For the Allen-Bradley 1746-OX8

Page 1

Installation Instructions

SLC 500 Digital I/O Modules

Input Catalog Numbers 1746-IA4, 1746-IA8, 1746-IA16, 1746-IB8, 1746-IB16, 1746-IC16, 1746-IG16, 1746-IH16, 1746-IM4, 1746-IM8, 1746-IM16, 1746-IN16, 1746-ITB16, 1746-ITV16, 1746-IV8, 1746-IV16 Output Catalog Numbers 1746-OA8, 1746-OA16, 1746-OAP12, 1746-OB8, 1746-OB6EI, 1746-OB16, 1746-OB16E, 1746-OBP8, 1746-OBP16, 1746-OG16, 1746-OV8, 1746-OV16, 1746-OVP16, 1746-OW4, 1746-OW8, 1746-OW16, 1746-OX8 Combination Input/Output Catalog Numbers 1746-IO4, 1746-IO8, 1746-IO12, 1746-IO12DC Table of Contents Topic

Page

Important User Information

2

North American Hazardous Location Approval

3

Environment and Enclosure

4

Prevent Electrostatic Discharge

4

Install and Remove the Module

5

Octal Label Kit Installation (for PLC processors only)

6

Wiring Diagrams

17

Apply the Octal Filter Label

6

Apply the Octal Door Label

6

Removable Terminal Blocks

6

Recovery From Blown Fuse/Processor Fault/Processor Shutdown

13

Replacement Fuse Recommendations

13

Replace Fuses

14

Electronically Protected Modules (1746-OB6EI and 1746-OB16E)

14

Specifications

29

Page 2

2

SLC 500 Digital I/O Modules

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences. SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures. IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

Overview In addition to providing the module’s electrical specifications, this document tells you how to: • install the module into a chassis. • wire the module’s terminal block. • install the Octal Filter Label.

Publication 1746-IN027D-EN-P - December 2012

Page 3

SLC 500 Digital I/O Modules

3

North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 1746-IA4, 1746-IA8, 1746-IA16, 1746-IB8, 1746-IB16, 1746-IC16, 1746-IG16, 1746-IH16, 1746-IM4, 1746-IM8, 1746-IM16, 1746-IN16, 1746-ITB16, 1746-ITV16, 1746-IV8, 1746-IV16, 1746-OA8, 1746-OA16, 1746-OAP12, 1746-OB8, 1746-OB6EI, 1746-OB16, 1746-OB16E, 1746-OBP8, 1746-OBP16, 1746-OG16, 1746-OV8, 1746-OV16, 1746-OVP16, 1746-OW4, 1746-OW8, 1746-OW16, 1746-OX8, 1746-IO4, 1746-IO8, 1746-IO12, 1746-IO12DC. The following information applies when operating this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

EXPLOSION HAZARD

RISQUE D’EXPLOSION

•

Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

•

Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.

•

Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

•

Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

•

Substitution of any component may impair suitability for Class I, Division 2.

•

•

If this product contains batteries, they must only be changed in an area known to be nonhazardous.

La substitution de tout composant peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

•

S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Publication 1746-IN027D-EN-P - December 2012

Page 4

4

SLC 500 Digital I/O Modules

Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see the following: • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements. • NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

Prevent Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation, if available. • Store the equipment in appropriate static-safe packaging when not in use.

Publication 1746-IN027D-EN-P - December 2012

Page 5

SLC 500 Digital I/O Modules

5

Install and Remove the Module ATTENTION: Never install, remove, or wire modules with power applied to chassis.

IMPORTANT

The first slot of the chassis is reserved for the processor or the 1747-ASB module.

Follow these steps to install the module: 1. Disconnect power.

Module Installation

2. Align the circuit board of module with the chassis card guide. (A) 3. Slide the module into the chassis until the bottom tabs lock into place. (B) B

4. Route the wires down and away from the module, securing them with the wire tie. (C)

D

5. Cover all unused slots with Card Slot Filler, catalog number 1746-N2, to keep the chassis free from debris.

Slot 1

A

6. To remove the module, press and hold the module release located on each self-locking tab, and slide the module out of the chassis slot. (D)

C

Max 2 mm2 (14 AWG) Max 2 wires per terminal Max torque: 0.9 Nm (8 lb-in.)

Publication 1746-IN027D-EN-P - December 2012

Page 6

6

SLC 500 Digital I/O Modules

Octal Label Kit Installation (for PLC processors only) The octal label kit consists of an octal filter label and a door label. Use these octal labels to replace the decimal labels that are attached to the I/O modules. TIP

The octal label kit can be obtained from your Allen-Bradley distributor. The octal kit is ordered based on the catalog number of the I/O module. Please refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011, for a listing of octal label kit catalog numbers.

