The text of a manual · part 10 of 12
Direct Communication Module (Cat. No. 1747-DCM) User Manual, pages 53 to 64
Pages 53 to 64 of 80: 7 - Troubleshooting; 8 - Application Examples
The original document is the PDF (429 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-DCM
Page 53
Chapter
7
Troubleshooting This chapter shows you how to identify and correct errors that you may encounter using LEDs. The topics include: • DCM status indicators • troubleshooting using the FAULT LED (red) • troubleshooting using the COMM LED (green)
DCM Status Indicators
Two LEDs indicate the status of the DCM.
DCM FAULT
Red
COMM
Green
Troubleshooting Using the FAULT LED (Red) If LED is:
Cause:
On
Internal Fault
Blinking
Configuration Error
Off
Normal State
Corrective action: Cycle power to the I/O chassis containing the DCM. Replace DCM if red LED remains lit after powerup. Check that the DIP switch settings are correct. Make sure that I/O group and rack size settings are compatible.➀ Also see that the setting for rack address is correct. Refer to chapter 4, Module Configuration, for help with DIP switches. No action required.
➀ The DCM cannot cross logical rack boundaries. Therefore, as an example, configuring the module for 1/2 logical rack with starting group 6 will cause a configuration error.
7–1
Page 54
Chapter 7 Troubleshooting
Troubleshooting Using the COMM LED (Green) If LED is:
Cause:
On
Normal State
Blinking
RIO scanner’s processor in Program/Test Fault Mode
Off
RIO scanner’s processor not connected to scanner RIO scanner’s processor rack inhibited No communication between RIO scanner’s processor and DCM
7–2
Corrective action: No action required. Check for RIO scanner’s processor error, correct condition, and cycle power to DCM. Check that the scanner is properly installed in rack (RIO scanner’s processor–2, #3). Check RIO scanner’s processor rack integrity, correct any problem, and cycle power to DCM. Check that the baud rate of the DCM matches the baud rate of the scanner. Check cable connections from the RIO scanner’s processor or scanner to the DCM. Check that the DCM connector is properly installed.
Page 55
Chapter
8
Application Examples This chapter provides and examines two applications of the DCM. • basic example • supplementary example
Basic Example
In the following application, the 1747-DCM in the remote rack 2 will monitor the 1747-SN data from the local rack 1. The program examples in both local and remote rack CPUs consist of 1 rung each. When input I:1/0 is enabled in the local rack, the output O:3.1/0 condition is transferred to the 1747-DCM input image via the 1747-SN output image. This condition enables O:2/0 in the remote rack output card.
ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ É É ÉÉ ÉÉ Output
DCM
SLC 5/01
P2
SN
Output
Input
SLC 5/02
Rack 2
P2
Rack 1
= slot not used
Input Switch
RIO (Belden 9463)
1747-SN Module Configuration➀ Baud Rate =
57.6K baud
G-file Size =
3 words
G-File 15
14
13
12
11
10
9
Word 1
0
0
0
0
0
0
0
0
Word 2
0
0
0
0
0
0
0
0
Word 0
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
1
= Starting Address 0
0
0
0
0
0
0
0
1
= 1/4 Rack Size
Reserved
➀
See SN manual for further details on configuration.
