Page 171

Replacement Parts

171

Replacement Terminal Blocks Description

Cat. No.

Replacement Terminal Block (Blue) - Used with dc I/O modules, catalog numbers 1746-IB16, 1746-IC16, 1746-IH16, 1746-IV16, 1746-OBP8, 1746-OB16, 1746-OB16E, 1746-OBP16, 1746-OVP16 1746-OV16, 1746-IN16, 1746-IG16, 1746-1746OG16

1746-RT25B

Replacement Terminal Block (Orange) - Used with relay output modules, catalog numbers 1746-OW16, 1746-OX8

1746-RT25C

Replacement Terminal Block (Green) - Used with Specialty I/O modules, catalog numbers 1746-HSCE, 1746-IO12, 1746-NR4, 1746-NI8

1746-RT25G

Replacement Terminal Block (Red) - Used with ac I/O modules, catalog numbers 1746-IA16, 1746-OA16, 1746-IM16, 1746-OAP12

1746-RT25R

Replacement Terminal Block - 2-position terminal block used with analog outputs, catalog numbers 1746-NO4I, 1746-NO4V

1746-RT26

Replacement Terminal Block - 8-position terminal block used with analog outputs, catalog numbers 1746-NO4I, 1746-NO4V

1746-RT27

Replacement Terminal Block - Used with analog input modules, catalog numbers 1746-NI4, 1746-NIO4I, 1746-NIO4V, 1746-FIO4I, 1746-FIO4V

1746-RT28

Replacement Terminal Block - Used with RIO Communication modules, catalog numbers 1747-SN, 1746-DSN, 1746-DCM

1746-RT29

Replacement Terminal Block - 6-position DH-485 plug/connector; used with DH-485 Link Coupler, catalog number 1747-AIC and Advanced Interface Converter, catalog number 1761-NET-AIC

1746-RT30

Replacement Terminal Block - used with SLC 500 Remote I/O Adapter module, catalog number 1747-ASB

1746-RT31

Replacement Terminal Block - used with Thermocouple/mV module, catalog number 1746-NT4

1746-RT32

Replacement Terminal Block - 3-position DH+ connector; used with SLC 5/04 processors, catalog numbers 1747-L541, 1747-L542, -L542P, 1747-L543

1746-RT33

Replacement Terminal Block (Green) - used with Thermocouple/mV Input module, catalog number 1746-NT8

1746-RT34

Replacement Terminal Block (Green) - used with RTD/resistance Input module, catalog number 1746-NR8

1746-RT35

Other Replacement Hardware Description

Cat. No.

Replacement Fuses, Five fuses per package. Orders must be for multiples of five.

-

Catalog number for 1746-P1 power supply.

1746-F1

Catalog number for 1746-P2 power supply.

1746-F2

Catalog number for 1746-P3 power supply.

1746-F3

Fixed I/O ac units, MDL 1.25 Ampere.

1746-F4

Fixed I/O dc units, MDL 1.6 Ampere.

1746-F5

Catalog numbers for 1746-OBP16 and 1746-OVP16 output modules.

1746-F8

Catalog numbers for 1746-OAP12 output module.

1746-F9

Publication 1747-UM011G-EN-P - June 2008

Page 172

172

Replacement Parts

Description

Cat. No.

Modular Card Slot Fillers - Two fillers per package. Orders must be for multiples of two.

1746-N2

Connector - Mating connector for 32-point user-made cable.

1746-N3

Kit consisting of 4 replacement terminal covers and labels for 4, 8, 16 I/O modules.

1746-R9

Replacement Covers and Labels - Two covers per package. Orders must be for multiples of two covers.

-

Catalog number for 1746-P1.

1746-R10

Catalog numbers for 1746-P2 and 1746-P3 power supplies.

1746-R11

SLC 5/01 and SLC 5/02 processors.

1746-R12

Specialty I/O.

1746-R13

SLC 5/03, SLC 5/04, and SLC 5/05 processor.

1746-R14

Catalog number for 1747-ASB module.

