Page 41
Selecting Your Hardware Components
41
1747-UIC USB to DH485 Interface Converter For communication with an SLC 5/01 through SLC 5/05 processor, you can connect the 1747-UIC interface between the computer’s USB port and the SLC controller. The 1747-UIC interface features an RS-232 port for communication with SLC 5/03 and later processors and an RS-485 port for communication with SLC 5/03 and previous processors.
Monitoring with a Data Table Access Module The Data Table Access Module (DTAM) is a plant floor device that lets you access data file information, change operating modes, monitor and clear processor faults, and transfer the user program between RAM and an EEPROM memory module with any SLC 5/01, SLC 5/02, or SLC 5/03 (except for the 1747-L533 processor) processor. You cannot use it to create new programs. Important features of DTAM include: • shorthand addressing, which provides easier access to data files. • display prompts in six, user-selectable languages: English, French, German, Italian, Spanish, and Japanese. • UL listed to US and Canadian Safety Standards. • NEMA type 12 and 13 enclosures. • point-to-point interface to an SLC family processor, or as a network device on a DH-485 network.
Monitoring with a PanelView or PanelView Plus Operator Terminal The PanelView or PanelView Plus operator terminals provide operator interface capabilities in space-saving, flat-panel designs. Offering optimum viewing angles, these electronic operator interfaces feature pixel graphics and high-performance functionality in both color and monochrome displays. The PanelView operator terminals let you enter input by using function keys or a touch screen, depending upon the model. All PanelView and PanelView Plus operator terminals are available with DF1 or DH-485 (RS-232) communication capability, letting them communicate directly with channel 0 on an SLC 5/03, SLC 5/04, or SLC 5/05 processor. The larger versions also offer DH-485 (RJ-45), DH+, Remote I/O, Ethernet, DeviceNet, and ControlNet network connectivity. Publication 1747-UM011G-EN-P - June 2008
Page 42
42
Selecting Your Hardware Components
Selecting a Memory Module for the SLC 5/01 and SLC 5/02 Processors
You can plug these optional EEPROM (Electrically Erasable Programmable Read Only Memory) memory modules into the SLC 500 controller. With a memory module, you can: • save the contents of the processor RAM for storage purposes. • load the contents of the EEPROM memory into the processor RAM. Adapter sockets (catalog number 1747-M5) are required when inserting EEPROMs or UVPROMs into the programming and erasing equipment. To program a memory module, see your programming software user manual.
EEPROM Memory Modules These optional memory modules provide a non-volatile memory back-up in a convenient modular form. The modules plug into a socket on the processor. You can store (save) your program in the EEPROM by inserting it into the processor and programming software to download the program. You can use an EEPROM module as a master, or you can use an archived processor file as the source by using the software PROM translator utility. Adapter sockets are required when inserting memory modules into commercially available PROM programmer. The memory module fits into the adapter socket and then into a PROM programmer.
ATTENTION
Make sure the adapter is inserted properly into the programming equipment or damage could result.
Memory Module Compatibility Use with this processor type Cat. No.
Publication 1747-UM011G-EN-P - June 2008
Description
SLC 5/01
SLC 5/02
1747-L511
1747-L514
1747-L524
1747-M1
1 K User Words EEPROM
X
X
X
1747-M2
4 K User Words EEPROM
X
X
X
1747-M5
Adapter Socket
X
X
X
Page 43
Selecting Your Hardware Components
43
Memory Backup for the 1747-L511, SLC 5/01 Processor The curve below illustrates the ability of the memory back-up capacitor to maintain the contents of the RAM in a 1747-L511 processor. To back up the memory for a longer period of time, a lithium battery, catalog number 1747-BA, is required.
