The text of a manual · part 21 of 26
SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual: E - Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller, pages 174 to 183
Pages 174 to 183 of 223, from SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C
Page 174
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L20R (12) 240 VAC Inputs & (8) Relay Outputs
Wiring Diagram (Hi) L1
(Lo) L2
5-265 VAC 5-125 VDC
(Hi) L1
5-265 VAC 5-125 VDC
1
CR
(Lo) L2 1
CR
CR
CR
VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 OUT 6 OUT 7 VDC 1 VDC 2
(Hi) L1
(Lo) L2
(Lo) L2
(Hi) L1
170-265 VAC
85-265 VAC
120/240 VAC VAC NEUT CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
IN 1
IN 0
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
Commons Connected Internally
➀ These outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–31
Page 175
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.15 µF IN
270
1870
1 µF
261
0.15 µF IN
On/Off State Voltage Ranges 0 VAC Off-state
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ
265 VAC
170 VAC
50 VAC
Input State Not Guaranteed
On-state
Output Circuit Diagram VAC/VDC
OUT
OUT
Operating Voltage Range 0 V 5 VAC 0 V 5 VDC
ÉÉ ÉÉ
Operation Not Guaranteed
E–32
265 VAC 125 VDC Recommended Operating Range
Page 176
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L30A (18) 120 VAC Inputs & (12) Relay Outputs (Hi) L1
5-265 VAC 5-125 VDC
Wiring Diagram
(Lo) (Hi) (Lo) L2 L1 5-265 VAC 1 L2 5-125 VDC
1
CR
CR
(Hi) L1
5-265 VAC 5-125 VDC
(Hi) L1
(Lo) L2 1
CR
CR
5-265 VAC 5-125 VDC
1
CR
(Lo) L2
CR
VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 NOT NOT VAC- OUT 6 OUT 7 OUT 8 OUT 9 VAC- OUT 10 OUT 11 NOT VDC 1 VDC 2 VDC 4 USED USED VDC 3 USED
(Hi) L1
(Lo) L2
(Lo) L2
NOT USED
(Hi) L1
85 - 132 VAC
85-265 VAC
120/240 VAC NEUT VAC CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
AC COM
AC COM
IN 0
IN 1
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
Commons Connected Internally
➀ These outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–33
Page 177
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.15 µF IN
270
1870
1 µF
261
0.15 µF IN
On/Off State Voltage Ranges 85 VAC
30 VAC
0 VAC Off-state
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ Input State Not Guaranteed
132 VAC On-state
Output Circuit Diagram VAC/VDC
OUT
OUT
Operating Voltage Range 0 V 5 VAC 0 V 5 VDC
ÉÉ ÉÉ
Operation Not Guaranteed
E–34
265 VAC 125 VDC Recommended Operating Range
Page 178
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L30B (18) 120 Vac Inputs & (12) Triac Outputs (Hi) L1
Wiring Diagram
(Hi) L1
(Lo) L2
85-265 VAC
85-265 VAC
1
CR
CR
CR
(Lo) L2 1
CR
CR
CR
VAC 1 VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 NOT NOT VAC 2 VAC 2 OUT 6 OUT 7 OUT 8 OUT 9 OUT 10 OUT 11 NOT USED USED USED
VAC 1 Connected Internally
(Hi) L1
NOT USED
VAC 2 Connected Internally
(Lo) L2
(Lo) L2
(Hi) L1
85-132 VAC
85 - 265 VAC
120/240 VAC NEUT VAC CHASSIS GND
NOT USED
NOT USED
AC COM
AC COM
AC COM
AC COM
IN 0
IN 1
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
Commons Connected Internally
➀ These outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
E–35
Page 179
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 270
1870
AC COM 1 µF
261
0.3 µF IN
270
1870
1 µF
261
0.3 µF IN
On/Off State Voltage Ranges 85 VAC
30 VAC
0 VAC Off-state
ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ Input State Not Guaranteed
132 VAC On-state
Output Circuit Diagram L1
OUT
OUT
Operating Voltage Range
ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ 0 VAC
85 VAC
Operation Not Guaranteed
265 VAC Recommended Operating Range
Important: If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance load, you may measure as much as 100 VAC even though the output is off.
