Page 161
Troubleshooting
161
Returning the SLC 5/03, SLC 5/04, and SLC 5/05 Processors to Initial Factory Conditions We only recommend this procedure if the communication channels have been shut down due to the configuration parameters, or if you absolutely cannot establish communication with the processor.
WARNING
If you return the processor to the initial factory conditions, the user program is lost and communication configurations are returned to their default settings.
Follow this procedure to return the processor to initial factory conditions. 1. Remove power from the SLC 500 power supply. 2. Remove the processor from the chassis. 3. Disconnect the battery by removing the battery connector from its socket. 4. Locate the VBB and GND connections on the right side of the motherboard. 5. Place a small bladed screwdriver across the VBB and GND connections and hold for 60 seconds. This returns the processor to the initial factory conditions.
Publication 1747-UM011G-EN-P - June 2008
Page 162
162
Troubleshooting
VBB
GND
SLC 5/03 (1747-L531, 1747-L532 and 1747-L533) Processors
GND VBB
Keyswitch
Mother Board
Right Side View
SLC 5/04 (1747-L541, 1747-L542, and 1747-L543) SLC 5/05 (1747-L551, 1747-L552, and 1747-L553) Processors
GND Keyswitch
GND VBB
Mother Board
Right Side View
Publication 1747-UM011G-EN-P - June 2008
VBB
Page 163
Troubleshooting
Troubleshooting Your Input Modules
163
The following will assist you in troubleshooting your input modules.
Input Circuit Operation An input circuit responds to an input signal in the following manner. 1. An input filter removes false signals due to contact bounce or electrical interference. 2. Opto-electrical isolation protects the input circuit and backplane circuits by isolating logic circuits from input signals. 3. Logic circuits process the signal. 4. An input status indicator turns on or off indicating the status of the corresponding input device.
Input
Input Conditioning
Opto-Electrical Isolation
Logic Circuits
Backplane status indicator
Publication 1747-UM011G-EN-P - June 2008
Page 164
164
Troubleshooting
Troubleshooting Your Input Modules If your input circuit status indicator is
And your input device is
And
Probable Cause
Recommended Action
On
On/closed/activated
Your input device will not turn off.
Device is shorted or damaged.
Verify device operation. Replace device.
Your program operates as though it is off.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Input is forced off in program.
Check the FORCED I/O or FORCE status indicator on processor and remove forces.
Input device Off-state leakage current exceeds input circuit specification.
Check device and input circuit specifications. Use load resistor to bleed-off current.
Input device is shorted or damaged.
Verify device operation. Replace device.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Input circuit is incompatible.
Check specification and sink/source compatibility (if dc input).
Off/open/deactivated
Off
On/closed/activated
Off/open/deactivated
Publication 1747-UM011G-EN-P - June 2008
Your program operates as though it is on and/or the input circuit will not turn off.
Your program operates as though it is off and/or the input circuit will not turn on.
Low voltage across the Check the voltage across input circuit input. and check source voltage. Incorrect wiring or an open circuit.
Check wiring and COMmon connections.
Input signal turn-on time too fast for input circuit.
Check timing specifications.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Your input device will not turn on.
Input device is shorted or damaged.
Verify operation. Replace device.
Your program operates as though it is on.
Input is forced on in program.
Check processor FORCED I/O or FORCE status indicator and remove forces. Verify proper wiring. Try other input circuit. Replace module.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Page 165
Troubleshooting
Troubleshooting Your Output Modules
165
The following will assist you in troubleshooting your output modules.
Output Circuit Operation An output circuit controls the output signal in the following manner. 1. Logic circuits determine the output status. 2. An output status indicator indicates the status of the output signal. 3. Opto-electrical isolation separates output circuit logic and backplane circuits from field signals. 4. The output driver turns the corresponding output on or off.
Backplane
Logic Circuits
Opto-Electrical Isolation
Logic Circuits
Output Drivers
Output status indicator
Publication 1747-UM011G-EN-P - June 2008
Page 166
166
Troubleshooting
Troubleshooting Your Output Modules If your Output Circuit status indicator is
And your output And device is
On
On/energized
Off/de-energized
Probable Cause
Programming problem. Your program indicates that the output circuit is off or the output circuit will not turn off.