Capacitor Memory Back-up Time VS Temperature
30 25
Time (Days)
20 15 10 5 0 0
5 (41˚F)
10 (50˚F)
15 (59˚F)
20 (68˚F)
25 (77˚F)
30 (86˚F)
35 40 45 50 55 60 (95˚F) (104˚F) (113˚F) (122˚F) (131˚F) (140˚F)
Temperature °C (°F)
Selecting a Memory Module for SLC 5/03, SLC 5/04, and SLC 5/05 Processors
The memory module for the SLC 5/03, SLC 5/04, and SLC 5/05 processors is called Flash EPROM (Flash Erasable Programmable Read Only Memory). Flash EPROMs combine the programming versatility of EEPROMs with the security precautions of UVPROMs. This means that you have the option of leaving your EPROM programs write-protected or unprotected. Write-protect the EPROM by using either your software or a PROM programmer. The memory modules consist of a Flash EPROM mounted on a circuit board with a connector and plastic housing. Adapter sockets (catalog number 1747-M15) are required when inserting memory modules into commercially available PROM
Publication 1747-UM011G-EN-P - June 2008
Page 44
44
Selecting Your Hardware Components programmer. The 1747-M15 Series B adapter socket is required for use with the memory module (catalog number 1747-M13). ATTENTION
Make sure the adapter is inserted properly in the programming equipment or damage could result.
See the table below for details on the Flash EPROM and adapter socket. Memory Module Compatibility Use with this processor type Cat. No.
SLC 5/03
Description
SLC 5/04
SLC 5/05
1747-L531, 1747-L532, 1747-L541, 1747-L542, 1747-L551, 1747-L552, 1747-L533 1747-L543 1747-L553 1747-M13
Supports up to 64 K of user-memory backup
X (Series C OS302 or later)
X (Series C OS401 or later)
X (Series C OS501 or later)
To program a memory module, refer to your programming software user manual or help resource. Follow this procedure to program a memory module. 1. Set the memory module configuration bits (S:1/10 to S:1/12) in your offline program file. Refer to SLC 500 Instruction Set Reference Manual, publication 1747-RM001, for details on the Memory Module Configuration Bits. 2. Download your program file to your processor. 3. Go online with the processor and burn the program to the EEPROM memory module (per the instructions outlined in your programming software user manual or help resource).
EEPROM Burning Options
You can burn a program into an EEPROM memory module using a processor that is the same or different from the one used to run the program. When burning EEPROMs, keep the following conditions in mind: • The processor burning the EEPROM must be of the same type and have the same OS version or lower than the target processor.
Publication 1747-UM011G-EN-P - June 2008
Page 45
Selecting Your Hardware Components
45
• The program size cannot exceed the processor memory size. For instance, an SLC 5/01 4 K processor can burn an EEPROM for a SLC 5/01 1 K processor as long as the program does not exceed 1 K. • The I/O and chassis configuration of the burning processor does not have to match the I/O configuration of the program being burned. • You do not have to enter the Run mode before burning an EEPROM. If the run mode is entered and the chassis configuration does not match, a major fault will occur. If you burn an EEPROM while in the fault mode, the fault will also be saved in the EEPROM. The following table summarizes the above conditions as to the type of processor you can use to burn EEPROMs for other processors.
