Page 31

Selecting Your Hardware Components

Selecting Modular Processors

31

SLC 500 modular processors are designed to meet a wide range of applications, from small stand-alone to large distributed systems and from simple to complex applications.

Processor Features Memory size - The SLC 500 modular processors memory is user configurable for either data storage or program storage. Memory size is 1 K...64 K. I/O points - The SLC 5/01 processor supports addressing of up to 3940 I/O. The SLC 5/02, SLC 5/03, SLC 5/04, and SLC 5/05 processors support addressing of 4096 I/O. The SLC 500 modular processors are supported by over 60 different I/O modules including digital, analog, and intelligent I/O. Performance - The SLC 500 modular processors are designed with throughput performance in mind. The program scan time for a typical instruction mix are 0.9 ms/K...8.0 ms/K depending on the processor. I/O scan times are 0.25 ms...2.6 ms depending on the processor and I/O installed in the system. Advanced instruction support - The instructions available depends on the processor used. The following table lists the instructions supported by the SLC 500 modular processors.

Instruction Support

SLC 5/01

SLC 5/02

SLC 5/03

SLC 5/04

SLC 5/05

Bit

•

•

•

•

•

Timer and Controller

•

•

•

•

•

Comparison

•

•

•

•

•

Basic Math

•

•

•

•

•

Move, Copy, and Bit Shift

•

•

•

•

•

Sequencer

•

•

•

•

•

Jump and Subroutine

•

•

•

•

•

Messaging

•

•

•

•

STI

•

•

•

•

FIFO/LIFO

•

•

•

•

PID

•

•

•

•

•

•

•

Advanced Math and Trig

Publication 1747-UM011G-EN-P - June 2008

Page 32

32

Selecting Your Hardware Components

Instruction Support

SLC 5/01

SLC 5/02

SLC 5/03

SLC 5/04

SLC 5/05

Indirect Addressing

•

•

•

Floating Point Math

•

•

•

ASCII

•

•

•

Processor Communication Options The SLC 500 processors support several communication options. The following sections describe the available physical connections and protocol options used by the SLC 500 processors.

Physical Connection Options Ethernet (10/100Base-T) channel offers: • 10/100 Mbps communication rate. • ISO/IEC 8802-3STD 802.3 (RJ45) connector for 10/100Base-T media. • TCP/IP communication protocol. • built-in isolation. Data Highway Plus (DH+) channel offers: • communication rates of 57.6 Kbaud, 115.2 Kbaud, and 230.4 Kbaud. • maximum network length of 3048 m (10,000 ft) at 57.6 Kbaud • Belden 9463 (blue hose) cable connection between nodes (daisy chain connection). • built-in isolation. DH-485 channel offers: • configurable isolation via the 1747-AIC or 1761-NET-AIC interfaces. • maximum network length of 1219 m (4000 ft). • RS-485 electrical specifications. • Belden 9842 or Belden 3106A cable connection between nodes (daisy-chain connection). RS-232 channel offers: • communication rates up to 19.2 Kbaud (38.4 Kbaud SLC 5/04 and SLC 5/05 processors). • maximum distance between devices is 15.24 m (50 ft). Publication 1747-UM011G-EN-P - June 2008

Page 33

Selecting Your Hardware Components

33

• RS-232C (EIA-232) electrical specifications. • modem support. • built-in isolation. Processor Channel Connections Processor

Physical Communication Channel DH-485

RS-232

DH+

Ethernet, - - - DH-485(1), DF1 full-duplex, DF1 half-duplex master/slave, ASCII, DF1 radio modem, and Modbus RTU Master protocols, - DH-485 protocol, - - - DH-485(1), DF1 full-duplex, DF1 half-duplex master/slave, ASCII, DF1 radio modem, and Modbus RTU Master protocols, - - - DH+ protocol, DH-485(1), DF1 full-duplex, DF1 half-duplex master/slave, ASCII, DF1 radio modem, and Modbus RTU Master protocols, - - - - - EtherNet TCP/IP protocol

SLC 5/01 and SLC 5/02 DH-485 protocol SLC 5/03 channel 0 channel 1 SLC 5/04 channel 0 channel 1 SLC 5/05 channel 0 channel 1 (1)

An 1761-NET-AIC interface is required when connecting to a DH-485 network.

