The text of a manual · part 2 of 5
SLC 500 Digital I/O Modules Installation Instructions, pages 11 to 20
Pages 11 to 20 of 48
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1746-OX8
Page 11
SLC 500 Digital I/O Modules
11
Processor Operation in Case of Blown Fuse – Processor Continues The factory set position for JP1 is shown in the following diagram. For this JP1 configuration the processor operation will continue if the module fuse blows. JP1 3
JP1 is in Factory Set position. There is no processor notification for blown fuse.
2 1 1746-OBP16 and 1746-OVP16
3
2
1 JP1
1746-OAP12
Processor Operation in Case of Blown Fuse – Processor Faults The Processor Fault position for JP1 is shown on the following page. For this JP1 configuration, the processor generates a nonrecoverable error for all SLC 500 processors. For a nonrecoverable error, note the following: • • • •
Processor operation halts and the processor fault light flashes. All outputs are reset to OFF. The processor major fault bit S:1/13 is set. Monitor processor status file word S:6 for error code xx58 for SLC 500, and SLC 5/01 processors, and error code xx60 for SLC 5/02 and later processors.
Publication 1746-IN027D-EN-P - December 2012
Page 12
12
SLC 500 Digital I/O Modules
JP1 in Processor Fault Notification Position
JP1 3 2 1 1746-OBP16 and 1746-OVP16
3
2
1
JP1 is in processor fault position. Processor is notified when fuse is blown.
1746-OAP12 JP1
IMPORTANT
When using SLC 5/02 processor and later processors, a user-fault routine cannot be used to clear the major fault bit.
ATTENTION: For 1746-OBP16 and 1746-OVP16 modules, all outputs on the module are OFF if the fuse blows. For the 1746-OAP12 module, all outputs on the same common as the blown fuse are OFF. If processor operation is allowed to continue after a blown fuse, extreme care should be taken to be sure the safety of personnel and guard against equipment damage.
For additional information on processor fault codes and user-fault routines refer to the following publications: • Your programming device’s reference manual • HHT User Manual, publication 1747-NP002: • Chapter 28, Troubleshooting Faults • Chapter 29, Understanding the Fault Routine
Publication 1746-IN027D-EN-P - December 2012
Page 13
SLC 500 Digital I/O Modules
13
The following table defines operation of all SLC 500 processors in the case of a blown fuse in 1746-OBP16, 1746-OVP16, and 1746-OAP12 modules.
Processor Operation After a Blown Fuse (1746-OBP16, 1746-OVP16, and 1746-OAP12 modules) JP1 Set to Processor Continues
JP1 Set to Processor Faults
No error. Processor continues with 1746-OBP16 and 1746-OVP16 outputs de-energized. 1746-OAP12 outputs, on the same common as the blown fuse, are de-energized.
Nonrecoverable error. Processor operations stop and all outputs reset to OFF.
Recovery From Blown Fuse/Processor Fault/Processor Shutdown Processor operation will stop under the following conditions: • The output module fuse blows due to a short circuit. • JP1 is set to the Processor Faults position (pins 2 and 3 connected). If the above conditions occur, the following procedures should be used for recovery. 1. Follow fuse replacement procedures described on page 14. 2. Clear the processor major fault bit S:1/13. 3. Clear processor status file S:6 major error code (optional). 4. Return the processor to Run mode. For additional information on processor fault codes and clearing processor fault bits, refer to the following user manuals: • Your programming device’s reference manual • HHT User Manual, publication 1747-NP002 • Chapter 28, Troubleshooting Fault • Chapter 29, Understanding the Fault Routine
Replacement Fuse Recommendations Use the following replacement fuses: • 1746-OBP16 and 1746-OVP16 modules – Littelfuse #322010,10A or #332010,10A. This fuse is required to maintain UL/CSA rating. Replacement Fuse Kit is catalog number 1746-F8 (five fuses per kit). • 1746-OAP12 module - Use SAN-O HQ 6.3A for replacement. This fuse is required to maintain UL/CSA rating. Replacement Fuse Kit is catalog number 1746-F9 (five fuses per kit).
Publication 1746-IN027D-EN-P - December 2012
Page 14
14
SLC 500 Digital I/O Modules
Replace Fuses ATTENTION: Never install, remove, or wire modules with power applied to chassis.