Your output device will not turn on and the program indicates that it is on.
Publication 1747-UM011G-EN-P - June 2008
Recommended Action
Check for duplicate outputs and addresses using the search function. If using subroutines, outputs are left in their last state when not executing subroutines. Use the force function to force output off. If this does not force the output off, output circuit is damaged. If the output does force off, then check again for logic/programming problem.
Output is forced on in program.
Check processor FORCED I/O or FORCE status indicator and remove forces.
Output circuit is damaged.
Use the force function to force the output off. If this forces the output off, then there is a logic/programming problem. If this does not force the output off, the output circuit is damaged. Try other output circuit. Replace module.
Low or no voltage across the load.
Measure the source voltage and check specifications.
Incorrect wiring or open circuit.
Check wiring and COMmon connections.
Output device is incompatible.
Check specifications and sink/source compatibility (if dc output).
Output circuit is damaged.
Check wiring. Try other output circuit. Replace module.
Page 167
Troubleshooting
If your Output Circuit status indicator is
And your output And device is
Probable Cause
Recommended Action
Off
On/energized
Output device is incompatible.
Check specifications.
Output circuit off-state leakage current may exceed output device specification.
Check specifications. Use load resistor to bleed off leakage current. See output specifications.
Incorrect wiring.
Check wiring. Disconnect from SLC processor and verify device operation.
Output device is shorted or damaged.
Verify device operation. Replace device.
Output circuit is damaged.
Check wiring. Try other output circuit. Replace module.
Off/de-energized
Your output device will not turn off and the program indicates that it is off.
Programming problem. Your program indicates that the output circuit is on or the output circuit will not turn on.
167
Check for duplicate outputs and addresses using search function. If using subroutines, outputs are left in their last state when not executing subroutines. Use the force function to force output on. If this does not force the output on, output circuit is damaged. If the output does force on, then check again for logic/programming problem.
Output is forced off in program.
Check processor FORCED I/O or FORCE status indicator and remove forces.
Output circuit is damaged.
Use the force function to force the output on. If this forces the output on, then there is a logic/programming problem. If this does not force the output on, the output circuit is damaged. Try other output circuit. Replace module.
Publication 1747-UM011G-EN-P - June 2008
Page 168
168
Troubleshooting
Notes:
Publication 1747-UM011G-EN-P - June 2008
Page 169
Chapter
11
Replacement Parts
This chapter provides a list of replacement parts and a list of replacement terminal blocks for your SLC 500 controller.
Replacement Cables and Connectors Description
Cat. No.
Chassis Interconnect Cable - The 1746-C7 cable is a 152.4 mm (6 in.) ribbon cable used when linking modular hardware 1746-C7 style chassis up to 152.4 mm (6 in.) apart in an enclosure. Chassis Interconnect Cable - The 1746-C9 cable is a 914.4 mm (36 in.) cable used when linking modular hardware style chassis from 152.4 mm (6 in.) up to 914.4 mm (36 in.) apart in an enclosure.
1746-C9
Chassis Interconnect Cable - The 1746-C16 cable is a 1.27m (50 in.) cable used when linking modular hardware style chassis from 0.914m (36 in.) up to 1.27m (50 in.) apart in an enclosure. This is the longest chassis interconnect cable recommended by Allen-Bradley.
1746-C16
32 Point Mating Connector - This connector is used for terminating a user-made cable. It is compatible with the DIN RAIL mountable terminal block interface module, catalog number 1492-IFM40x (used with 32-point I/O modules).
1746-N3
Replacement Processor to Peripheral Programming/Communication Cable - This 1.8 m (6 ft) cable is used to connect the interface converter to the SLC 500 controller when using personal computer interface software. This cable is also used to connect the Hand-held Terminal to the SLC 500 controller and to connect the Data Table Access Module to the SLC 500 controller.
