Page 11

Installation Instructions

11

1746-P3 Wiring Considerations This information describes special wiring considerations for the 1746-P3 power supply that are not labeled as revision (REV) B.

Any voltage applied to the 1746-P3 DC NEUT terminal will be present at the SLC logic ground and the processor DH-485 port. To prevent unwanted potentials across the logic ground of the controller and/or damage to the SLC chassis, the DC NEUTRAL terminal of the external DC power source must be either isolated from the SLC chassis ground or connected to earth ground as shown in the following illustration.

ATTENTION

!

1746-P3 External DC Power Source

Processor

Door DH-485 Port

DC Neut

DC Neut

Earth Ground

IMPORTANT

SLC Logic Ground

+24V dc

+24V dc

Chassis Ground

SLC 500 Chassis

• A jumper wire is recommended between the DC NEUT and Chassis Ground of the external power source.

Earth Ground

SLC 500 series A chassis (1746-A4, 1746-A7, 1746-A10, and 1746-A13) manufactured before November 1992 have a resistor between the logic ground and chassis ground as the drawing on the following page illustrates. This resistor could be damaged if the wiring recommendation described within the attention box above is not followed. See the figure on the following page for the location of the resistor. SLC 500 series A chassis (1746-A4, 1746-A7, 1746-A10, and 1746-A13) with a manufacture date of November 1992 or later do not have this resistor. SLC 500 series B chassis have a 1 MΩ resistor that limits the current between logic ground and chassis ground.

Publication 1746-IN004B-EN-P - March 2008

Page 12

12

Installation Instructions

1746-P3

SLC 500 Chassis

Processor

Door Not Used Not Used

DH-485 Port

SLC Logic Ground Resistor

+24V dc

• •

DC Neut Chassis Ground

Chassis Ground

Earth Ground

5. (Optional) For the 1746-P1, 1746-P2, 1746-P4, 1746-P5, and 1746-P6 power supplies, use PWR OUT +24V dc and PWR OUT COM terminals to power 24V dc sensors and loads. The terminals on the 1746-P1, 1746-P2, 1746-P5, and 1746-P6 power supplies provide an isolated, non-fused 200 mA, 24V dc power supply. The terminals on the 1746-P4 power supply provide an isolated, non-fused 1A, 24V dc power supply. (The 1746-P3 and 1746-P7 power supplies do not provide for an external power source.) Catalog Number 1746-P1, 1746-P2, 1746-P5, & 1746-P6 User Power

Catalog Number 1746-P4

PWR OUT +24V dc

PWR OUT +24V dc PWR OUT COM

Publication 1746-IN004B-EN-P - March 2008

User Power

PWR OUT COMMON

Page 13

Installation Instructions

13

SLC 500 Operation with 24V dc User-power Overcurrent Condition Cat. No.

SLC Operation

Recovery Procedure

1746-P1 series A (made in Japan)

Power supply shutdown, CPU Fault

Reload user program

1746-P1 series A (made in Malaysiacurrent production)

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P2 series A, B

Power supply shutdown, CPU Fault

Reload user program

1746-P2 series C

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P4 series A

Power supply shutdown, CPU Fault

Reload user program

1746-P5 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P6 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

ATTENTION

!

For 1746-P1 (made in Malaysia), 1746-P2 series C, 1746-P5 series A, and 1746-P6 series A power supplies, monitor the 24V dc user output with a 24V dc input channel to avoid unexpected operation due to 24V dc user power shutdown.

6. Remove the protective label.

Publication 1746-IN004B-EN-P - March 2008

Page 14

14

Installation Instructions

Power Supply Undervoltage Operation SLC 500 controllers continue to operate (hold-up) for a short period of time if the input voltage to the power supply drops below the recommended operating voltage range. The controller continues to scan the user program and control I/O during this time. CPU hold-up for each power supply is shown on pages 14 and 16. SLC 500 controllers turn OFF (stop scanning and disable outputs) if input voltage to the power supply is removed or drops below the recommended operating range for a period exceeding the CPU hold-up time. The controller resumes operation automatically when the input voltage is restored to normal. If the input voltage to the 1746-P7 power supply falls into a range of 4 to 9V for a period exceeding the CPU hold-up time, the controller turns OFF and will not turn back ON until input voltage is increased to 11V dc.

General Specifications (1746-P1, 1746-P2, 1746-P3, and 1746-P4) Attribute

Value 1746-P3

1746-P4

Line voltage

85...132/170...265V ac 47...63 Hz

19.2...28.8V dc

85...132/ 170...250V ac 47...63 Hz

Typical line power requirement

135VA

180VA

90VA

150VA

Inrush current, max

20 A

Internal current capacity

2 A at 5V dc 0.46 A at 24V dc

5 A at 5V dc 0.96 A at 24V dc

3.6 A at 5V dc 0.87 A at 24V dc

10.0 A at 5V dc 2.88 A at 24V dc(1)

Fuse protection(2)

1746-F1 or equivalent(3) (4)

1746-F2 or equivalent(3) (5)

1746-F3 or equivalent(3) (6)

Fuse is soldered in place.