Protocol Options EtherNet TCP/IP Protocol - Standard Ethernet, utilizing the TCP/IP protocol, is used as the backbone network in many office and industrial buildings. Ethernet is a local area network that provides communication between various devices at 10/100 Mbps. This network provides the same capabilities as DH+ or DH-485 networks, plus: • SNMP support for Ethernet network management. • optional dynamic configuration of IP addresses by using a BOOTP/DHCP utility. • SLC 5/05 Ethernet data rate up to 40 times faster than SLC 5/04 DH+ messaging. • ability to message entire SLC 5/05 data files. • much greater number of nodes on a single network possible compared to DH-485 (32) and DH+ (64). Data Highway Plus (DH+) Protocol - The Data Highway Plus protocol is used by the PLC-5 family of processors and the SLC 5/04 processor. This protocol is similar to DH-485, except that it can support up to 64 devices (nodes) and runs at faster communication (baud) rates.

Publication 1747-UM011G-EN-P - June 2008

Page 34

34

Selecting Your Hardware Components

DH-485 Protocol - The SLC 500 processors have a DH-485 channel that supports the DH-485 communication network. This network is a multi-master, token-passing network protocol capable of supporting up to 32 devices (nodes). This protocol allows: • monitoring data and processor status, along with program uploading and downloading of any device on the network from one location. • SLC processors to pass data to each other (peer-to-peer communication). • operator interface devices on the network to access data from any SLC processor on the network. DF1 full-duplex protocol - DF1 full-duplex protocol (also referred to as DF1 point-to-point protocol) lets two devices communicate with each other at the same time. This protocol allows: • transmission of information across modems (dial-up, leased line, radio, or direct cable connections). • communication to occur between Allen-Bradley products and third-party products. DF1 half-duplex protocol (master and slave) - DF1 half-duplex protocol provides a multi-drop single master/multiple slave network capable of supporting up to 255 devices (nodes). This protocol also provides modem support and is ideal for SCADA (Supervisory Control and Data Acquisition) applications because of the network capability. ASCII protocol - The ASCII protocol provides connection to other ASCII devices, such as bar code readers, weigh scales, serial printers, and other intelligent devices. DF1 radio modem protocol - The DF1 radio modem protocol, optimized for use with radio modem networks, is a hybrid between DF1 full-duplex protocol and DF1 half-duplex protocol. DF1 radio modem: • supports Store and Forward capability. • uses a node address (0...254) on channel 0. Modbus RTU (Remote Terminal Unit) transmission mode Master protocol The Modbus RTU Master protocol provides communication between Modbus RTU devices through a multi-drop single-master/multiple-slaves network. This protocol is capable of supporting up to 247 slave devices (nodes).

Publication 1747-UM011G-EN-P - June 2008

Page 35

Selecting Your Hardware Components

35

SLC Communication Options Communication Protocol

Processor SLC 5/01

DH-485 peer-to-peer receive only DH-485 via RS232 port DF1 via RS232 port (full-duplex or half-duplex master or slave) ASCII via RS232 port Data Highway Plus (DH+) Ethernet DeviceNet ControlNet Modbus RTU Master, receive only(1), receive only(2)

SLC 5/02

SLC 5/03 receive and initiate receive and initiate, - - receive and initiate(9)

receive and initiate(9)

receive and initiate(9)

receive and initiate receive and initiate receive and initiate receive and initiate receive and initiate receive and initiate receive and initiate(5)

receive and initiate receive and initiate(5)

receive and initiate(6)

receive and initiate(6)

receive and initiate receive only(1), receive only(2)

SLC 5/04

SLC 5/05, - - receive and initiate(3)

receive and initiate(3)(7)

receive and initiate(3)(7)

receive and initiate(3)(7), receive and initiate(4)

receive and initiate(4)(8)

receive and initiate(4)(8)

receive and initiate(4)(8), - initiate only initiate only initiate only

(1)

A 1747-KE or 1770-KF3 interface is required to bridge from DF1 (full-duplex or half-duplex slave only) to DH485 network.