EEPROM Burning Options To burn EEPROMs for these processors SLC 5/05 (16K)
SLC 5/05 (32K)
SLC 5/05 (64K)
SLC 5/05 (16K)
•
16 K max
16 K max
SLC 5/05 (32K)
16 K max
•
32 K max
SLC 5/05 (64K)
16 K max
32 K max
•
SLC 5/04 (16K)
SLC 5/04 (32K)
SLC 5/04 (64K)
SLC 5/04 (16K)
•
16 K max
16 K max
SLC 5/04 (32K)
16 K max
•
32 K max
SLC 5/04 (64K)
16 K max
32 K max
•
SLC 5/03
SLC 5/03 (8K)
SLC 5/03 (16K)
(32K)
SLC 5/03 (8K)
•
8K max
8K max
SLC 5/03 (16K)
8K max
•
16 K max
SLC 5/03 (32K)
8K max
16 K max
•
SLC 5/01 (1K)
SLC 5/01 (4K)
SLC 5/01 (1K)
•
1 K max
SLC 5/01 (4K)
1 K max
•
Use these processors
SLC 5/02 (4K)
SLC 5/02 (4K)
•
• valid combination
Publication 1747-UM011G-EN-P - June 2008
Page 46
46
Selecting Your Hardware Components
Selecting Isolation Transformers
If there is high frequency conducted noise in or around your distribution equipment, use an isolation transformer in the ac line to the power supply. This type of transformer provides isolation from your power distribution system and is often used as a step down transformer to reduce line voltage. Any transformer used with the controller must have a sufficient power rating for its load. This power rating is generally expressed in voltamperes (VA). To select an appropriate isolation transformer, calculate the power required by the chassis power supply (or supplies if more than one chassis in system) and any input circuits and output loads that are connected through this transformer. You can find the power requirement (VA rating) for the chassis power supplies in the specifications starting on page 177. The power requirement for the input circuits is determined by the number of inputs, the operating voltage, and the nominal input current. The power requirement for output loads is determined by the number of outputs, the load voltage, and load current. For example, if you have a 1746-P1 power supply, a 16-point ac input module, catalog number 1746-IA16, (12 mA at 120V ac) and a 16-point ac triac output module, catalog number 1746-OA16, (0.5A at 120V ac), the power consumed would be: 135VA + (16)(120V)(0.012 A) + (16)(120V)(0.5 A) = 1118VA
IMPORTANT
In this case, 0.5 A is the maximum rating of the triac output at 30 °C (86 °F). If the load draws less than 0.5 A, this figure may be reduced accordingly. The output portion of the VA calculation should reflect the current requirements of selected loads.
In general, we recommend that the transformer is oversized to provide some margin for line voltage variations and other factors. Typically a transformer that is 25% larger than the calculated VA is sufficient. Most industrial environments are susceptible to power transients or spikes. To help insure fault-free operation and protection of equipment, use suppression devices on power line to the equipment in addition to the isolation equipment.
Publication 1747-UM011G-EN-P - June 2008
Page 47
Selecting Your Hardware Components
Special Considerations
47
The recommendations given previously provide favorable operating conditions for most controller installations. Some applications may involve adverse conditions, such as excessive line voltage variations and/of excessive noise, as described below. Additional measures can be taken to minimize the effect of these conditions.
Class I, Division 2 Applications IMPORTANT
When installing peripheral devices (for example, push buttons, lamps) into a hazardous environment, ensure that they are Class I, Division 2 certified, or determined to be safe for the environment.
Excessive Line Voltage Variations The best solution for excessive line voltage variation is to correct any feeder problems in your distribution system. Where this does not solve the line variation problem, or in certain critical applications, use a constant voltage transformer. If you require a constant voltage transformer, connect it to the power supply and all input devices connected to the SLC 500 controller. Connect output devices on the same power line, but their connection along the power line is normally made before the constant voltage transformer. A constant voltage transformer must have a sufficient power rating for its load.
Excessive Noise When operating the SLC 500 controller in an environment with a high amount of electrical noise, give special consideration to the possibility of electrical interference. The following reduces the effect of electrical interference. • SLC 500 controller design features • Proper mounting of controller within an enclosure • Proper equipment grounding • Proper routing of wires (power, communication, control lines) • Proper suppression added to noise generating devices Potential sources of noise include inductive loads, such as relays, solenoids, and motor starters when operated by hard contacts like push buttons or selector switches. Suppression may be necessary
Publication 1747-UM011G-EN-P - June 2008
Page 48
48
Selecting Your Hardware Components when such loads are connected as output devices or when connected to the same supply line that powers the controller. Lack of surge suppression on inductive loads may contribute to processor faults and sporadic operation. RAM can be corrupted (lost) and I/O modules may appear to be faulty or reset themselves. For extremely noisy environments, use a memory module and program it for auto-loading on processor fault or power cycle for quick recovery.
