Page 191
Setting Up the DH-485 Network
191
Software Considerations Software considerations include the configuration of the network and the parameters that can be set to the specific requirements of the network. The following are major configuration factors that have a significant effect on network performance. • Number of nodes on the network • Addresses of those nodes • Communication rate • Maximum node address selection • SLC 5/03, SLC 5/04, and SLC 5/05 processors only - token hold factor • Maximum number of communicating devices The following sections explain network considerations and describe ways to select parameters for optimum network performance (speed).
Number of Nodes The number of nodes on the network directly affects the data transfer time between nodes. Unnecessary nodes (such as a second programming terminal that is not being used) slow the data transfer rate. The maximum number of nodes on the network is 32.
Setting Node Addresses The best network performance occurs when node addresses start at 0 and are assigned in sequential order. SLC 500 processors default to node address 1. The node address is stored in the processor status file (S:15L). Processors cannot be node 0. Also, initiators such as personal computers should be assigned the lowest numbered addresses to minimize the time required to initialize the network.
Setting Processor Communication Rate The best network performance occurs at the highest communication rate. All devices must be at the same communication rate. The communication rate is stored in the processor status file (S:15H).
Publication 1747-UM011G-EN-P - June 2008
Page 192
192
Setting Up the DH-485 Network
Maximum Node Address Setting The maximum node address parameter should be set as low as possible. This minimizes the amount of time used in soliciting successors when initializing the network. If all nodes are addressed in sequence from 0, and the maximum node address is equal to the address of the highest addressed node, the token rotation will improve by the amount of time required to transmit a solicit successor packet plus the slot timeout value. Note that this does not allow any node to be added to the network without affecting the response time. On the other hand, since the time required to hold an open station address is greater than the time required to pass a token, it can be useful to leave a temporary device (such as a personal computer) connected if there is only one such device. (A solicit successor packet requires the same transmission time as the token pass, but there is an added slot timeout period.) See your programming software user manual for the procedures to set node addresses, processor communication rate, and maximum node addresses. IMPORTANT
The SLC 500 series A (only) processors set the maximum node address to 31 when power is cycled increasing initialization and response time of the network.
Maximum Number of Communicating Devices SLC 500 fixed and SLC 5/01 processors can be selected by two initiators maximum at the same time. Using more than two initiators to select the same SLC 500 fixed and SLC 5/01 processors at the same time can cause communication timeouts.
Publication 1747-UM011G-EN-P - June 2008
Page 193
Setting Up the DH-485 Network
Installing the DH-485 Network
193
To install a DH-485 network, you will need tools to strip the shielded cable and to attach the cable and terminators to the Isolated Link Coupler. Install the DH-485 network using the following tools (or equivalent). Description
Part Number
Manufacturer
Shielded twisted pair cable
Belden #3106A or #9842
Belden
Stripping tool
45-164
Ideal Industries
1/8 in. slotted screwdriver
Not applicable
Not applicable
DH-485 Communication Cable and Isolated Link Coupler The link coupler provides a connection for each node. The isolated link coupler electrically isolates the DH-485 communication interface from the processor and peripheral connections. Electrical-optical isolation is provided to 1500V. The suggested DH-485 communication cable is Belden #3106A or #9842 cable. The cable is jacketed and shielded with two twisted wire pairs and a drain wire. One pair provides a balanced signal line, and one wire of the other pair is used for a common reference line between all nodes on the network. The shield reduces the effect of electrostatic noise from the industrial environment on the network communication.
Installing the DH-485 Communication Cable The communication cable consists of a number of cable segments daisy-chained together. The total length of the cable segments cannot exceed 1219 m (4000 ft). When cutting cable segments, make them long enough to route them from one link coupler to the next with sufficient slack to prevent
Publication 1747-UM011G-EN-P - June 2008
Page 194
194
Setting Up the DH-485 Network strain on the connector. Allow enough extra cable to prevent chafing and kinking in the cable. Belden #3106A or #9842 Cable
Belden #3106A or #9842 Cable
Belden #3106A or #9842 Cable
Link Coupler 1747-AIC
Link Coupler 1747-AIC
Link Coupler 1747-AIC
DH-485
DH-485
DH-485
Connector
Connector
Connector
Peripheral
Peripheral
Peripheral
CPU
CPU
CPU
Power
Power
Power
IMPORTANT
A daisy-chained network is recommended as shown above. We do not recommend the following:
Belden #3106A or #9842 Cable
Connector
Belden #3106A or #9842 Cable
Connector
Belden #3106A or #9842 Cable
Connector
Incorrect
Connecting the Communication Cable to the Isolated Link Coupler Attach the terminal block of the link coupler to the Belden #3106A or #9842 cable as shown below. Additional terminal blocks are available for replacement, see chapter 11.