(2)

A ControlLogix gateway with a 1746-DHRIO interface and a 1756-DH485 interface is required to bridge from DH+ to DH-485 network.

(3)

A 1747-SDN module is required for scanning I/O and for explicit messaging on DeviceNet network.

(4)

A 1747-SCNR module is required for scanning I/O and for explicit messaging on ControlNet network.

(5)

The SLC 5/04’s channel-to-channel passthru feature may be used to bridge between DH+ and DH-485 network or between DH+ and DF1 full-duplex network (DH+ to DF1 full-duplex passthru available starting with OS401). Another option is to use the 1785-KE interface to bridge between DH+ and DF1 full-duplex or DH+ and DF1 half-duplex master/slave network.

(6)

A 1761-NET-ENI interface is required to bridge from DF1 full-duplex to Ethernet network.

(7)

A 1761-NET-DNI interface is required to bridge from DF1 to DeviceNet network.

(8)

A 1747-KFC15 module or 1770-KFC15 interface is required to bridge from DF1 to ControlNet network.

(9)

If using 1747-AIC interface for isolation, connect to DH-485 network using 1747-PIC interface. If using a 1761-NET-AIC interface for isolation, connect directly to DH-485 network with 1747-CP3 serial cable (or equivalent RS-232 null-modem cable).

TIP

The 1785-KE module requires the use of a 1771 series chassis and power supply.

Publication 1747-UM011G-EN-P - June 2008

Page 36

36

Selecting Your Hardware Components

Selecting Discrete I/O Modules

There are three types of discrete I/O modules: input, output, and combination. They are available in a wide variety of densities including 4, 8, 16, and 32 point and can interface to ac, dc, and TTL voltage levels. Output modules are available with solid-state ac, solid-state dc, and relay contact type outputs. For a complete listing of discrete I/O modules and specifications, contact your Allen-Bradley sales office for the latest selection guide, publication 1747-SG001.

Selecting Specialty I/O Modules

The SLC 500 family offers specialty I/O modules that enhance your control system. Modules range in function from analog interface to motion control, from communication to high-speed counting. For a complete listing of specialty I/O modules and their specifications, contact your Allen-Bradley sales office for the latest selection guide, 1747-SG001.

Selecting Power Supplies

To select a power supply, you need: • power supply specifications. • power supply worksheet, one for each chassis. • SLC 500 Systems Selection Guide, publication 1747-SG001. When configuring a modular system, you must have a power supply for each chassis. Careful system configuration will result in the best performance. Excessive loading of the power supply outputs can cause a power supply shutdown or premature failure. There are three different ac power supplies and four dc power supplies. For ac power supplies, the 120/240V selection is made by a jumper. Place the jumper to match the input voltage. ATTENTION

Ensure that the power supply jumper is in the correct position before supplying power to the SLC 500 system or personal injury or damage to the system may result.

SLC power supplies have an status indicator that illuminates when the power supply is functioning properly.

Publication 1747-UM011G-EN-P - June 2008

Page 37

Selecting Your Hardware Components

37

1746-P7 Current Capacity 24V dc Output Current

5V dc Output Current

0.87 A

3.6 A

0.625 A

2.64 A

0.46A

2.0 A Input Voltage (dc)

10V

12.2V 15V

19.2V

30V

Example for Selecting Power Supplies Select a power supply for chassis 1 and chassis 2 in the control system below.