1. Remove SLC 500 system power and correct the conditions causing the short circuit. 2. Remove the output module from the chassis. 3. Remove the fuse. • 1746-OBP16 and 1746-OVP16 modules: Use a wide-tipped, slotted-head screwdriver to remove the blown fuse. Slide the screwdriver tip under the fuse and use a twisting motion to pry the fuse from the fuse clip. Use care so that the printed circuit board and surrounding electronics are not damaged. • 1746-OAP12 module: A fuse holder is provided with each fuse. Simply grasp the fuse holder with needle-nose pliers, or your fingers, and pull it out. 4. Replace the fuse. • 1746-OBP16 and 1746-OVP16 modules: Center the replacement fuse over the fuse clip and press down. If you use a tool to press the fuse in place, apply pressure to the metal end caps only, not the center of the fuse. • 1746-OAP12 module: Insert a new fuse into the fuse holder, align the fuse holder on fuse clips, and press down. 5. Replace the output module in the chassis. 6. Restore SLC 500 system power. 7. Clear processor fault bits as indicated in the steps provided on page 13.
Electronically Protected Modules (1746-OB6EI and 1746-OB16E) The electronic protection of the 1746-OB6EI and 1746-OB16E modules have been designed to provide protection for the modules from short circuit and overload current conditions. The protection is based on a thermal cut-out principle. In the event of a short circuit or overload current condition on an output channel, that channel will limit current within milliseconds after its thermal cut-out temperature has been reached. All other channels continue to operate as directed by the CPU (processor) module. IMPORTANT
The modules do not provide protection against reverse polarity wiring or wiring to ac power sources. Electronic protection is not intended to replace fuses, circuit breakers, or other code-required wiring protection devices.
Publication 1746-IN027D-EN-P - December 2012
Page 15
SLC 500 Digital I/O Modules
15
E-FUSE LED Indicator OUTPUT E F U S E
E-FUSE LED Indicator
There is no jumper setting on this module.
Front View
Auto Reset Operation IMPORTANT
The 1746-OB6EI and 1746-OB16E modules perform auto-reset under overload conditions. When an output channel overload occurs, that channel will limit current within milliseconds after its thermal cut-out temperature has been reached. While in current limit, the output channel can cool below the thermal cut-out temperature allowing the module to auto-reset and resume control of the output channel as directed by the processor until the thermal cut-out temperature is again reached. Removing power from an overloaded output channel would also allow the output channel to cool below the thermal cut-out temperature, allowing auto-reset to occur when power is restored. The output channel would operate as directed by the processor until the thermal cut-out temperature is again reached. To avoid auto-reset of an output channel under overload conditions, an external mechanical fuse can be used to open the circuit when overloaded.
Short Circuit/Overload Current Diagnostics If a short circuit or overload current condition occurs on an output channel: • the E-FUSE LED indicator will illuminate provided that power is applied to the module. Power required: 5V DC via backplane and load power via an external supply. • all other channels continue to operate as directed by the CPU (processor) module.
Publication 1746-IN027D-EN-P - December 2012
Page 16
16
SLC 500 Digital I/O Modules
Recovery from Channel Shutdown 1. Remove the SLC 500 system power and correct the conditions causing the short circuit or overload current condition. 2. Restore the SLC 500 system power. The module automatically resets and resumes control of the output channel and associated load.
Publication 1746-IN027D-EN-P - December 2012
Page 17
SLC 500 Digital I/O Modules
17
Wiring Diagrams The wiring diagrams in these installation instructions are examples only. It is not necessary to connect an I/O device to each and every I/O module terminal.
Labeling for SLC/PLC Systems In this document, 16-point I/O module wiring diagrams include both decimal and octal numbers for I/O addressing and wire identification (see figure below). To wire your 16-point I/O module when used in a SLC system, use the decimal numbers in the upper left portion of each box. When used in a PLC system, use the octal numbers in the lower right portion of the box. As shipped from the factory, the I/O module has a decimal address label on the inside of its door. A separate octal conversion kit can be ordered, to allow you to convert your module to the octal system. You can order the octal label kit from your Allen-Bradley Distributor. The octal kit is ordered based on the catalog number of the I/O module.