8–1
Page 56
Chapter 8 Application Examples
DCM configuration: Rack Address =
1
I/O Group =
0
Baud Rate =
57.6K baud
Clear On Fault = no
Last Rack = no
Rack Size =
1/4
DIP Switch Settings Switch 1 ON
1
2
3
4
5
X
X
X
X
X
OFF
Switch 2 6
7
8
1
2
3
4
5
6
X
X
X
X
X
X
X
X
7
8
X
= Not used
System Configuration for Rack 1 Amount
Device
Catalog Number
1
Power Supply
1746-P2
1
SLC 5/02 Processor
1747-L524
1
4-Slot Rack
1746-A4
1
AC Input, 16 Inputs
1746-IA16
1
Relay Output, 16 Outputs
1746-OW16
1
Scanner
1747-SN
System Configuration for Rack 2 Amount
8–2
Device
Catalog Number
1
Power Supply
1746-P2
1
SLC 5/01 Processor
1747-L511
1
4-Slot Rack
1746-A4
1
Relay Output, 16 Outputs
1746-OW16
1
DCM
1747-DCM
Page 57
Chapter 8 Application Examples
Image Table Configuration Output Image SN
DCM
O:3.1/0
I:1.1/0
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
5
4
3
2
1
0
0
0
0
0
0
1
15
14
13
12
11
10
Input Image 9 8 7 6
0
0
0
0
0
0
0
0
0
0
Program Listing When I:1/0 is set, enabling O:3.1/0 in the SN output image, the data is sent to the input image of the DCM I:1.1/0. The output in rack 2 is then set to output module O:2/0. Rack 1, Program 1 I:1 ] [ 0 From Input Switch
O:3.1 ( ) 0 To SN Output Word 1, Bit 0
Rack 2, Program 2 I:1.1 ] [ 0 From DCM Input Word 1, Bit 0
O:2 ( ) 0
8–3
Page 58
Chapter 8 Application Examples
Supplementary Example
RIO (Belden 9463)
Module Configuration PLC-5 configuration for scanner I/O status, inhibit bits: S:27/0 =
*
S:27/1 =
0
S:27/2 =
1
S:27/3 =
1
* = Don’t care
DCM configuration: Rack Address =
1
I/O Group =
0
Baud Rate =
57.6K baud
Clear on Faults = No
8–4
Last Rack =
No
Rack Size =
Full Rack
NO4I
NI4 NO4I
É É É É É É É ÉÉ ÉÉ
NI4
SLC 5/01 DCM
P2
I/O
I/O
I/O
I/O
PLC–5 CPU
In the following application, the PLC-5/15, via its integrated RIO scanner and the DCM, will monitor the analog data from an SLC 500. This case is unique in that the data to be monitored is twice what the DCM can transfer. The program in the SLC 500 will multiplex the data into four, 4-word packets with a start and end of data word attached. The start and end of data word is also used to designate which module the data is coming from. This is also used by the PLC-5/15 to indicate that the data was transferred successfully.
= slot not used
Page 59
Chapter 8 Application Examples
DIP Switch Settings Switch 1 ON
1
2
3
4
5
X
X
X
X
X
OFF
Switch 2 6
7
8
1
2
3
4
X
X
X
X
X
X
X
5
6
X
X
7
8
= Not used
System Configuration Amount
Device
Catalog Number
1
Power Supply
1746-P2
1
SLC 5/01 Processor
1747-L511
1
7-Slot Rack
1746-A7
2
Analog Input, 4 point
1746-NI4
2
Analog Output, 4 point
1746-NO4I
1
DCM
1747-DCM
Image Table Configuration Output Image 15
DCM
NO4I
NO4I
O:1.0 O:1.1 O:1.2 O:1.3 O:1.4 O:1.5 O:1.6 O:1.7 O:4.0 O:4.1 O:4.2 O:4.3 O:5.0 O:5.1 O:5.2 O:5.3
14
13
12
11
10 9 8 7 6 5 4 3 Status Word to PLC-5 from SLC Counter ACC word denotes module being read Word 0 of analog module being read Word 1 of analog module being read Word 2 of analog module being read Word 3 of analog module being read Counter ACC word denotes module being read Not used NO4I word 0 NO4I word 1 NO4I word 2 NO4I word 3 NO4I word 0 NO4I word 1 NO4I word 2 NO4I word 3
2
1
8–5
0
Page 60
Chapter 8 Application Examples
15
DCM
NI4
NI4
14
13
12
I:1.0 I:1.1 I:1.2 I:1.3 I:1.4 I:1.5 I:1.6 I:1.7 I:2.0 I:2.1 I:2.2 I:2.3 I:3.0 I:3.1 I:3.2 I:3.3
11
Input Image 10 9 8 7 6 5 Status Word to SLC from PLC-5 Not used Not used Not used Not used Not used Not used Not used NI4 word 0 NI4 word 1 NI4 word 2 NI4 word 3 NI4 word 0 NI4 word 1 NI4 word 2 NI4 word 3
4
3
2
1
Program Listing for 5/01 Processor File: MULTPLX1.ACH Rung 0 sets the starting point of the C5:0 counter. This is done on the first scan of the program S:1/15 (first scan bit) and C5:0/DN (done bit 0) of the counter, ensuring that only the analog modules in slots 2 through 5 are read.
