
180
Volts (AC), max
120
15
240
7.5
Volts (DC), max
125
0.22
(2)
1.0
28
24
1.2(2)
2.0
28
0.75
(1)
The continuous current per module must be limited so the module power does not exceed 1440V A.
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28VA by the applied DC voltage. For example, 28V A/48V DC = 0.58 A. For DC voltage applications less than 14V, the make/break ratings for relay contacts cannot exceed 2 A.
Publication 1746-IN027D-EN-P - December 2012
Page 44
44
SLC 500 Digital I/O Modules
Relay Contact Ratings – 1746-OX8 Voltages
Volts (AC), max
Volts (DC), max
Amperes
Amperes(1) Make
Break
120
30
3.0
240
15
Continuous(3)
Volt-Amperes Make
Break
5.0
3600
360
125
0.22
(2)
1.0
28
24
1.2(2)
2.0
28
1.5
(1)
Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication 1747-UM011. Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28V A by the applied DC voltage. For example, 28V A/48V DC = 0.58 A. For DC voltage applications less than 14V, the make/break ratings for relay contacts cannot exceed 2 A.
(3)
The continuous current per module must be limited so the module power does not exceed 1440V A.
Publication 1746-IN027D-EN-P - December 2012
Page 45
SLC 500 Digital I/O Modules
45
Combination Input/Output Modules Specifications – 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC Attribute
Value 1746-IO4(1)(2)
1746-IO8(1)(2)
1746-IO12(1)(3)(4)
1746-IO12DC(3)(5)(6)(7)
2 inputs 2 outputs
4 inputs 4 outputs
6 inputs 6 outputs
6 inputs 6 outputs
Points per common
2
4
6
Voltage category
120V AC
24V DC
Voltage, operating (inputs)
85...132V AC
10...30V DC
Voltage category (outputs)
100/120V AC Relay contact output
Voltage, operating (outputs)
5...265V AC 5...125V DC
Backplane current consumption
5V DC
0.030 A
0.060 A
0.090 A
0.080 A
24V DC
0.025 A
0.045 A
0.070 A
0.060 A
Points per module
6
(1)
Certified for Class 1, Division 2 hazardous location by CSA.
(2)
See specifications for catalog numbers 1746-IA4 and 1746-OW4. Continuous Current per 1746-IO4 Module is 4.0 A. Continuous Current per 1746-IO8 Module is 8.0 A.
(3)
Removable terminal block.
(4)
See specifications for catalog numbers 1746-IA16 and 1746-OW16. Continuous Current per 1746-IO12 Module is 8.0 A.
(5)
See specification for catalog numbers 1746-IB16 and 1746-OW16. Continuous Current per 1746-IO12DC Module is 8.0 A.
(6)
Certified for Class 1, Division 2 hazardous location by C-UL.
(7)
Use the following ID Code when configuring your system with programming software or the HHT: 1746-IO12DC = 1512.
TIP
For combination I/O modules 1746-IO4, 1746-IO8, 1746-IO12 and 1746-IO12DC):
The first several seconds of any powerup or when power is applied to a rack that is not under processor control, the output LED indicators of the combination input and output modules in the rack will be illuminated. Racks are not under processor control if one of the following conditions exist: • Modular Hardware Style (only): Processor is absent from the rack or the rack interconnect cable is not properly connected. • Modular Hardware Style and Fixed Hardware Style: The processor does not have the firmware PROM installed or the processor is not functioning properly.
Publication 1746-IN027D-EN-P - December 2012
Page 46
46
Notes:
Publication 1746-IN027D-EN-P - December 2012
SLC 500 Digital I/O Modules
Page 47
SLC 500 Digital I/O Modules
47
Notes:
Publication 1746-IN027D-EN-P - December 2012
Page 48
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States
1.440.646.3434 Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for the return procedure.
Allen-Bradley, Rockwell Automation, SLC 500, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1746-IN027D-EN-P - December 2012 Supersedes Publication 1746-IN027C-EN-P - August 2008
PN-185007 Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.