TIP
Please refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for a listing of octal label kit catalog numbers.
IMPORTANT
Be sure the octal labels are used with your PLC system. Directions on how to install the labels are included with the kit and on page 6 of this document.
Decimal and Octal Labeling for 16-point I/O Modules 1746-IA16 L1
100/120V AC IN 0
For SLC (decimal)
0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
IN 14
5
IN 6
100/120V AC
16
6
IN 7
10
IN 9
7
IN 8
11
IN 10 12
IN 11
14
IN 13
13
IN 12
For PLC (octal)
15
IN 14 16 IN 15
17
L2
AC COM AC COM
Internally Connected Commons
SLC PLC
Publication 1746-IN027D-EN-P - December 2012
Page 18
18
SLC 500 Digital I/O Modules
AC Input Modules Wiring Diagrams 1746-IA4, 1746-IA8, 1746-IA16
1746-IA4
1746-IA8
100/120V AC
100/120V AC
L1
NOT USED
IN 1
NOT USED
IN 2
NOT USED
L1
100/120V AC
L2
IN 0
NOT USED
IN 3
100/120V AC
IN 0
IN 4
IN 1
IN 5
IN 2
IN 6
IN 3
IN 7
AC COM
AC COM
L2
Internally Connected Commons
1746-IA16
100/120V AC L1 IN 0 0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
5
IN 6
100/120V AC
6
IN 7
10
IN 9
12
IN 11
7
IN 8
11
IN 10
13
IN 12 14
IN 13
IN 14
15 16 IN 15
L2
17 AC COM AC COM
Internally Connected Commons
Publication 1746-IN027D-EN-P - December 2012
SLC PLC
AC COM
Page 19
SLC 500 Digital I/O Modules
19
1746-IM4, 1746-IM8, 1746-IM16 1746-IM4
1746-IM8
200/240V AC
200/240V AC L1
NOT USED
IN 0
NOT USED
IN 1
NOT USED
IN 2
NOT USED
L1
IN 3
200/240V AC
IN 0
IN 4
IN 1
200/240V AC
IN 5
IN 2
IN 6
IN 3
L2
IN 7
L2
AC COM
AC COM
Internally Connected Commons
AC COM
1746-IM16
200/240V AC L1 IN 0 0
IN 1
2
IN 3
4
IN 5
6
IN 7
10
IN 9
1
IN 2
3
IN 4
200/240V AC
5
IN 6
7
IN 8
11
IN 10 12
IN 11
14
IN 13
13
IN 12
15
IN 14 16 IN 15
L2
17 AC COM AC COM
Internally Connected Commons
SLC PLC
Publication 1746-IN027D-EN-P - December 2012
Page 20
20
SLC 500 Digital I/O Modules
DC Input Modules Wiring Diagrams 1746-IN16 1746-IN16
24V AC/DC Sinking L1 or +DC IN 0 0
IN 1
2
IN 3
4
IN 5
1
IN 2
3
IN 4
V AC/DC
IN 6
5 6 IN 7 7
IN 8 10 IN 9
11
IN 10 12
IN 1 1 13
IN 12 14 IN 13
15
IN 14 16 IN 15 AC/DC COM
L2 or -DC
17 AC/DC COM
Internally Connected Commons
SLC PLC
1746-IB8, 1746-IB16, 1746-ITB16, 1746-IC16, 1746-IH16 1746-IB8
1746-IB16,1746 -ITB16
1746-IC16
1746-IH16
24V DC Sinking
24V DC Sinking
48V DC Sinking
125V DC Sinking
+DC +DC
IN 0
IN 0
IN 1
24V DC
IN 2
IN 2
(1746-IB16, 1746- ITB16)
IN 4
IN 3
48V DC
IN 6
24V dc
(1746-IC16) IN 4 IN 5
125V DC (1746-IH16)
IN 6
-DC
Internally Connected Commons
1 2
3 4 IN 5 5 7
IN 10
11 12 IN 1 1 14
IN 14
-DC
IN 3
6 IN 7 IN 8 6 10 IN 9
IN 12
IN 7 DC COM
0 IN 1
DC COM
13
IN 13 15
16 IN 15 17 DC COM
DC COM
Publication 1746-IN027D-EN-P - December 2012
Internally Connected Commons
SLC PLC