Chassis 1

Chassis 2

DH-485 Network

?

?

1747-AIC Interface

?

?

1747-AIC Interface

1747-PIC Interface

Personal Computer

Publication 1747-UM011G-EN-P - June 2008

Page 38

Selecting Your Hardware Components

38

Chassis 1

Slot

0

1 2 3

Slot Numbers

Description

Cat. No.

Power Supply at Power Supply at 5V dc (Amps) 24V dc (Amps)

0

Processor unit

1747-L511

0.090

0.000

1

Input module

1747-IV8

0.050

0.000

2

Transistor output module

1746-OB8

0.135

0.000

3

Triac output module

1746-OA16

0.370

0.000

Peripheral device

Isolated link coupler

1747-AIC

0.000

0.085

0.645

0.085(1)

Total Current: (1)

Chassis 2

? Slot

0

1

2

The 1746-P1 power supply is sufficient for Chassis #1. The internal current capacity for this power supply is 2 A at 5V dc, 0.46 A at 24V dc.

Slot Numbers

Description

Cat. No.

Power Supply at Power Supply at 5V dc (Amps) 24V dc (Amps)

0

Processor unit

1747-L514

0.090

0.000

1

Output module

1746-OW16

0.170

0.180

2

Combination module

1746-IO12

0.090

0.070

3, 4, 5, 6

Analog output modules

1746-NO4I

0.220 (4 x 0.055)

0.780 (4 x 0.195)

Peripheral device

Isolated link coupler

1747-AIC

0.000

0.085

Peripheral device

Interface converter

1746-PIC

Not applicable

Not applicable

0.570

1.115(1)

3 4 5 6

Total Current: (1)

The 1746-P4 power supply is sufficient for Chassis #2. The internal current capacity for this power supply is 10 A at 5V dc, 2.88 A at 24V dc; not to exceed 70 W.

Example Worksheet for Selecting a 1746 Power Supply If you have a multiple chassis system, make copies of the Power Supply Worksheet found on page 230. For a detailed list of device load currents, refer to the SLC 500 Modular Chassis and Power Supplies Technical Data, publication 1746-TD003. TIP

Publication 1747-UM011G-EN-P - June 2008

Consider future system expansion when selecting a power supply.

Page 39

Selecting Your Hardware Components

39

Procedure 1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents. Also include the power consumption of any peripheral devices that may be connected to the processor other than a DTAM or PIC device - the power consumption of these devices is accounted for in the power consumption of the processor.

Chassis Number Slot Number

1 Cat. No.

Maximum Currents

Chassis Number at 5V dc at 24V dc

Slot Number

2 Cat. No.

Maximum Currents at 5V dc at 24V dc

Slot

0

1747-L511

0.090 A

0.000 A

Slot

0

1747-L514

0.090 A

0.000 A

Slot

1

1746-IV8

0.050 A

-

Slot

1

1746-OW16

0.170 A

0.180 A

Slot

2

1746-OB8

0.135 A

-

Slot

2

1746-NO4I

0.055 A

0.195 A

Slot

3

1746-OA16

0.370 A

-

Slot

3

1746-NO4I

0.055 A

0.195 A

Slot

Slot

4

1746-NO4I

0.055 A

0.195 A

Slot

Slot

5

1746-NO4I

0.055 A

0.195 A

Slot

Slot

6

1746-IO12

0.090 A

0.070 A

Slot

Slot 1747-AIC

-

0.085 A

0.570 A

1.115 A

Peripheral Device

1747-AIC

-

0.085 A

Peripheral Device

Peripheral Device Peripheral Device

2.Add the loading currents of all the system devices at 5 and 24V dc to determine the Total Current.

0.645 A

0.085 A

2.Add the loading currents of all the system devices at 5 and 24V dc to determine the Total Current.

3.For 1746-P4 power supplies, calculate the total power consumption of all system devices. If you are not using a 1746-P4 power supply, go to step 4.

