Manual · Allen-Bradley
SLC 500 Modular Hardware Style User Manual
Manual296 pagesPDF 3.5 MB
Hardware user manual for Allen-Bradley SLC 500 modular processors, including the 1747-L524 SLC 5/02, covering installation, wiring and troubleshooting.
Covers · 1 model
The models it covers
Summary
What is in it
The hardware user manual for the modular SLC 500 controller family (catalog numbers 1747-L511 through 1747-L553, including the 1747-L524). It explains how to select hardware components, plan and mount the system, identify processor features for the SLC 5/01 to SLC 5/05, install chassis, modules and power supplies, wire I/O modules, start up, maintain and troubleshoot the system. Appendices cover specifications, DH-485, RS-232, DH+ and Ethernet communication, power supply loading and heat dissipation.
Its parts
- Quick Start for Experienced Users
- Selecting Your Hardware Components
- System Installation Recommendations
- Mounting Your SLC 500 Control System
- Identifying the Components of Your Processor
- Installing Your Hardware Components
- Wiring Your I/O Modules
- Starting Up Your Control System
- Maintaining Your Control System
- Troubleshooting
- Replacement Parts
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley user manual (publication 1747-UM011G-EN-P, June 2008) for the SLC 500 modular hardware style processors 1747-L511, 1747-L514, 1747-L524, 1747-L531 to 1747-L533, 1747-L541 to 1747-L543 and 1747-L551 to 1747-L553. It covers selecting, installing, wiring, starting up, maintaining and troubleshooting the processors, chassis, power supplies and I/O, with replacement parts and specifications.
- Product
- SLC 500 modular hardware style processor p. 1, 136
- Battery
- 1747-L524: replaceable lithium battery backs up RAM for about two years; can be changed with power on p. 136
- Memory modules
- 1747-L524: 1747-M1 (1 K user words) or 1747-M2 (4 K user words) EEPROM; 1747-M5 adapter socket p. 42
- Memory socket
- 1747-L524: memory module plugs into a socket on the processor board; jumper J1 is set for the module type p. 103, 104
- Environment
- Operating 0 °C...60 °C; storage -40 °C...85 °C; humidity 5 to 95% without condensation p. 176
- Chassis capacity
- Up to 3 chassis and 30 I/O slots p. 176
- Power-loss hold-up
- Program scan hold-up 20 ms...3 s after loss of power, depending on power supply loading p. 176
- SLC 5/02 features
- SLC 5/02: 4 K instructions program memory, up to 4096 I/O, PID, built-in DH-485 channel, battery-backed RAM p. 83
- SLC 5/02 indicators
- SLC 5/02: RUN, CPU FAULT, FORCED I/O, BATTERY LOW and COMM, all red p. 84, 85
- SLC 5/02 DH-485 defaults
- SLC 5/02: 19.2 K rate, node address 1, maximum node address 31 p. 148
- Programming cables
- 1747-C10 (1.8 m) or 1747-C20 (6.09 m) processor to peripheral cable; 1747-C11 to isolated link coupler p. 169
- Chassis cables
- Chassis interconnect 1746-C7 (152.4 mm), 1746-C9 (914.4 mm), 1746-C16 (1.27 m) p. 169
- Covers and labels
- SLC 5/01 and SLC 5/02 processors: replacement covers and labels 1746-R12 p. 172
- Power supply wiring
- Power supply terminals take two 2 mm2 (#14 AWG) wires p. 104
What this manual walks you through
- Selecting a modular processor by memory, I/O and instructions p. 31
- Selecting a memory module for the SLC 5/01 and SLC 5/02 p. 42
- SLC 5/02 hardware features and status indicators p. 83, 84, 85
- Installing and removing the memory module p. 103, 104
- Installing or replacing the processor battery p. 136
- Troubleshooting SLC 5/01 and SLC 5/02 errors from the status indicators p. 144, 145, 146, 147
- Fixing SLC 5/02 DH-485 communication errors p. 148
- Ordering replacement cables, terminal blocks, fuses and labels p. 169, 170, 171, 172
- Specifications of the processors and 1746 power supplies p. 175, 176, 177
Good to know
- The processor only works in slot 0 of the first chassis. p. 145
- Once BATTERY LOW lights, do not remove processor power or the program may be lost. p. 136
- Turn off controller power before removing the processor or a memory module. p. 103
- Handle memory modules by the carrier ends or housing edges and keep them away from static. p. 103
- Erratic, repeated power cycling can cause a processor major hardware fault. p. 146
Questions this manual answers
How long does the 1747-L524 battery last?
About two years; a red BATTERY LOW indicator warns when it runs low, and it can be replaced while the processor is powered. p. 136
Which memory modules fit the 1747-L524?
The 1747-M1 (1 K user words) and 1747-M2 (4 K user words) EEPROM modules; a 1747-M5 adapter socket is needed to put one in programming equipment. p. 42
What does a flashing CPU FAULT light mean on an SLC 5/02?
At power up it means the processor has not been configured; during operation it means a major error in the processor, expansion chassis or memory. p. 84
What are the default DH-485 settings of an SLC 5/02?
A communication rate of 19.2 K, node address 1 and maximum node address 31. p. 148
Which chassis slot must the SLC processor go in?
Slot 0 of the first chassis. p. 145
Contents
Chapters and sections
Each line opens the PDF at its page.
- SLC 500 Modular Hardware Style User Manual1
- Important User Information2
- Summary of Changes3
- Preface13
- 1 - Quick Start for Experienced Users15
- 2 - Selecting Your Hardware Components27
- 3 - System Installation Recommendations55
- 4 - Mounting Your SLC 500 Control System75
- 5 - Identifying the Components of Your Processor81
- 6 - Installing Your Hardware Components97
- 7 - Wiring Your I/O Modules111
- 8 - Starting Up Your Control System121
- 9 - Maintaining Your Control System133
- 10 - Troubleshooting141
- 11 - Replacement Parts169
- A - Specifications175
- B - Setting Up the DH-485 Network181
- C - RS-232 Communication Interface201
- D - Setting Up the DH+ Network221
- E - Power Supply Worksheet227
- F - Control Networks231
- G - Communicating with Devices on an Ethernet Network237
- H - Calculating Heat Dissipation for the SLC 500 Control System261
- Glossary271
- Index287
- Rockwell Automation Support296
The whole text · 30 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 150141-150
- Pages 151 to 160151-160
- Pages 161 to 170161-170
- Pages 171 to 180171-180
- Pages 181 to 190181-190
- Pages 191 to 200191-200
- Pages 201 to 210201-210
- Pages 211 to 220211-220
- Pages 221 to 230221-230
- Pages 231 to 240231-240
- Pages 241 to 250241-250
- Pages 251 to 260251-260
- Pages 261 to 270261-270
- Pages 271 to 280271-280
- Pages 281 to 290281-290
- Pages 291 to 296291-296
The file