Manual · Allen-Bradley
SLC 500 Digital I/O Modules Installation Instructions
Manual48 pagesPDF 1.2 MB
Installation instructions for Allen-Bradley SLC 500 digital I/O modules, including the 1746-OX8 isolated relay output module.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation instructions covering the SLC 500 digital input, output and combination I/O modules, from the 1746-IA4 to the 1746-OX8 and 1746-IO12DC. It explains hazardous location approval, environment and enclosure needs, static protection, installing and removing a module, octal labels, removable terminal blocks, recovery from a blown fuse, fuse replacement, the electronically protected 1746-OB6EI and 1746-OB16E, a wiring diagram for each module and full specifications.
Its parts
- Important User Information
- North American Hazardous Location Approval
- Environment and Enclosure
- Prevent Electrostatic Discharge
- Install and Remove the Module
- Octal Label Kit Installation
- Removable Terminal Blocks
- Wiring Diagrams
- Specifications
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1746-IN027D-EN-P) for the SLC 500 digital I/O modules: inputs such as the 1746-IA4 and 1746-IB16, outputs such as the 1746-OA8, 1746-OW16 and 1746-OX8, and the 1746-IO4, 1746-IO8, 1746-IO12 and 1746-IO12DC combination modules. It explains installing a module in the chassis, wiring its terminal block and fitting octal labels, with wiring diagrams and specifications for each module. For the 1746-OX8 it gives the wiring of its eight channel-to-channel isolated relay outputs and its ratings.
- Device type
- SLC 500 AC/DC relay output module, channel-to-channel isolated p. 27, 42
- Outputs
- 8 relay outputs, individually isolated p. 42
- Signal delay
- On 10.0 ms, off 10.0 ms (max, resistive load) p. 43
- Leakage and minimum load
- Off-state leakage 0 mA max; minimum load current 10 mA @ 5V DC p. 43
- Operating temperature
- 0...60 °C (32...140 °F); nonoperating -40...85 °C p. 29
- Heat dissipation
- 0.825 W per point, 2.590 W minimum, 8.60 W total p. 31
- Module power limit
- Continuous current per module limited so module power does not exceed 1440 VA p. 44
- DC contact rating
- DC make/break amperes = 28 VA divided by the applied DC voltage; below 14 V, at most 2 A p. 44
- Isolation
- 1500V, electro-optical between I/O terminals and control logic p. 29
- Terminal block
- Removable terminal block p. 43
- Wiring
- Max 2 mm2 (14 AWG), max 2 wires per terminal, max torque 0.9 Nm (8 lb-in.) p. 5
- Shock
- 10 g operating (relay contact modules, including 1746-OX8) p. 29
- Relays
- K1…K8 p. 42
- Humidity
- 5...95% operating, noncondensing p. 29
What this manual walks you through
- Installing and removing a module in an SLC 500 chassis p. 5
- Applying the octal filter and door labels p. 6
- Removing a colored terminal block p. 6
- Wiring the eight isolated relay outputs of the 1746-OX8 p. 27
- Calculating module heat dissipation p. 29, 31
- Relay contact ratings for the 1746-OX8 p. 44
Good to know
- Never install, remove or wire modules with power applied to the chassis. p. 5
- The first chassis slot is reserved for the processor or the 1747-ASB module. p. 5
- Some chemicals may degrade the relay epoxy; inspect the relays periodically and replace the module if degradation is found. p. 42
- Surge suppressors across external inductive loads extend the life of the relay contacts. p. 44
- Cover unused chassis slots with the 1746-N2 card slot filler. p. 5
Questions this manual answers
How many outputs does the 1746-OX8 have?
Eight relay outputs, each individually isolated. p. 42
How much heat does a 1746-OX8 dissipate?
8.60 W total with all points energized, from 0.825 W per point plus 2.590 W minimum. p. 31
What wire size fits the 1746-OX8 terminals?
Up to 2 mm2 (14 AWG), at most 2 wires per terminal, tightened to 0.9 Nm (8 lb-in.) max. p. 5
What is the operating temperature of the 1746-OX8?
0...60 °C (32...140 °F), measured in the air around the SLC 500 system. p. 29
How do I work out the DC current rating of the 1746-OX8 contacts?
Divide 28 VA by the applied DC voltage; for example 28 VA / 48 V DC = 0.58 A. p. 44
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1746-IN027D-EN-P SLC 500 Digital I/O Modules Installation Instructions1
- Important User Information2
- North American Hazardous Location Approval3
- Environment and Enclosure4
- Prevent Electrostatic Discharge4
- Install and Remove the Module5
- Octal Label Kit Installation (for PLC processors only)6
- Apply the Octal Filter Label6
- Apply the Octal Door Label6
- Removable Terminal Blocks6
- Wiring Diagrams17
- Specifications29
- Back Cover48
The whole text · 5 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file