Page 51
Selecting Your Hardware Components
51
Suitable surge suppression methods for inductive ac load devices include a varistor, an RC network, or an Allen-Bradley surge suppressor. These components must be appropriately rated to suppress the switching transient characteristic of the particular inductive device. For inductive dc load devices, a diode is suitable. A diode, catalog number 1N4004, is acceptable for most applications. A surge suppressor can also be used. See the table on page 49. Locate the suppression device as close as possible to the load device.
Transistor Output Transient Pulses This section applies to the following SLC 500 fixed I/O processors and SLC 500 I/O modules that have transistor outputs. Fixed I/O processors with transistor outputs
I/O modules with transistor outputs
• 1747-L20E
• 1746-OB8
• 1746-OBP16
• 1747-L20G
• 1746-OBP8
• 1746-OV16
• 1747-L20L
• 1746-OV8
• 1746-OVP16
• 1747-L20N
• 1746-OB16
• 1746-OB32
• 1747-L30L
• 1746-OB16E
• 1746-OB32E
• 1747-L40E
• 1746-OB16EI
• 1746-OV32
• 1747-L40L
For the SLC 500 products listed above, the maximum duration of the transient pulse occurs when minimum load is connected to the output. However, for most applications the energy of the transient pulse is not sufficient to energize the load. ATTENTION
A transient pulse occurs in transistor outputs when the external dc supply voltage is applied to the common output terminals (for example, via the master control relay). The sudden application of voltage creates this transient pulse. (See the following graph.) This condition is inherent in transistor outputs and is common to solid state devices. A transient pulse can occur regardless of the processor having power or not.
Publication 1747-UM011G-EN-P - June 2008
Page 52
52
Selecting Your Hardware Components
Transient Pulse
Current Transient (I)
(On-State Load Current)
Duration of Transient (T) Time
To reduce the possibility of inadvertent operation of devices connected to transistor outputs, adhere to the following guidelines: • Either ensure that any programmable device connected to the transistor output is programmed to ignore all output signals until after the transient pulse has ended, • Add an external resistor in parallel to the load to increase the on-state load current. The duration of the transient pulse is reduced when the on-state load current is increased. The duration of the transient pulse is proportional to the load impedance. This is illustrated in the following graph. Transient Pulse/Load Impedance Graph 10 9 8
Duration of Transient (ms)
7 6 5 4 3 2 1 0 1
Publication 1747-UM011G-EN-P - June 2008
100
200
400 500 600 700 300 On-State Load Current (mA)
800
900 1000
Page 53
Selecting Your Hardware Components
EXAMPLE
53
Increasing the load current by 100 mA decreases the transient time from approximately 7 ms to less than 2.5 ms. To calculate the size of the resistor added in parallel to increase the current, use the following information: 24V = your applied voltage Need 100 mA of load current to reduce the transient to <2.5 ms. (taken from graph). R (W) = V (Volts)/I (Amps) Resistor value (Ohms) = Applied voltage (Volts)/Desired current (Amps) = 24/0.1 = 240 W P (Watts) = 12 (Amps) x R (W) Actual Power (Watts) = (Desired Current)2 x Resistor Value = (0.1)2 x 240 = 2.4 (Watts) Resistor size = 2 x Actual power (Watts) = 4.8 W = approximately 5 W Use a resistor rated for 240 W at 5 W to decrease the transient time from approximately 7 ms to less than 2.5 ms.
Publication 1747-UM011G-EN-P - June 2008
Page 54
54
Selecting Your Hardware Components
Notes:
Publication 1747-UM011G-EN-P - June 2008
Page 55
Chapter
3
System Installation Recommendations
To help you install the SLC 500 programmable controller as safely and securely as possible, follow the specific recommendations in this chapter. For general installation guidelines, also refer to the requirements specific to your region. • Europe: Reference the standards found in EN 60204 and your national regulations. • United States: Refer to article 70E of the National Fire Protection Association (NFPA). It describes electrical safety requirements for employee workplaces. This chapter covers the following: • System overview • Typical installation • Spacing your controllers • Preventing excessive heat • Grounding guidelines • Master control relay • Power considerations • Safety considerations • Preventive maintenance
55
Publication 1747-UM011G-EN-P - June 2008
Page 56
56
System Installation Recommendations
System Overview
Refer to the following sections when planning your system layout.
