Page 11

Table of Contents

11

Appendix F Control Networks

Allen-Bradley Remote I/O Network . . . . . . . . . . . . . . . . . . . . . . . . . 231 Remote I/O Passthru . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 The 1747-SDN DeviceNet Scanner . . . . . . . . . . . . . . . . . . . . . . . 233 The 1761-NET-DNI DeviceNet Interface . . . . . . . . . . . . . . . . . 234 DeviceNet Network Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 ControlNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 The 1747-SCNR ControlNet Scanner Module . . . . . . . . . . . . . . 236 The 1747-KFC15 ControlNet Messaging Module. . . . . . . . . . . . 236

Appendix G Communicating with Devices on an Ethernet Network

SLC 5/05 Processors and Ethernet Communication. . . . . . . . . . . . . 237 SLC 5/05 Performance Considerations . . . . . . . . . . . . . . . . . . . . . . . 238 SLC 5/05 Processor and Personal Computer Connections to the Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 Ethernet Network Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 Ethernet Channel 1 8-pin 10Base-T Connector. . . . . . . . . . . . . . 240 Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 Configuring the Ethernet Channel on the SLC 5/05 Processor . . . . 241 Configuration Using RSLogix 500 Programming Software . . . . . . . . 242 Configuration Via BOOTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 Use the Rockwell BOOTP Utility. . . . . . . . . . . . . . . . . . . . . . . . . 244 Using DCHP Software To Configure Your Processor . . . . . . . . . . . 245 Using Subnet Masks and Gateways. . . . . . . . . . . . . . . . . . . . . . . . . . . 246 Manually Configuring Channel 1 for Processors on Subnets . . . 247 SLC 5/05 Processor Embedded Web Server Capability . . . . . . . . . . 248 Module Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249 TCP/IP Configuration Data (Read Only) . . . . . . . . . . . . . . . . . . 249 Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Data Table Memory Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251 Data Table Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 User Provided Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253

Appendix H Calculating Heat Dissipation for the SLC 500 Control System

Definition of Key Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 Calculating Module Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . 261 Calculated Watts vs. Total Watts. . . . . . . . . . . . . . . . . . . . . . . . . . 262 Power Supply Loading Reference Table. . . . . . . . . . . . . . . . . . . . 263 Power Supply Heat Dissipation Graphs . . . . . . . . . . . . . . . . . . . . 266 Example Heat Dissipation Calculation . . . . . . . . . . . . . . . . . . . . . . . . 267 Example Worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 Blank Worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269

Publication 1747-UM011G-EN-P - June 2008

Page 12

12

Table of Contents

Glossary Index

Publication 1747-UM011G-EN-P - June 2008

Page 13

Preface

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning: • who should use this manual. • the purpose of this manual. • related documentation. • conventions used in this manual.

Who Should Use This Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use SLC 500 programmable controllers. You must have a basic understanding of electrical circuitry and familiarity with relay logic.

Purpose of This Manual

This manual describes the procedures you use to install, wire, and troubleshoot your controller. This manual: • explains how to install and wire your controllers. • gives you an overview of the SLC 500 programmable controller system. Refer to the SLC 500 Instruction Set reference manual, publication 1747-RM001, for the SLC 500 instruction set and for application examples to show the instruction set in use. Refer to your programming software user documentation for more information on programming your SLC 500 programmable controller.

13

Publication 1747-UM011G-EN-P - June 2008

Page 14

14

Preface

Additional Resources

The table below provides a listing of publications that contain important information about SLC 500 controller systems.

Pub. Number

Pub. Title

Description

1747-SG001

SLC 500 System Overview

An overview of the SLC 500 family of products.

1747-IN007

SLC 5/03 and SLC 5/04 Processors Firmware/Operating System Upgrade Installation Instructions

Details on the latest operating system upgrade to the SLC 5/03 and SLC 5/04 processors.

1747-IN019

SLC 5/05 Processors Firmware/Operating System ControlFlash Information on the SLC 5/05 ControlFlash upgrade. Upgrade Installation Instructions

1747-RM001

SLC 500 Instruction Set Reference Manual

Detailed information on the SLC instruction set.