1746-R16

Replacement Fuse Holder for catalog number 1746-OAP12. Two fuse holders per package. Orders must be for multiples 1746-R17 of two. (Price is per holder.) Replacement Retainer Clips - Four clips per package. Orders must be for multiples of four.

1746-R15

Replacement Remote I/O Address Labels: Includes five labels for remote PLC system and five labels for remote SLC system.

1746-RL35

Replacement Octal Label Kit - Kit includes one octal status indicator label and one door label module.

- for 1746-IA16 module

1746-RL40 for 1746-IB16 module

1746-RL41 for 1746-IG16 module

1746-RL42 for 1746-IM16 module

1746-RL43 for 1746-IN16 module

1746-RL44 for 1746-IV16 module

1746-RL45 for 1746-ITB16 module

1746-RL46 for 1746-ITV16 module

1746-RL47 for 1746-OA16 module

1746-RL50 for 1746-OB16 module

1746-RL51 for 1746-OG16 module

1746-RL52 for 1746-OV16 module

1746-RL53 for 1746-OW16 module

1746-RL54 for 1746-OBP16 module

1746-RL55 for 1746-OVP16 module

1746-RL56 for 1746-OAP12 module

1746-RL57 for 1746-IC16 module

1746-RL58 for 1746-IH16 module

1746-RL59 for 1746-IB32 module

1746-RL60 for 1746-IV32 module

1746-RL61 for 1746-OB32 and 1746-OB32E module

1746-RL70

Publication 1747-UM011G-EN-P - June 2008

Page 173

Replacement Parts

Description

173

Cat. No.

for 1746-OV32 module

1746-RL71 for 1746-OB16E module

1746-RL72

Lithium Battery Assembly. This is an optional part used for the SLC 500 fixed and modular hardware style processors and the Hand-held Terminal. Refer to product documentation for proper storage and handling instructions. For disposal information, consult your nearest Rockwell Automation Sales Office.

1747-BA

Replacement Keys for the SLC 5/03, SLC 5/04, and SLC 5/05 processors.

1747-KY1

Publication 1747-UM011G-EN-P - June 2008

Page 174

174

Replacement Parts

Notes:

Publication 1747-UM011G-EN-P - June 2008

Page 175

Appendix

A

Specifications

This appendix provides the specifications for the SLC 500 processors as well as the SLC power supplies.

The table below lists SLC 500 system test specifications.

SLC 500 System General Specifications Attribute

Value

Industry Standard

Temperature, operating

0 °C...60 °C (32 °F...140 °F)

Not applicable

Temperature, storage

-40 °C...85°C (-40 °F...185 °F)

Not applicable

Humidity

5 to 95% without condensation

Not applicable

Vibration, operating

2.5 g at 5...2000 Hz

Not applicable

Vibration, non-operating

5 g at 5...2000 Hz

Not applicable

Shock, operating all modules except relay contact 30.0 g (3 pulses, 11 ms)

Not applicable

Shock, operating relay contact modules - OW, OX, IO combo 10.0 g (3 pulses, 11 ms)

Not applicable

Shock, non-operating

50.0 g (3 pulses, 11 ms)

Not applicable

Free fall (drop test)

Portable, 2.268 kg (5 lb) or less at 0.762 m (30 in.) (six drops)

Not applicable

Portable, 2.268 kg (5 lb) or more at 0.1016 m (4 in.) (three flat drops)

Not applicable

Dielectric withstand: 1500V ac

UL 508, CSA C22.2 No. 142

Isolation between communication circuits: 500V dc

Not applicable

Isolation between backplane and I/Os: 1500V ac

Not applicable

Flammability and electrical ignition: UL94V-0

Not applicable

UL listed to US and Canadian Safety Standards Class I, Groups A, B, C or D, Division 2 CE compliant for all applicable directives C-Tick marked for all applicable acts

Not applicable

Safety

Certification

175

Publication 1747-UM011G-EN-P - June 2008

Page 176

176

Specifications

Processor General Specifications

The table below lists general specifications for SLC 500 modular processors.