Selecting Surge Suppressors Most output modules have built-in surge suppression to reduce the effects of high voltage transients. However, you should use an additional suppression device if an output module is being used to control an inductive device such as: • relays. • motor starters. • solenoids. • motors. Additional suppression is especially important if your inductive device is in series with or parallel to a hard contact such as: • push buttons. • selector switches. By adding a suppression device directly across the coil of an inductive device, you reduce the effects of voltage transients caused by interrupting the current to that inductive device and prolong the life of the switch contacts. You also prevent electrical noise from radiating into system wiring. The diagram below shows an output module with a suppression device.
Publication 1747-UM011G-EN-P - June 2008
Page 49
Selecting Your Hardware Components
49
Surge Suppression Diagram + dc or L1 VAC/VDC Snubber
Out 0 Out 1 Out 2 ac or dc Output Module
Out 3 Out 4 Out 5 Out 6 Out 7 COM dc COM or L2
If you connect an SLC 500 controller triac output to control an inductive load, use varistors to suppress noise. Choose a varistor that is appropriate for the application. We recommend the following surge suppressors for triac outputs when switching 120V ac inductive loads: • Harris MOV, part number V220 MA2A • Allen-Bradley MOV, catalog number 599-K04 or 599-KA04, Series C or later. Consult the varistor manufacturer’s data sheet when selecting a varistor for your application. ATTENTION
Damage could occur to SLC 500 triac outputs if you use suppressors having RC networks and the triac load current is 15 mA or less.
Allen-Bradley surge suppressors recommended for use with Allen-Bradley relays, contactors, and starters are shown in the table below. Devices Requiring Surge Suppression Device
Coil Voltage
Suppressor Cat. No.
Bulletin 509 Motor Starter Bulletin 509 Motor Starter
120V ac 240V ac
599-K04 (1) 599-KA04(1)
Bulletin 100 Contactor Bulletin 100 Contactor
120V ac 240V ac
199-FSMA1 (2), 199-GSMA1() 199-FSMA2 (2)
Bulletin 709 Motor Starter
120V ac
1401-N10(2)
Bulletin 700 Type R, RM Relays ac coil none required
Publication 1747-UM011G-EN-P - June 2008
Page 50
50
Selecting Your Hardware Components
Devices Requiring Surge Suppression Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
12V dc 12V dc
199-FSMA9
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
24V dc 24V dc
199-FSMA9
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
48V dc 48V dc
199-FSMA9
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
115-125V dc 115-125V dc
199-FSM10
Bulletin 700 Type R Relay Bulletin 700 Type RM Relay
230-250V dc 230-250V dc
199-FSMA11
Bulletin 700 Type N, P, or PK Relay
150V max, ac or dc
700-N24(2)
Miscellaneous electromagnetic devices limited to 35 sealed VA
150V max, ac or dc
700-N24(2)
(1)
Varistor
(2)
RC Type – Damage could occur with SLC 500 triac outputs if you use suppressors having RC networks and the load current is 15 mA or less.
Selecting Contact Protection Inductive load devices such as motor starters and solenoids may require the use of some type of surge suppression to protect the controller output contacts. Switching inductive loads without surge suppression can significantly reduce the lifetime of relay contacts. Surge Suppression for Inductive Load Devices Surge Suppression for Inductive ac Load Devices
Output Device
Output Device
Output Device
Surge Suppressor Varistor
RC Network Surge Suppression for Inductive DC Load Devices
-
+ Output Device
Diode (A surge suppressor can also be used.) Contact protection methods for inductive ac and DC output devices.
These surge suppression circuits connect directly across the load device. This reduces arcing of the output contacts. (High transient can cause arcing that occurs when switching off an inductive device.) Publication 1747-UM011G-EN-P - June 2008