ATTENTION: Do not touch or remove the terminal block when the SLC 500 system is powered. Contact with AC line potential may cause injury to personnel.

Apply the Octal Filter Label 1. Remove the octal filter label from its paper carrier. 2. Align the octal filter label numbers horizontally to the module color bar and over the decimal filter numbers. Refer to Installing Octal Labels on page 7 for filter label placement. 3. Apply the octal label to the filter. 4. Press firmly to be sure that the label adheres properly.

Apply the Octal Door Label 1. Remove the octal door label from its paper carrier. 2. Align the octal label directly over the decimal door label on the inside of the door. Refer to Installing Octal Labels on page 7 for door label placement. 3. Press firmly to be sure that the label adheres properly.

Removable Terminal Blocks Colored terminal blocks are removable by loosening the upper and lower retaining screws. Black terminal blocks are not removable.

Publication 1746-IN027D-EN-P - December 2012

Page 7

SLC 500 Digital I/O Modules

7

Installing Octal Labels Octal Filter Label Module Color Bar

Beveled Edge

Upper retaining screw max torque = 0.6 Nm (5.3 lb-in.)

OCTAL

Removable Terminal Block Terminal Wiring Max 2mm2 (14 AWG) Max 2 wires per terminal Max torque: 0.9 Nm (8 lb-in.)

1746-xxxx (OCTAL) Octal Door Label

1746-xxxx

Lower retaining screw max torque = 0.6 Nm (5.3 lb-in.)

Fuse Protection and Blown Fuse Diagnostics This section describes fusing characteristics for the following modules: • 1746-OBP16 • 1746-OVP16 • 1746-OAP12

Fuse Protection (1746-OBP16 and 1746-OVP16 modules) The fuse on the 1746-OBP16 and 1746-OVP16 modules (shown on Location of Jumpers and Fuses for 1746-OBP16 and 1746-OVP16 Modules on page 9) provides short-circuit protection for 13 mm2 (16 AWG) or larger wiring to external loads. In the event of a short circuit on an output channel, it is likely that the transistor associated with that channel will be damaged. In this event, the module should be replaced or the load moved to a spare output channel. The fuse does not provide overload protection. In the event of an overload on an output channel, it is likely that the fuse will not blow and the transistor associated with that channel will be damaged. To provide overload protection for your application, user-supplied fuses should be installed externally and properly sized to match your individual load characteristics. Publication 1746-IN027D-EN-P - December 2012

Page 8

8

SLC 500 Digital I/O Modules

Fuse Protection (1746-OAP12 modules) A fuse is provided on each common of the 1746-OAP12 module (shown on Location of Jumpers and Fuses for 1746-OAP12 Module on page 10) for a total of two fuses. The fuses are designed to protect the module from short-circuit conditions. The fuse does not provide overload protection. In the event of an overload on an output channel, it is likely that the fuse will not blow and the output device associated with that channel will be damaged. To provide overload protection for your application, user-supplied fuses should be installed externally. The recommended fuse for overload protection is SAN-O HT. Select the fuse rating according to your load. Do not use HT fuses rated higher than 2.0 Amps.

Blown Fuse Diagnostics If the fuse blows on the 1746-OBP16, 1746-OVP16, or 1746-OAP12 module, the following occurs: • The blown fuse LED indicator will illuminate, provided power (5V DC via backplane and load power via external supply) is applied to the module. • A processor error will occur if JP1 connects pins 2 and 3. (See figures on page 9 and page 10.)

Publication 1746-IN027D-EN-P - December 2012

Page 9

SLC 500 Digital I/O Modules

9

Location of Jumpers and Fuses for 1746-OBP16 and 1746-OVP16 Modules Location for 1746-OBP16 Fuse (F1)

Jumper for processor notification (JP1)

1 2 3

Left side view

Location for 1746-OVP16 Fuse (F1) WHEN FUSE OPENS OUTPUT F U S E

Brown fuse LED Indicator

3 2

2 1

PROCESSOR CONTINUES PROCESSOR FAULTS

REPLACEMENT FUSE LITTLEFUSE 322010 or 332010

Front view

A.B. CAT. NO. 1746-F9

Jumper settings and fuse replacement information

Publication 1746-IN027D-EN-P - December 2012

Page 10

10

SLC 500 Digital I/O Modules

Location of Jumpers and Fuses for 1746-OAP12 Module F1

2 1 3 JP1

Jumper for Processor Notification (JP1)

Left side view

F2

WHEN FUSE OPENS

OUTPUT F U S E

Blown Fuse LED indicator

2

1

JP1 3

2

PROCESSOR CONTINUES PROCESSOR FAULT

REPLACEMENT FUSE: SAN-O HQ 6.3A A-B CAT. NO. 1746-F9 Jumper Settings and Fuse Replacement Information

Front View

Publication 1746-IN027D-EN-P - December 2012