Attribute (1747-)

SLC 5/02 SLC 5/03

SLC 5/01

SLC 5/04

SLC 5/05

L511

L514

L524

L531

L532

L533

L541

L542

L543

L551

L552

L553

Program memory (words)

1K

4K

4K

8K

16 K

32 K

16 K

32 K

64 K

16 K

32 K

64 K

I/O capacity

3940 discrete

4096 discrete

Remote I/O capacity

Not applicable

Processor memory and chassis power limit up to 4096 inputs and 4096 outputs

Chassis/slots, max

3 Chassis/30 Slots of I/O

Standard RAM

Capacitor 2 weeks(2) optional lithium battery 5 years Lithium battery 2 years Capacitor - 30 minutes minimum

Memory back-up options

EEPROM

Status indicators

Run CPU Fault Forced I/O Battery Low

Flash EPROM Run CPU Fault Forced I/O Battery Low RS-232 DH-485

Run CPU Fault Forced I/O Battery Low RS-232 DH+

Run CPU Fault Forced I/O Battery Low RS-232 Ethernet

Power supply loading 90 mA at 5V dc

500 mA at 5V dc

1A at 5V dc

1A at 5V dc

0 mA at 24V dc

175 mA at 24V dc

0 mA at 24V dc(4)

0 mA at 24V dc

Not applicable

±54 sec./month at 25 °C (77 °F); ±81 sec./month at 60 °C (140 °F)

Clock/calendar accuracy(1)

Run CPU Fault Forced I/O Battery Low COMM

Program scan hold-up 20 ms...3 s (dependent on power supply loading) time after loss of power Noise immunity

NEMA Standard ICS 2-230

Temperature rating operating: 0 °C...60 °C (32 °F...140°F); storage: -40 °C...85 °C (-40 °F...185 °F)

Humidity

5 to 95% without condensation

Shock, operating

30 g

Vibration

Displacement:.015 in., peak-to-peak at 5...57 Hz Acceleration: 2.5 g at 57...2000 Hz

Publication 1747-UM011G-EN-P - June 2008

Page 177

Specifications

Attribute (1747-)

SLC 5/01 L511

Certification (when product is marked)

SLC 5/02 SLC 5/03 L514

L524

L531

SLC 5/04 L532

L533

L541

177

SLC 5/05

L542

L543

L551

L552

L553

UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations C-UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations CE(3) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2 Industrial Immunity EN 50081-2 Industrial Emissions or EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with safety related portions of: EN61131-2 Programmable Controllers C-Tick, Australian Radio Communications Act, compliant with: AS/NZS 2064 Industrial Emissions

(1)

RTC should not be relied upon for time-based periodic control. Use STI subroutine for periodic control.

(2)

See Capacitor Memory Backup vs. Temperature Curve.

(3)

See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

(4)

SLC 5/04 processors manufactured prior to April 2002 draw 200 mA at 24V dc. Check your label to verify your processor’s current draw.

Power Supply Specifications

This section provides specifications for the SLC 500 power supplies.

1746-P1, 1746-P2, 1746-P3, and 1746-P4 Power Supplies Attribute

Value 1746-P1

1746-P2

1746-P3

1746-P4

Line voltage

85...132/170...265V ac, 47...63 Hz

19.2....28.8V dc

85...132/170...265V ac 47...63 Hz

Typical line power requirement

135VA

90VA

240VA

Inrush current, max

20 A

Internal current capacity

2 A at 5V dc 0.46 A at 24V dc

5 A at 5V dc 0.96 A at 24V dc

3.6 A at 5V dc 0.87 A at 24V dc

10.0 A at 5V dc 2.88 A at 24V dc(10)

Fuse protection(1)

1746-F1 or equivalent(5) (6)

1746-F2 or equivalent(5) (8)

1746-F3 or equivalent(5) (9)

Fuse is soldered in place

24V dc user-power current capacity

200 mA not applicable

1 A(1)

24V dc user-power voltage range

18...30V dc

User-supplied overcurrent protection, max(2)

15 A

Ambient temperature, operating

0 °C...60 °C (32 °F...140 °F) Current capacity is derated 5% above 55 °C (131°F)

