For the Allen-Bradley 1747-L524

Page 161

Troubleshooting

161

Returning the SLC 5/03, SLC 5/04, and SLC 5/05 Processors to Initial Factory Conditions We only recommend this procedure if the communication channels have been shut down due to the configuration parameters, or if you absolutely cannot establish communication with the processor.

WARNING

If you return the processor to the initial factory conditions, the user program is lost and communication configurations are returned to their default settings.

Follow this procedure to return the processor to initial factory conditions. 1. Remove power from the SLC 500 power supply. 2. Remove the processor from the chassis. 3. Disconnect the battery by removing the battery connector from its socket. 4. Locate the VBB and GND connections on the right side of the motherboard. 5. Place a small bladed screwdriver across the VBB and GND connections and hold for 60 seconds. This returns the processor to the initial factory conditions.

Publication 1747-UM011G-EN-P - June 2008

Page 162

162

Troubleshooting

VBB

GND

SLC 5/03 (1747-L531, 1747-L532 and 1747-L533) Processors

GND VBB

Keyswitch

Mother Board

Right Side View

SLC 5/04 (1747-L541, 1747-L542, and 1747-L543) SLC 5/05 (1747-L551, 1747-L552, and 1747-L553) Processors

GND Keyswitch

GND VBB

Mother Board

Right Side View

Publication 1747-UM011G-EN-P - June 2008

VBB

Page 163

Troubleshooting

Troubleshooting Your Input Modules

163

The following will assist you in troubleshooting your input modules.

Input Circuit Operation An input circuit responds to an input signal in the following manner. 1. An input filter removes false signals due to contact bounce or electrical interference. 2. Opto-electrical isolation protects the input circuit and backplane circuits by isolating logic circuits from input signals. 3. Logic circuits process the signal. 4. An input status indicator turns on or off indicating the status of the corresponding input device.

Input

Input Conditioning

Opto-Electrical Isolation

Logic Circuits

Backplane status indicator

Publication 1747-UM011G-EN-P - June 2008

Page 164

164

Troubleshooting

Troubleshooting Your Input Modules If your input circuit status indicator is

And your input device is

And

Probable Cause

Recommended Action

On

On/closed/activated

Your input device will not turn off.

Device is shorted or damaged.

Verify device operation. Replace device.

Your program operates as though it is off.

Input circuit is damaged.

Verify proper wiring. Try other input circuit. Replace module.

Input is forced off in program.

Check the FORCED I/O or FORCE status indicator on processor and remove forces.

Input device Off-state leakage current exceeds input circuit specification.

Check device and input circuit specifications. Use load resistor to bleed-off current.

Input device is shorted or damaged.

Verify device operation. Replace device.

Input circuit is damaged.

Verify proper wiring. Try other input circuit. Replace module.

Input circuit is incompatible.

Check specification and sink/source compatibility (if dc input).

Off/open/deactivated

Off

On/closed/activated

Off/open/deactivated

Publication 1747-UM011G-EN-P - June 2008

Your program operates as though it is on and/or the input circuit will not turn off.

Your program operates as though it is off and/or the input circuit will not turn on.

Low voltage across the Check the voltage across input circuit input. and check source voltage. Incorrect wiring or an open circuit.

Check wiring and COMmon connections.

Input signal turn-on time too fast for input circuit.

Check timing specifications.

Input circuit is damaged.

Verify proper wiring. Try other input circuit. Replace module.

Your input device will not turn on.

Input device is shorted or damaged.

Verify operation. Replace device.

Your program operates as though it is on.

Input is forced on in program.

Check processor FORCED I/O or FORCE status indicator and remove forces. Verify proper wiring. Try other input circuit. Replace module.

Input circuit is damaged.

Verify proper wiring. Try other input circuit. Replace module.

Page 165

Troubleshooting

Troubleshooting Your Output Modules

165

The following will assist you in troubleshooting your output modules.

