Page 21
Quick Start for Experienced Users
6.
Install the processor.
IMPORTANT
Reference
If your processor has a battery, the battery is an option for the SLC 5/01 (1747-L511) processor, make sure it is connected before installing your processor into the chassis. This provides memory backup for your processor should the controller power supply fail.
Make sure system power is off. Then insert the processor into the 1746 chassis.
IMPORTANT
21
Chapter 2 (Selecting Your Hardware Components) Chapter 6 (Installing Your Hardware Components)
The SLC 500 modular processor must be inserted into the left slot (slot 0), as shown below. Remove the protective label on the power supply after installing the processor.
Module Release Card Guide Protective Label
Publication 1747-UM011G-EN-P - June 2008
Page 22
22
7.
Quick Start for Experienced Users
Apply power to the processor.
Reference
1. Energize the chassis power supply. 2. Check the chassis power supply and processor status indicators. The power status indicator on the power supply should be on and the fault status indicator on the processor should be flashing.
Power supply and SLC 5/01 and SLC 5/02 processor status indicators POWER
RUN
COMM
CPU FAULT FORCED I/O BATTERY LOW
The RUN status indicator on the SLC 5/01 processor is actually labeled PC RUN. Also, the SLC 5/01 processor does not have a COMM status indicator. Power supply and SLC 5/05 processor status indicators
Chapter 8 (Starting Up Your Control System) Chapter 10 (Troubleshooting)
Power supply and SLC 5/03 and SLC 5/04 processor status indicators POWER
RUN
FORCE
FLT BATT
DH485 RS232
The DH485 status indicator on the SLC 5/03 processor is labeled DH+ on the SLC 5/04 processor.
Refer to the following key to determine the status of the status indicators:
POWER RUN
FORCE
Indicates the status indicator is off.
FLT BATT
ENET RS232
Indicates the status indicator is on. Indicates the status indicator is FLASHING. Status of status indicator does not matter.
8.
Load your software.
Refer to your software package’s documentation.
Publication 1747-UM011G-EN-P - June 2008
Reference
Page 23
Quick Start for Experienced Users
9.
Establish communication to the processor.
Reference
Refer to the following to establish communication between the processor and your personal computer.
Chapter 8 (Starting Up Your Control System)
Processor
Procedure
SLC 5/01
Connect 1747-PIC interface from the processor to your personal computer serial port or connect 1747-UIC interface from the processor to your personal computer USB port, or use a 1784-PKTX(D) or 1784-PMCK interface.
SLC 5/02
Connect 1747-PIC interface from the processor to your personal computer serial port or connect 1747-UIC interface from the processor to your personal computer USB port, or use a 1784-PKTX(D) or 1784-PMCK interface.
SLC 5/03
Connect the 1747-PIC interface from the processor to your personal computer serial port or connect the 1747-UIC interface from the processor to your personal computer USB port to the processor by using the 1747-C13 or 1747-CP3 cable. You can also use a 1784-PKTX(D) or 1784-PCMK interface, or a 1747-CP3 cable from channel 0 of the processor to the personal computer serial port.
SLC 5/04
Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial port or connect the 1747-UIC interface from channel 0 of the processor to your personal computer USB port, or use a 1784-PKTX(D) or 1784-PCMK interface.
SLC 5/05
Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial port, or connect the 1747-UIC interface converter from channel 0 of the processor to your personal computer USB port. For Ethernet connection, connect channel 1 of the processor and the PC Ethernet card to an Ethernet hub by using 10/100Base-T compatible cable.(1)
(1)
23
EtherNet/IP address must first be set via BOOTP or an RS-232 connection. See appendix C for more information.
Set the communication parameters of software to match the default parameters of the processor. Comms Channel
Channel 0 Configuration
Channel 1 Configuration
SLC 5/01 and 5/02
SLC 5/03, 5/04, and 5/05 SLC 5/03
SLC 5/04
SLC 5/05
DH-485:
DF1 Full-duplex:
DH-485:
DH+:
Ethernet:
• 19.2 Kbaud
• no handshaking
• 19.2 Kbaud
• 57.6 Kbaud
BOOTP enabled
• node address = 1
• 19.2 Kbaud
• node address = 1
• node address = 1
• CRC Error Check • duplicate packet, detect on • no parity
Publication 1747-UM011G-EN-P - June 2008
Page 24
Quick Start for Experienced Users
24
10.