Current

Multiply by = Watts

Current

Total Current at 5V dc

0.645 A

5V

3.225 W

Total Current at 5V dc

0.570 A

5V

2.850 W

Total Current at 24V dc

0.085 A

24V

2.040 W

Total Current at 24V dc

1.115 A

24V

26.76 W

User Current at 24V dc

0.500 A

24V

12.00 W

User Current at 24V dc

0.500 A

24V

12.00 W

17.26 W

Add the Watts values to determine Total Power

Add the Watts values to determine Total Power (cannot exceed 70 Watts)

Multiply by = Watts

41.61 W

(cannot exceed 70 Watts)

4.Choose the power supply from the list of catalog numbers shown below. Compare the Total Current required for the chassis with the Internal Current capacity of the power supplies. Be sure that the Total Current consumption for the chassis is less than the Internal Current Capacity for the power supply, for both 5V and 24V loads.

Cat. No.

Internal Current Capacity at 5V dc at 24V dc

1746-P1

2.0 A

0.46 A

1746-P2

5.0 A

1746-P3

3.6 A

1746-P4 (see step 3) 1746-P5

(1)

at 24V dc

1746-P1

2.0 A

0.46 A

0.96 A

1746-P2

5.0 A

0.96 A

0.87 A

1746-P3

3.6 A

0.87 A

10.0 A

2.88 A

1746-P4 (see step 3)

10.0 A

2.88 A

5.0 A

0.96 A

1746-P5

5.0 A

0.96 A

5.0 A

0.96 A

1746-P6

2.0 A

0.46 A

1746-P7(1)

24V dc input

3.6 A

0.87 A

Required Power Supply

Internal Current Capacity at 5V dc

12V dc input

1746-P6 1746-P7(1)

Cat. No.

1746-P1

5.0 A

0.96 A

12V dc input

2.0 A

0.46 A

24V dc input

3.6 A

0.87 A

Required Power Supply

1746-P4

See 1746-P7 current capacity graph on page 37.

Publication 1747-UM011G-EN-P - June 2008

Page 40

40

Selecting Your Hardware Components

Selecting Enclosures

The enclosure protects the equipment from atmospheric contamination. Standards established by the National Electrical Manufacturer’s Association (NEMA) define enclosure types, based on the degree of protection an enclosure will provide. Use a fan to circulate the air of sealed enclosures that use convection cooling to dissipate heat. Select a NEMA-rated enclosure that suits your application and environment. The enclosure should be equipped with a disconnect device. To calculate the heat dissipation of your controller, see appendix H.

Selecting Operator Interfaces

Use an operator interface to program and/or monitor your SLC 500 controller. You can choose from several Allen-Bradley operator interface devices.

Programming with a Personal Computer Contact Rockwell Software or your local Allen-Bradley distributor for specifications and availability of software packages available to program the SLC 500 Modular Controllers.

AIC+ Advanced Interface Converter (1761-NET-AIC) The AIC+ advanced interface converter provides communication links between various networked devices. It has three communication ports: one for DH-485 and two for RS-232. The AIC+ converter is compatible with a variety of SLC and MicroLogix controllers and peripherals.

1747-PIC RS-232/DH485 Interface Converter For communication with a SLC 5/01, SLC 5/02, or SLC 5/03 processor, you can use an RS-232/DH-485 interface convertor (catalog number 1747-PIC) between the computer and SLC controller. The converter includes a 279.4 mm (11 in.) ribbon cable, already attached to the converter, for connection to the computer serial port and a catalog number 1746-C10 cable for connection to the controller. If you are using an SLC 5/03, SLC 5/04, or SLC 5/05 processor, you do not need the 1747-PIC interface. You can program via the RS-232 channel using DF1 full-duplex protocol or DH485 protocol and RS-232 program cable (catalog number 1747-CP3). Publication 1747-UM011G-EN-P - June 2008