Manual · Allen-Bradley
SLC 500 Power Supplies, Catalog Numbers 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6, 1746-P7, Installation Instructions
Manual20 pagesPDF 610 KB
Installation instructions for the Allen-Bradley SLC 500 power supplies 1746-P1 through 1746-P7, including the 1746-P2.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation installation instructions for the Allen-Bradley SLC 500 chassis power supplies, catalog numbers 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6 and 1746-P7. It covers hazardous location notes, the optional chassis interconnect cable, sliding the supply into the chassis, setting the input voltage jumper, grounding and incoming power wiring, the 24V dc user-power terminals, undervoltage behavior, general specifications for each supply and physical dimensions.
Its parts
- Overview
- Hazardous Location Considerations
- Install the Chassis Interconnect Cable (optional)
- Power Supply Installation
- Power Supply Wiring
- SLC 500 Operation with 24V dc User-power Overcurrent Condition
- General Specifications (1746-P1, 1746-P2, 1746-P3, and 1746-P4)
- General Specifications (1746-P5, 1746-P6, and 1746-P7)
- Physical Dimensions
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
These are Allen-Bradley installation instructions, publication 1746-IN004B-EN-P of March 2008, for the SLC 500 power supplies 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6 and 1746-P7. They show how to fit the supply into an SLC 500 chassis, set the input jumper, wire power and ground, and use the 24V dc user power terminals. General specifications and dimensions close the document.
- Device
- SLC 500 power supply; slides into the card guides on the left side of the chassis p. 1, 7
- 24V dc user power
- 1746-P1, 1746-P2, 1746-P5 and 1746-P6: isolated, non-fused 200 mA at 24V dc for sensors and loads p. 12
- Input voltage jumper
- Set to match the input voltage; the 1746-P3, 1746-P5, 1746-P6 and 1746-P7 have none p. 8
- User-power overcurrent
- 1746-P2 series A, B: supply shuts down, CPU faults, reload program; series C: 24V dc user output shuts down, CPU continues p. 13
- Operating temperature
- 0...60 °C (32...140 °F) p. 14
- Length (approx.)
- 1746-P2: 85 mm (3.35 in.) p. 17
- Ground wire
- 1.68 mm (#14 AWG) 75° copper, leads as short as possible; terminal screws 0.8 Nm (7 lb-in) p. 9
- Mounting screw torque
- 1.2 Nm (11 lb-in) max. p. 7
- Tools
- Flat head (1/8 in.) and Phillips head (1/4 in., #2) screwdrivers p. 5
- Chassis interconnect
- Joins up to three SLC 500 chassis; install the cable before the power supply p. 7
- Undervoltage hold-up
- Controller keeps running briefly on low input voltage, turns off past the CPU hold-up time, and restarts by itself when voltage returns p. 14
- Environment
- Pollution Degree 2, overvoltage Category II, up to 2000 m (6561 ft) without derating p. 4
- Related publications
- 1747-UM011 (SLC 500 Modular Hardware Style User Manual); 1746-IN016 (chassis installation and grounding); 1770-4.1 (wiring and grounding) p. 7, 8
What this manual walks you through
- Installing the chassis interconnect cable p. 7
- Installing the power supply in the chassis p. 7
- Setting the input voltage jumper p. 8
- Grounding the supply and connecting incoming power p. 9, 10
- Special wiring for the 1746-P3 p. 11, 12
- Powering 24V dc sensors and loads from the user power terminals p. 12
- What happens on a 24V dc user-power overcurrent, and how to recover p. 13
- Undervoltage operation and CPU hold-up p. 14
- Reading the general specifications and dimensions p. 14, 15, 16, 17
Good to know
- Set the input jumper before applying power; exposed pins carry hazardous voltage once powered. p. 8
- Turn off incoming power before connecting wires. p. 9
- Use an isolation transformer when switching inductive loads such as motors, starters, solenoids and relays, since surges can damage the supply. p. 10
- For the 1746-P2 series C (and some other supplies), monitor the 24V dc user output with a 24V dc input channel. p. 13
- The supply is open type equipment and must be mounted in a suitable enclosure. p. 4
Questions this manual answers
How much 24V dc can the 1746-P2 supply to sensors?
Its user power terminals provide an isolated, non-fused 200 mA at 24V dc. p. 12
What happens if the 1746-P2 user power is overloaded?
On series A and B the supply shuts down and the CPU faults, so the user program must be reloaded. On series C only the 24V dc user output shuts down and the CPU continues. p. 13
Does the 1746-P2 have a voltage selection jumper?
Yes. The jumper is set to match the input voltage before power is applied; only the 1746-P3, 1746-P5, 1746-P6 and 1746-P7 lack one. p. 8
What wire is used to ground an SLC 500 power supply?
A 1.68 mm (#14 AWG) 75° copper wire to the nearest ground or ground bus, kept as short as possible. p. 9
What is the operating temperature of the 1746-P2?
The specifications give 0...60 °C (32...140 °F) ambient. p. 14
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1746-IN004B-EN-P SLC 500 Power Supplies Installation Instructions1
- SLC 500 Power Supplies3
- Overview5
- Hazardous Location Considerations5
- Environnements dangereux6
- Install the Chassis Interconnect Cable (optional)7
- Power Supply Installation7
- Power Supply Wiring8
- SLC 500 Operation with 24V dc User-power Overcurrent Condition13
- General Specifications (1746-P1, 1746-P2, 1746-P3, and 1746-P4)14
- General Specifications (1746-P5, 1746-P6, and 1746-P7)16
- Physical Dimensions17
- Back Cover20
The whole text · 2 parts