1747-C10
Replacement Processor to Isolated Link Coupler Cable - This 304.8 mm (12 in.) cable is used to connect the SLC 500 controller to the isolated link coupler.
1747-C11
Communication Module to Isolated Link Coupler Cable - This 914.4 mm (36 in.) cable is used to connect communication 1747-C13 modules (for example, 1746-BAS, 1747-KE, and 1747-UIC interface) to the isolated link coupler. The isolated link coupler must be powered by an external power supply or connected to a device with a 1747-C10 or 1747-C11 cable. Replacement Processor to Peripheral Programming/Communication Cable - This 6.09 m (20 ft) cable is used to connect the interface converter to the SLC 500 controller when using personal computer interface software. This cable is used to connect the Data Table Access Module to the SLC 500 controller.
1747-C20
SLC 5/03, SLC 5/04, and SLC 5/05 RS-232 Programmer Cable - This 3.96 m (12 ft) cable has two 9-pin DTE connectors and is used to connect the SLC processor RS-232 channel (channel 0) to a personal computer serial port.
1747-CP3
SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 45 cm (17.7 in.) cable has two 9-pin DTE connectors and 1761-CBL-AC00 is used to connect the SLC processor RS-232 channel (channel 0) to port 1 of the 1761-NET-AIC advanced interface converter. SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 2 m (6.5 in.) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC advanced interface converter.
1761-CBL-PM02
SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 45 cm (17.7 in.) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC advanced interface converter.
1761-CBL-AP00
169
Publication 1747-UM011G-EN-P - June 2008
Page 170
170
Replacement Parts
Description
Cat. No.
RJ45 to 6-Pin Phoenix Connector Communication Cable - This 3 m (9.8 ft) cable is used to connect the SLC 500 fixed, SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the 1761-NET-AIC advanced interface converter.
1761-CBL-AS03
RJ45 to 6-Pin Phoenix Connector Communication Cable - This 9.5 m (31.2 ft) cable is used to connect the SLC 500 fixed, 1761-CBL-AS09 SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the 1761-NET-AIC advanced interface converter. Catalog 1492 pre-wired interface cables
1492
Cable Connectivity Summary For Connectivity Between These Devices
Preferred Cable Cat. No.
These Cables May Be Used
1746-A4, 1746-A7, 1746-A10, or 1746-A13 chassis
1746-A4, 1746-A7, 1746-A10, or 1746-A13 chassis
1746-C7 1746-C9 1746-C16
-
1747-PIC Personal Interface Converter 1747-DTAM-E Data Table Access module 2707-Lxxx, 2707-Vxxx DTAM Plus
1747-AIC Isolated Link Coupler SLC 500 processors (DH-485 channel)
1747-C10
1747-C11 1747-C20
1747-AIC Isolated Link Coupler
SLC 500 processors (DH-485 channel)
1747-C11
1747-C10 1747-C13 1747-C20
1747-KE DH-485/RS-232C interface module 1746-BAS BASIC module
1747-AIC Isolated Link Coupler
1747-C13
1747-C11 1747-C10
1746-xx32 32 point I/O modules
1492-IFM40x
1492-CABLExH
-
SLC 5/03 processor (RS-232 channel 0) SLC 5/04 processor (RS-232 channel 0) SLC 5/05 processor (RS-232 channel 0)
Personal computer serial port (9-Pin DTE) 1747-UIC RS-232 port
1747-CP3
-
1746-I/O
1492-IFMxx interface modules
1492-CABLExx
-
Belden 9463
-
Remote I/O network 1747-SN Remote I/O Scanner 1747-DCM Direct Communication Module 1747-ASB SLC Remote I/O Adapter module SLC 5/04 processors (1747-L541, 1747-542, and 1747-543) 1747-AIC Isolated Link Coupler 1770-KF3 DH-485 communication interface
1747-AIC Isolated Link Coupler
Belden 9842 or 3106A
-
1747-UIC RJ-485 port
SLC 500 processors (DH-485 channel)
1747-C13
-