E–36
Page 180
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L30C (18) 24 VDC Sinking Inputs, High-Speed Counter Input & (12) Relay Outputs (Hi) L1
5-265 VAC 5-125 VDC
Wiring Diagram
(Lo) (Lo) (Hi) L2 L1 5-265 VAC 1 L2 5-125 VDC
1
CR
CR
(Hi) L1
1
(Lo) L2
(Hi) (Lo) L1 5-265 VAC 1 L2 5-125 VDC
CR
CR
CR
5-265 VAC 5-125 VDC
CR
VAC- OUT 0 OUT 1 OUT 2 OUT 3 VAC- OUT 4 OUT 5 NOT NOT VAC- OUT 6 OUT 7 OUT 8 OUT 9 VAC- OUT 10 OUT 11 NOT VDC 1 VDC 2 VDC 4 USED USED VDC 3 USED
(Hi) L1
NOT USED
(Lo) L2
85-265 VAC Sourcing Device 120/240 VAC NEUT VAC CHASSIS GND
PWR OUT DC +24VDC 2 COM
PWR OUT DC COM 2 COM
DC COM
DC COM
IN 1
IN 0 HSC
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
Commons Connected Internally - DC
10-30 VDC
+ DC
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
➁ 24 VDC, 200mA user power is available for sensors.
E–37
Page 181
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Input Circuit Diagram 560
560
INPUT 0 (HSC) 0.01 µ F
1. 5K
OTHER INPUTS
390
1. 5K 0.1 µ F
560
COM
On/Off State Voltage Ranges – Input 0 (HSC)
0 VDC
ÉÉÉÉÉÉ ÉÉÉÉÉÉ
10 VDC
4 VDC
Off-state
30 VDC On-state
Input State Not Guaranteed
On/Off State Voltage Ranges – All Other Inputs 0 VDC
ÉÉÉÉÉ ÉÉÉÉÉ 5 VDC
Off-state
10 VDC
Input State Not Guaranteed
E–38
30 VDC On-state
Page 182
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Output Circuit Diagram VAC/VDC
OUT
OUT
Operating Voltage Range 0 V 5 VAC 0 V 5 VDC
ÉÉ ÉÉ
265 VAC 125 VDC Recommended Operating Range
Operation Not Guaranteed
E–39
Page 183
Appendix E Wiring and Circuit Diagrams and Voltage Ranges for Your Fixed Controller
Catalog Number 1747-L30D (18) 24 VDC Sinking Inputs, High-Speed Counter Input & (12) Triac Outputs
Wiring Diagram
(Hi) L1 1
85-265 VAC
CR
(Hi) L1
(Lo) L2
85-265 VAC
CR
CR
(Lo) L2
1
CR
CR
CR
VAC 1 VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 NOT NOT VAC 2 VAC 2 OUT 6 OUT 7 OUT 8 OUT 9 OUT 10 OUT 11 NOT USED USED USED
VAC 1 Connected Internally
(Hi) L1
NOT USED
VAC 2 Connected Internally
(Lo) L2
85-265 VAC Sourcing Device 120/240 VAC NEUT VAC CHASSIS GND
PWR OUT DC +24VDC 2 COM
PWR OUT DC COM 2 COM
DC COM
DC COM
IN 1
IN 0 HSC
IN 3 IN 2
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11 IN 10
IN 13
IN 12
IN 15
IN 14
IN 17
IN 16
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
Commons Connected Internally - DC
10-30 VDC
+ DC
➀ The outputs are isolated in groups as shown. Therefore, different voltages can be applied to each group as the specific application requires.
➁ 24 VDC, 200mA user power is available for sensors.
E–40