(Optional) Return the SLC 5/03, SLC 5/04, or SLC 5/05 processor to initial factory conditions.
Use this procedure if the communication channels are shut down due to configuration parameters, or if you absolutely cannot establish communication with the processor.
ATTENTION
If you return the processor to the initial factory conditions, the communication configurations are returned to their default settings and the user program is cleared.
1. Remove power from the SLC 500 power supply. 2. Remove the processor from the chassis. 3. Disconnect the battery by removing the battery connector from its socket. 4. Locate the VBB and GND connections on the right side of the motherboard. 5. Place a small bladed screwdriver across the VBB and GND connections and hold for 60 seconds. This returns the processor to the initial factory conditions.
Publication 1747-UM011G-EN-P - June 2008
Reference Chapter 10 (Troubleshooting)
Page 25
Quick Start for Experienced Users
25
VBB
GND
SLC 5/03 Processors (1747-L531, 1747-L532, and 1747-L533)
Keyswitch
GND VBB
Mother Board Mother Board
Right Side View
SLC 5/04 Processors (1747-L541, 1747-L542, and 1747-L543) SLC 5/05 Processors (1747-L551, 1747-L552, and 1747-L553)
GND VBB
Keyswitch
GND VBB
Mother Board Mother Board
Right Side View
Publication 1747-UM011G-EN-P - June 2008
Page 26
26
Quick Start for Experienced Users
Notes:
Publication 1747-UM011G-EN-P - June 2008
Page 27
Chapter
2
Selecting Your Hardware Components
This chapter provides general information on what your SLC 500 controller can do, an overview of the modular control system, and special considerations for controller installations. It also explains how to select: • chassis. • modular processors. • discrete I/O modules. • specialty I/O modules. • power supplies. • enclosures. • operator interfaces. • memory modules. • isolation transformers. This chapter does not provide you with all the information that you need to select a complete SLC 500 control system. To do this, we recommend that you use the latest version of the system overview, SLC 500 Programmable Controllers and I/O Modules, publication 1747-SG001.
27
Publication 1747-UM011G-EN-P - June 2008
Page 28
28
Selecting Your Hardware Components
European Union Directive Compliance
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment • EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.
Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1.
Publication 1747-UM011G-EN-P - June 2008
Page 29
Selecting Your Hardware Components
Overview of Your Modular Control System
The basic modular controller consists of a chassis, power supply, processor (CPU), Input/Output (I/O modules), and an operator interface device for programming and monitoring. The figure below shows typical hardware components for a modular controller.
Modular Controller
Modular Hardware Components
Power Supply
Processor Module
29
Input Module
Output Module
Combination I/O Module
OR
Programming Personal Computer
Programming Terminal
Chassis
Publication 1747-UM011G-EN-P - June 2008
Page 30
30
Selecting Your Hardware Components
Principles of Machine Control You enter a ladder logic program into the controller by using the software. The logic program is based on your electrical relay print diagrams. It contains instructions that direct control of your application. With the ladder logic program entered into the controller, placing the controller in the Run mode initiates an operating cycle. The controller’s operating cycle consists of a series of operations performed sequentially and repeatedly, unless altered by your ladder logic program.
➄
Overhead
Input
➀ Scan
Service Comms
➁
➃
Program Scan
Operation Cycle
Output Scan
➂
1. Input scan - The time required for the controller to scan and read all input data; typically accomplished within a few milliseconds. 2. Program scan - The time required for the processor to execute the instruction in the program. The program scan time varies depending on the instruction used and each instruction’s status during the scan time. IMPORTANT
Subroutine and interrupt instructions within your logic program may cause deviations in the way the operating cycle is sequenced.
3. Output scan - The time required for the controller to scan and write all output data; typically accomplished within a few milliseconds. 4. Service communication - The part of the operating cycle in which communication takes place with other devices, such as an HHT or a personal computer. 5. Housekeeping and overhead - The time spent on memory. Publication 1747-UM011G-EN-P - June 2008