0 °C...60 °C (32 °F...140 °F) no derating

Isolation(3)

1800V ac RMS for 1 s

2600V dc for 1 s

180VA

45 A

20.4...27.6V dc not applicable

600v ac rms for 1s

15 A

Publication 1747-UM011G-EN-P - June 2008

Page 178

178

Specifications

Attribute

Value 1746-P1

1746-P2

1746-P3

1746-P4

CPU hold-up time(4)

20 ms (full load) 3000 ms (no load)

5 ms (full load) 20 ms (full load) 1000 ms (no load) 3000 ms (no load)

Certification (when product is marked)

UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations

UL Listed Industrial Control Equipment

C-UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations

CSA Certified Process Control Equipment for Class I, Div 2, Groups A, B, C, D Hazardous Locations

CE(7) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2 Industrial Immunity EN 50081-2 Industrial Emissions or EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with safety related portions of: EN61131-2 Programmable Controllers C-Tick, Australian Radio Communications Act, compliant with: AS/NZS 2064 Industrial Emissions (1)

Power supply fuse is to guard against fire hazard due to short-circuit conditions. Fuse may not protect the supply from miswiring or excessive transient in the power line.

(2)

Use time-delay type overcurrent protection in all ungrounded conductors.

(3)

Isolation is between input terminals and backplane.

(4)

CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(5)

Fuse sizes specified are for end-devices only. Fuse size may need to be reduced depending on the size of circuit wiring.

(6)

Equivalent fuses: 250V-3A fuse, nagasawa ULCS-61ML-3, or BUSSMAN AGC 3.

(7)

See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

(8)

Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3.

(9)

Equivalent fuse: 125V-5A fuse, LITTLEFUSE 223.

(10)

The combination of all output power (5 volt backplane, 24 volt backplane, and 24 volt user source) cannot exceed 70 watts.

Publication 1747-UM011G-EN-P - June 2008

Page 179

Specifications

179

1746-P5, 1746-P6, and 1746-P7 Power Supplies Attribute

Value 1746-P5

1746-P6

1746-P7

Line voltage

90-146V dc

30-60V dc

10-30V dc(5)

Typical line power requirement

85VA

100VA

12V dc input: 50VA

Inrush current, max

20A

20 A (required for turn-on)

Internal current capacity

5 A at 5V dc 0.96 A at 24V dc

24V dc input: 12V dc input: 2.0 A at 5V dc 0.46 A at 24V 3.6 A at 5V dc 0.87 A at 24V dc dc

24V dc input: 75VA

See P7 current capacity chart Fuse protection(1)

Fuse is soldered in place

24V dc user-power current capacity

200 mA

24V dc user-power voltage range

18-30V dc

Ambient temperature, operating

0 °C...60 °C (32 °F...140 °F) Current capacity is derated 5% above 55 °C (131°F)

Isolation(2)

1800V ac RMS for 1 s

CPU hold-up time(3)

20 ms (full load) 5 ms (full load) 12V dc input: 3000 ms (no load) 1500 ms (no load) 1.37 ms at 0V dc (full load) 895 ms at 0V dc (no load) 10 ms at 9V dc (full load) continuous at 9V dc (no load)

Certification (when product is marked)

UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations not applicable

600V ac RMS for 1 s 24V dc input: 40 ms at 0V dc (full load) 1860 ms at 0V dc (no load) 790 ms at 11V dc (full load) continuous at 11V dc (no load)

C-UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations CE(4) European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2 Industrial Immunity EN 50081-2 Industrial Emissions or EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions European Union 73/23/EEC LVD Directive, compliant with safety related portions of: EN61131-2 Programmable Controllers C-Tick Australian Radio Communications Act, compliant with: AS/NZS 2064 Industrial Emissions (1)

Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the power line.

(2)

Isolation is between input terminals and backplane.

(3)

CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(4)

See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

(5)

See page 70 for information on power supply under voltage operation.

Publication 1747-UM011G-EN-P - June 2008

Page 180

180

Specifications

Publication 1747-UM011G-EN-P - June 2008