1761-UM004

Advanced Interface Converter (AIC+) User Manual

A description on how to install and connect an AIC+ interface. This manual also contains information on network wiring.

1761-UM005

DeviceNet Interface User Manual

Information on how to install, configure, and commission a DNI interface.

1761-UM006

MicroLogix Ethernet Interface User Manual

Information on using the 1761-NET-ENI Ethernet interface.

1770-6.5.16

DF1 Protocol and command Set Reference Manual

Information on DF1 protocol.

GMC-RM001

System Design for Control of Electrical Noise

Information on reducing electrical noise.

1770-4.1

Allen-Bradley Programmable controller Grounding and Wiring Information on grounding and wiring Allen-Bradley Guidelines programmable controllers.

SGI-1.1

Application Considerations for Solid-state Controls, publication

A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices., National Electrical Code - Published by the National Fire Protection Association of Boston, MA

An article on wire sizes and types for grounding electrical equipment.

AG-7.1

Allen-Bradley Industrial Automation Glossary

A glossary of industrial automation terms and abbreviations.

You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documents, contact your local Rockwell Automation distributor or sales representative.

Common Techniques Used in This Manual

Publication 1747-UM011G-EN-P - June 2008

The following conventions are used throughout this manual: • Bulleted lists, such as this one, provide information, not procedural steps. • Numbered lists provide sequential steps or hierarchical information.

Page 15

Chapter

1

Quick Start for Experienced Users

This chapter can help you to get started using the SLC 500 Modular Processors. We base the procedures here on the assumption that you have an understanding of SLC 500 products. You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application. Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more information. If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information. This chapter: • tells you what tools and equipment you need. • lists how to install your chassis. • lists how to install and wire your power supply. • lists how to install and apply power to your processor. • lists how to establish communication with the processor. • describes how to return the SLC 5/03, SLC 5/04, and SLC 5/05 processors to initial factory conditions if required.

15

Publication 1747-UM011G-EN-P - June 2008

Page 16

16

Quick Start for Experienced Users

Required Tools and Equipment

Have the following tools and equipment ready: • Medium blade screwdriver • Programming equipment • Compatible communication cable and/or interface (The table below indicates with an X, which cables are compatible with the SLC 5/01 through 5/05 processors.) Network Interface

Processor SLC 5/01

SLC 5/02

SLC 5/03

SLC 5/04

SLC 5/05

1747-UIC

X(1)

X(1)

X(1)(4)

X(4)

X(4)

1747-PIC

X

X

X X

X

X

1747-CP3 1784-PKTX(D)

X(2)

X(2)

X(2)

X

1784-PCMK

X(3)

X(3)

X(3)

X(5)

10/100Base-T Ethernet (1)

Requires 1747-C13 cable.

(2)

Requires 1784-CP14 cable.

(3)

Requires 1784-PCM4 cable.

(4)

Requires 1747-CP3 cable.

(5)

Requires 1784-PCM6 cable.

X

Procedures 1.

Check the contents of the shipping box.

Unpack the shipping boxes making sure that the contents include: • SLC 500 modular processor – installation instructions (publication 1747-IN009) • SLC 500 modular chassis (catalog numbers 1746-A4, 1746-A7, 1746-A10, or 1746-A13) – installation instructions (publication 1746-IN016) • SLC 500 modular power supplies (catalog numbers 1746-P1, 1746-P2, 1746-P3, 1746-P4, 1746-P5, 1746-P6, or 1746-P7) – installation instructions (publication 1746-IN004) If the contents are incomplete, call your local Rockwell Automation representative for assistance.

Publication 1747-UM011G-EN-P - June 2008

Reference

Page 17

Quick Start for Experienced Users

2.

Install the chassis.