RUNG 2.0
C5:0 ] [ DN
MOV MOVE Source Dest
2 C5:0.ACC
S:1 ] [ 15 Rung 1 increments the C5:0 every 5.12 seconds. The value in the ACC is referenced to the slot that the DCM will send the data from, starting at slot 2.
RUNG 2.1
8–6
S:4 ] [ 8 5.12 Seconds Time Bit
CTU Countup Counter Preset Accum
C5:0 6 0
0
Page 61
Chapter 8 Application Examples
For rungs 2.2 through 2.5 the module number being monitored is shown above each example. For each rung, when SOURCE A = C5:0.ACC equals the value in SOURCE B = MODULE #, the rung moves the module number to word 1 of the DCM output file. This verifies the start of the data and the module number it’s coming from. Then it copies the four words of analog data to the DCM output words 2 through 5, followed by the module number at word 6 to indicate the end of data.
Module Number Monitored = 2
RUNG 2.2
EQU
MOV
EQUAL Source A
MOVE Source
Source B
C5:0.ACC 0 2
Dest
C5:0.ACC 0 0:1.1 0
COP COPY FILE Source Dest Length
#I:2.0 #0:1.2 4
MOV MOVE Source Dest
C5:0.ACC 0 0:1.6 0
Module Number Monitored = 3
RUNG 2.3
EQU
MOV
EQUAL Source A
MOVE Source
Source B
C5:0.ACC 0 3
Dest
C5:0.ACC 0 0:1.1 0
COP COPY FILE Source Dest Length
#I:3.0 #0:1.2 4
MOV MOVE Source Dest
C5:0.ACC 0 0:1.6 0
8–7
Page 62
Chapter 8 Application Examples
Module Number Monitored = 4
RUNG 2.4
EQU
MOV
EQUAL Source A
MOVE Source
Source B
C5:0.ACC 0 4
Dest
C5:0.ACC 0 0:1.1 0
COP COPY FILE Source Dest Length
#I:4.0 #0:1.2 4
MOV MOVE Source Dest
C5:0.ACC 0 0:1.6 0
Module Number Monitored = 5
RUNG 2.5
EQU
MOV
EQUAL Source A
MOVE Source
Source B
C5:0.ACC 0 5
Dest
C5:0.ACC 0 0:1.1 0
COP COPY FILE Source Dest Length
#I:5.0 #0:1.2 4
MOV MOVE Source Dest
<END>
8–8
C5:0.ACC 0 0:1.6 0
Page 63
Chapter 8 Application Examples
Program Listing for PLC5/15 The following examples are for rungs 2.0 through 2.3. The module number being monitored is shown above the examples. For each rung, the first EQU monitors the module number and the start of the data transfer, while the second EQU monitors the module number and the end of the data transfer. The COP then moves the four words of analog data to an integer file. Module Number Monitored = 2
RUNG 2.0
EQU
EQU
COP
EQUAL Source A
EQUAL Source A
I:016 0 2
COPY FILE Source Dest Length
Source B
I:011 0 2
Source B
#I:012 #N7:0 4
Module Number Monitored = 3
RUNG 2.1
EQU
EQU
COP
EQUAL Source A
EQUAL Source A
I:016 0 3
COPY FILE Source Dest Length
Source B
I:011 0 3
Source B
#I:012 #N7:4 4
Module Number Monitored = 4
RUNG 2.2
EQU
EQU
COP
EQUAL Source A
EQUAL Source A
I:016 0 4
COPY FILE Source Dest Length
I:016 0 5
Source B
I:011 0 4
Source B
#I:012 #N7:8 4
Module Number Monitored = 5
RUNG 2.3
EQU
EQU
COP
EQUAL Source A
EQUAL Source A
COPY FILE Source Dest Length
Source B
I:011 0 5
Source B
#I:012 #N7:12 4
<END> 8–9