Publication 1747-UM011G-EN-P - June 2008
Page 195
Setting Up the DH-485 Network
195
Single Cable Connection Orange with White Stripes Belden #3106A or #9842 Shrink Tubing Recommended
White with Orange Stripes
Blue (#3106A) or Blue with White Stripes (#9842)
Drain Wire
6 Termination 5A 4B 3 Common 2 Shield 1 Chassis Ground
Multiple Cable Connection to Previous Device to Successive Device
Wire/Terminal Connections for DH-485 Connectors for Belden #3106A For this wire/pair
Connect this wire
To this terminal
Shield/drain
Non-jacketed
Terminal 2 - Shield
Blue
Blue
Terminal 3 - (Common)
White/drain
White with orange stripe
Terminal 4 - (Data B)
Orange with white stripe
Terminal 5 - (Data A)
Wire/Terminal connections for DH-485 connectors for Belden #9842. For this wire/pair
Connect this wire
To this terminal
Shield/drain
Non-jacketed
Terminal 2 - Shield
Blue/white
White with blue stripe
Cut back - no connection(1)
Blue with white stripe
Terminal 3 - (Common)
White with orange stripe
Terminal 4 - (Data B)
Orange with white stripe
Terminal 5 - (Data A)
White/orange (1)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire immediately after the insulation jacket is removed. This wire is not used by DH-485.
IMPORTANT
In 1747-AIC interface series A, terminal 5 was called DATA B and terminal 4 was called DATA A. In this case, use terminal numbers only and ignore signal names DATA B and DATA A. The internal circuitry of the series A is the same as series B.
Publication 1747-UM011G-EN-P - June 2008
Page 196
196
Setting Up the DH-485 Network
Grounding and Terminating the DH-485 Network Only one of the link couplers at the end of the link must have Terminals 1 and 2 of the network connector jumpered together. This provides an earth ground connection for the shield of the communication cable. Link couplers at both ends of the network must have terminals 5 and 6 of the link connectors jumpered together. This connects the termination impedance (of 120 Ω) that is built into each link coupler as required by the DH-485 specification. See the figure below for the proper jumpering. End-of-line Termination
Jumper
Jumper
6 5
6 5 4
Belden #9842 Cable 1219 m (4000 ft) maximum length
3 2 1
4 3 2 1
Jumper
Powering the Link Coupler In normal operation with the programmable controller connected to the link coupler, the processor powers both the link coupler and peripheral device (DTAM, PIC) if connected through the 1747-C11 cable. If you do not connect the processor to the link coupler, then use a 24V dc power supply to power the link coupler and peripheral device. The 1747-AIC interface requires 85 mA at 24V dc. With a peripheral device connected, the total current required is 190 mA at 24V dc. If both the processor and external power are connected to the link coupler, only the external source is used. IMPORTANT
Publication 1747-UM011G-EN-P - June 2008
Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V dc supply is used.
Page 197
Setting Up the DH-485 Network
197
Below are three options for externally powering the 1747-AIC interface. • If the link coupler is to be installed in an office environment, you can use the 1747-NP1 wall mount power supply or 1747-NP2 global desktop power supply. The link coupler would be powered through either the 1747-C10 cable or by hardwiring from the supply to the screw terminals on the link coupler. • If you use any of the following chassis power supplies (1746-P1, 1746-P2, 1746-P4, 1746-P5, and 1746-P6), you can use the 24V dc user power supply (200 mA maximum) built into the power supply. The link coupler would be powered through a hard-wired connection from the screw terminals on the power supply to the screw terminals on the bottom of the link coupler. • You can use an external dc power supply with the following specifications: – operating voltage: 24V dc + 25% – output current: 190 mA – rated NEC The link coupler would be powered through a hard-wired connection from the external supply to the screw terminals on the bottom of the link coupler. ATTENTION
If you use an external power supply, it must be 24V dc. Permanent damage will result if miswired with wrong power source.
The figure below shows the external wiring connections and specifications of the link coupler.
Publication 1747-UM011G-EN-P - June 2008
Page 198
198
Setting Up the DH-485 Network
Link Coupler
SLC 500 DH-485
LINK COUPLER
CAT
SER
LISTED IND. CONT. EQ. FOR HAZ. LOC. A196
OPERATING TEMPERATURE CODE T3C
CLASS 1, GROUPS A, B, C AND D, DIV. 2 6 TERMINATION 5 A 4 B 3 COMMON 2 SHIELD 1 CHASSIS GROUND
Left Side View EXTERNAL POWER REQUIREMENTS 24 VDC ± 25% A T 190 mA N.E.C. CLASS 2
CAUTION EXTERNAL POWER, IF USED, MUST BE 24VDC PERMANENT DAMAGE TO CIRCUITRY WILL RESULT IF MISWIRED WITH THE WRONG POWER SOURCE. 24VDC
DC NEUT CHS GND
FAC 1P
MADE IN U.S.A.
CHS GND
DC NEUT
24V dc
Bottom View
You can connect an unpowered link coupler to the DH-485 network without disrupting network activity. In addition, if an SLC 500 controller powers a link coupler that is connected to the DH-485 network, network activity will not be disrupted should the SLC 500 controller be removed from the link coupler. Publication 1747-UM011G-EN-P - June 2008
Page 199
Setting Up the DH-485 Network
199
Installing and Attaching the Link Couplers • When installing the link coupler in an enclosure, use care so that the cable connecting the SLC 500 controller to the link coupler does not hit the enclosure door. • Carefully plug the terminal block into the DH-485 port on the link coupler you are putting on the network. Allow enough cable slack to prevent stress on the plug. • Provide strain relief for the cable after it is wired to the terminal block. This guards against breakage of the Belden cable wires.
Publication 1747-UM011G-EN-P - June 2008
Page 200
200
Setting Up the DH-485 Network
Notes:
Publication 1747-UM011G-EN-P - June 2008