17

Reference

1. Determine the amount of spacing required for mounting your system.

Chapter 3 (System Installation Recommendations)

C

C

1746-C9 Cable SLC 500 Controller

A

A

SLC 500 Controller

1746-C7 Cable

B

B

C

SLC 500 Controller

D

1746-C9 Cable

B

B

SLC 500 Controller

A

SLC 500 Controller 1746-C9 Cable

B

Recommended Spacing A. 15.3...20.0 cm (6...8 in.) when using the 1746-C9 cable. If you mount two 13-slot chassis above each other, the distance cannot exceed 10.2...12.7 cm (4...5 in.). B. Greater than 10.2 cm (4 in.). C. Greater than 15.3 cm (6 in.).

SLC 500 Controller

C

D. 6.35...10.2 cm (2.5...4 in.) when using the 1746-C7 cable. If you are using a 1746-P4 power supply, your maximum spacing is 6.35 cm (2.5 in.).

Publication 1747-UM011G-EN-P - June 2008

Page 18

18

Quick Start for Experienced Users

2. Drill holes in the backpanel of your enclosure and install the top mounting hardware. Chapter 6 (Installing Your Use M4 or M5 (#10 or #12) phillips screw and star washer (or SEM screw).

Hardware Components)

3. Scrape off the paint from the backpanel between the chassis and backpanel. 4. Slide the chassis over the installed hardware and tighten the screws.

5. Install the remaining tab hardware.

3.

Install the power supply.

Reference

1. Align the circuit board of the power supply with the card guides on the left side of the Chapter 6 (Installing Your chassis, and slide the power supply in until it is flush with the chassis.

Hardware Components)

2. Fasten the power supply to the chassis.

Use these screws to fasten the power supply to the chassis. 1.2 Nm (11 lb-in) Maximum Torque

Publication 1747-UM011G-EN-P - June 2008

Page 19

Quick Start for Experienced Users

4.

Make jumper selection for 120/240V ac on 1746-P1, 1746-P2, and 1746-P4 power supplies.

Place the input voltage jumper to match the input voltage. This does not apply to the 1746-P3, 1746-P5, 1746-P6, or 1746-P7 power supplies which do not have jumpers.

19

Reference Chapter 6 (Installing Your Hardware Components)

Set the input jumper before applying power. Hazardous voltage is present on exposed pins when power is applied; contact with the pin may cause injury to personnel.

ATTENTION

1746-P1 and 1746-P2 Power Supplies POWER

Fuse

1746-P4 Power Supply

Jumper Selection

POWER

85-132V ac

Jumper Selection 100/120 Volts

170-250V ac

200/240 Volts

Publication 1747-UM011G-EN-P - June 2008

Page 20

20

5.

Quick Start for Experienced Users

Wire power to the power supply.

ATTENTION

Reference

Turn off incoming power before connecting wires. Failure to do so could cause injury to personnel and/or equipment.

Chapter 6 (Installing Your Hardware Components)

Connect incoming power. 1746-P1 and 1746-P2 PWR OUT +24V dc

User Power

PWR OUT COM

1746-P3 NOT USED

User Power

NOT USED +24V dc

120/240V ac Incoming Power

V ac NEUT CHASSIS GROUND

Incoming Power

CHASSIS GROUND 1746-P5

1746-P4 User Power dc NEUT

PWR OUT +24V dc PWR OUT COM

PWR OUT +24V dc

User Power

PWR OUT COM +125V dc

85 to 132V ac JUMPER

Incoming Power dc NEUT CHASSIS GROUND

170 to 250V ac 1746-P6 L1: 85 to 132/170 to 250V ac Incoming Power

L2: NEUTRAL CHASSIS GROUND

User Power Incoming Power

PWR OUT +24V dc PWR OUT COM +48V dc dc NEUT CHASSIS GROUND

1746-P7 NOT USED NOT USED +12/24V dc Incoming Power dc NEUT CHASSIS GROUND

Publication 1747-UM011G-EN-P - June 2008

IMPORTANT

Terminal screws on the 1746-P1, 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies should be tightened with a maximum torque of 1 Nm (8.8 lb-in). Terminal screws on the 1746-P4 power supply should be tightened with a max torque of 0.8 Nm (7 lb-in).