24V dc user-power current capacity

200 mA

Not applicable

1 A(1)

24V dc user-power voltage range

18...30V dc

User-supplied overcurrent protection(7), max

15 A

Temperature, ambient operating

0...60 °C (32...140 °F) Current capacity is derated 5% above 55 °C (131 °F).

Isolation(8)

1800V ac RMS for 1 s

600V ac RMS for 1 s 2600V dc for 1 s (version B or later)

CPU hold-up time(9)

20 ms (full load) 3000 ms (no load)

5 ms (full load) 1000 ms (no load)

1746-P1

1746-P2

45 A

Publication 1746-IN004B-EN-P - March 2008

20.4...27.6V dc Not applicable

15 A

0...60 °C (32...140 °F) no derating

20 ms (full load) 3000 ms (no load)

Page 15

Installation Instructions

Attribute

Value 1746-P1

Certification (when product is marked)

15

1746-P2

1746-P3

1746-P4

UL Listed Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations

UL Listed Industrial Control Equipment

C-UL Listed Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations

CSA Certified Process Control Equipment for Class 1, Div 2, Groups A, B, C, D Hazardous Locations

CE(10) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2 Industrial Immunity EN50081-2 Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with: EN61131-2 Programmable Controllers C-Tick Australian Radiocommunications Act, compliant with: AS/NZS 2064 Industrial Emissions (1)

The combination of all output power (5V backplane, 24V backplane, and 24V user source) cannot exceed 70 W.

(2)

Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the power line.

(3)

Fuse sizes specified are for end-devices only. Fuse size may need to be reduced depending on the size of circuit wiring.

(4)

Equivalent fuses: 250V-3A fuse, nagasawa ULCS-61ML-3, or BUSSMAN AGC 3.

(5)

Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3.

(6)

Equivalent fuse: 125V-5A fuse, LITTLEFUSE 233.

(7)

Use time-delay type overcurrent protection in all ungrounded conductors.

(8)

Isolation is between input terminals and backplane.

(9)

CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(10) See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1746-IN004B-EN-P - March 2008

Page 16

16

Installation Instructions

General Specifications (1746-P5, 1746-P6, and 1746-P7) Attribute

Value 1746-P5

1746-P6

1746-P7

Line voltage

90...146V dc

30...60V dc

10...30V dc(1)

Typical line power requirement

85VA

100VA

12V dc input: 50VA

Inrush current, max 20 A

20 A (required for turn-on)

Internal current capacity

12V dc input: 2.0 A at 5V dc 0.46 A at 24V dc

5 A at 5V dc 0.96 A at 24V dc

24V dc input: 75VA

24V dc input: 3.6 A at 5V dc 0.87 A at 24V dc

See 1746-P7 current capacity chart on page 17. Fuse is soldered in place.

(2)

Fuse protection

24V dc user-power 200 mA current capacity

Not applicable

24V dc user-power 18...30V dc voltage range Temperature, operating ambient

0...60 °C (32...140 °F) Current capacity is derated 5% above 55 °C (131 °F).

Isolation(3)

1800V ac RMS for 1 s

600V ac RMS for 1 s

CPU hold-up time

20 ms (full load) 3000 ms (no load)

12V dc input: 1.37 ms at 0V dc (full load) 895 ms at 0V dc (no load) 10 ms at 9V dc (full load) continuous at 9V dc (no load)

Certification (when product is marked)

UL Listed Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations

(4)

5 ms (full load) 1500 ms (no load)

24V dc input: 40 ms at 0V dc (full load) 1860 ms at 0V dc (no load) 790 ms at 11V dc (full load) continuous at 11V dc (no load)

C-UL Listed Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations CE(5) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2 Industrial Immunity EN50081-2 Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with: EN61131-2 Programmable Controllers C-Tick Australian Radiocommunications Act, compliant with: AS/NZS 2064 Industrial Emissions

(1)

See page 14 for information on power supply undervoltage operation.

(2)

Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the power line.

(3)

Isolation is between input terminals and backplane.

(4)

CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(5)

See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1746-IN004B-EN-P - March 2008

Page 17

Installation Instructions

17

1746-P7 Current Capacity 24V dc Output Current

5V dc Output Current

0.87 A

3.6 A

0.625 A

2.64 A

0.46 A

2.0 A Input Voltage

10V dc

12.2V dc 19.2V dc 15V dc

30V dc

Physical Dimensions Controller

Length, Approx. mm (in.)

Depth, Approx. mm (in.)

Height, Approx. mm (in.)

1746-P1

65 (2.56)

140 (5.70)

140 (5.51)

1746-P2

85 (3.35)

1746-P3 1746-P4

110 (4.33)

145 (5.70)

1746-P5

85 (3.35)

140 (5.70)

1746-P6 1746-P7

Publication 1746-IN004B-EN-P - March 2008

Page 18

18

Installation Instructions

Notes:

Publication 1746-IN004B-EN-P - March 2008

Page 19

19

Notes:

Publication 1746-IN004B-EN-P - March 2008

Page 20

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running. United States

1.440.646.3434 Monday – Friday, 8am – 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned. United States

Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for return procedure.