Environment and Enclosure ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6561.7 ft) without derating. This equipment is considered Group I, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements pertaining to this equipment.
Publication 1747-UM011G-EN-P - June 2008
Page 57
System Installation Recommendations
57
Hazardous Location Considerations Products marked CL1, DIV 2, GP A, B, C, D are suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD • Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be non-hazardous. Secure any external connections that mate to this equipment using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • All wiring must comply with N.E.C. article 501-4(b).
Publication 1747-UM011G-EN-P - June 2008
Page 58
58
System Installation Recommendations
Typical Installation
The figure below consists of some components that make up a typical installation.
1. NEMA-rated enclosure suitable for your application and environment that shields your controller from electrical noise and airborne contaminants.
(1) (4) MCR
2. Disconnect device, to remove power from the system
(2) Disconnect Device
(6) (3) Isolation Transformer
3. Fused isolation transformer or a constant voltage transformer, as your application requires (5)
4. Master control relay/emergency-stop circuit
SLC 500 Controller
5. Terminal blocks or wiring ducts 6. Suppression devices for limiting EMI (electromagnetic interference) generation
ATTENTION
Spacing Your Controller
The figure on the following page depicts acceptable layouts. Follow the recommended minimum spacing to allow for convection cooling within the enclosure. Air temperature in the enclosure must be kept within a range of 0 °C...60 °C (32 °F...140 °F). IMPORTANT
Publication 1747-UM011G-EN-P - June 2008
Vertical mounting is not recommended due to thermal considerations.
Be careful of metal chips when drilling mounting holes for the controllers. Do not drill holes above a mounted SLC 500 controller.
Page 59
System Installation Recommendations
IMPORTANT
C
59
The 1746-C9 and 1746-C16 cables have a rigid, unbendable shrink wrap applied at the end of each connector, which provides strain relief. When using these cables, provide at least 101.6 mm (4 in.) of clearance at the side of the chassis to allow for proper bend radius of the cable.
SLC 500 Controller
SLC 500 Controller
C
1746-C9 Cable
A
A
1746-C7 Cable
SLC 500 Controller
B
B
C
SLC 500 Controller
D
1746-C9 Cable
B
B
SLC 500
A
Recommended Spacing
1746-C9 Cable
B
A. 15.3...20.0 cm (6...8 in.) when using the 1746-C9 cable. If you mount two 13-slot chassis above each other, the distance cannot exceed 10.2...12.7 cm (4...5 in.). B. Greater than 10.2 cm (4 in.). C. Greater than 15.3 cm (6 in.).
C
SLC 500 Controller
D. 6.35...10.2 cm (2.5...4 in.) when using the 1746-C7 cable. If you are using a 1746-P4 power supply, your maximum spacing is 6.35 cm (2.5 in.).
Publication 1747-UM011G-EN-P - June 2008
Page 60
60
System Installation Recommendations
Preventing Excessive Heat
For most applications, normal convection cooling will keep the SLC 500 controller components within the specified operating range of 0 °C...60 °C (32 °F...140 °F). Proper spacing of components within the enclosure is usually sufficient for heat dissipation. In some applications, a substantial amount of heat is produced by other equipment inside or outside the enclosure. In this case, place blower fans inside the enclosure to assist in air circulation and to reduce hot spots near the SLC 500 controller. Additional cooling provisions might be necessary when high ambient temperatures are encountered. IMPORTANT
Publication 1747-UM011G-EN-P - June 2008
Do not bring in unfiltered outside air. It may introduce harmful contaminants of dirt that could cause improper operation or damage to components. In extreme cases, you may need to use air conditioning to protect against heat build-up within the enclosure.