Output Circuit Operation An output circuit controls the output signal in the following manner. 1. Logic circuits determine the output status. 2. An output status indicator indicates the status of the output signal. 3. Opto-electrical isolation separates output circuit logic and backplane circuits from field signals. 4. The output driver turns the corresponding output on or off.

Backplane

Logic Circuits

Opto-Electrical Isolation

Logic Circuits

Output Drivers

Output status indicator

Publication 1747-UM011G-EN-P - June 2008

Page 166

166

Troubleshooting

Troubleshooting Your Output Modules If your Output Circuit status indicator is

And your output And device is

On

On/energized

Off/de-energized

Probable Cause

Programming problem. Your program indicates that the output circuit is off or the output circuit will not turn off.

Your output device will not turn on and the program indicates that it is on.

Publication 1747-UM011G-EN-P - June 2008

Recommended Action

Check for duplicate outputs and addresses using the search function. If using subroutines, outputs are left in their last state when not executing subroutines. Use the force function to force output off. If this does not force the output off, output circuit is damaged. If the output does force off, then check again for logic/programming problem.

Output is forced on in program.

Check processor FORCED I/O or FORCE status indicator and remove forces.

Output circuit is damaged.

Use the force function to force the output off. If this forces the output off, then there is a logic/programming problem. If this does not force the output off, the output circuit is damaged. Try other output circuit. Replace module.

Low or no voltage across the load.

Measure the source voltage and check specifications.

Incorrect wiring or open circuit.

Check wiring and COMmon connections.

Output device is incompatible.

Check specifications and sink/source compatibility (if dc output).

Output circuit is damaged.

Check wiring. Try other output circuit. Replace module.

Page 167

Troubleshooting

If your Output Circuit status indicator is

And your output And device is

Probable Cause

Recommended Action

Off

On/energized

Output device is incompatible.

Check specifications.

Output circuit off-state leakage current may exceed output device specification.

Check specifications. Use load resistor to bleed off leakage current. See output specifications.

Incorrect wiring.

Check wiring. Disconnect from SLC processor and verify device operation.

Output device is shorted or damaged.

Verify device operation. Replace device.

Output circuit is damaged.

Check wiring. Try other output circuit. Replace module.

Off/de-energized

Your output device will not turn off and the program indicates that it is off.

Programming problem. Your program indicates that the output circuit is on or the output circuit will not turn on.

167

Check for duplicate outputs and addresses using search function. If using subroutines, outputs are left in their last state when not executing subroutines. Use the force function to force output on. If this does not force the output on, output circuit is damaged. If the output does force on, then check again for logic/programming problem.

Output is forced off in program.

Check processor FORCED I/O or FORCE status indicator and remove forces.

Output circuit is damaged.

Use the force function to force the output on. If this forces the output on, then there is a logic/programming problem. If this does not force the output on, the output circuit is damaged. Try other output circuit. Replace module.

Publication 1747-UM011G-EN-P - June 2008

Page 168

168

Troubleshooting

Notes:

Publication 1747-UM011G-EN-P - June 2008

Page 169

Chapter

11

Replacement Parts

This chapter provides a list of replacement parts and a list of replacement terminal blocks for your SLC 500 controller.

Replacement Cables and Connectors Description

Cat. No.

Chassis Interconnect Cable - The 1746-C7 cable is a 152.4 mm (6 in.) ribbon cable used when linking modular hardware 1746-C7 style chassis up to 152.4 mm (6 in.) apart in an enclosure. Chassis Interconnect Cable - The 1746-C9 cable is a 914.4 mm (36 in.) cable used when linking modular hardware style chassis from 152.4 mm (6 in.) up to 914.4 mm (36 in.) apart in an enclosure.

1746-C9

Chassis Interconnect Cable - The 1746-C16 cable is a 1.27m (50 in.) cable used when linking modular hardware style chassis from 0.914m (36 in.) up to 1.27m (50 in.) apart in an enclosure. This is the longest chassis interconnect cable recommended by Allen-Bradley.

1746-C16

32 Point Mating Connector - This connector is used for terminating a user-made cable. It is compatible with the DIN RAIL mountable terminal block interface module, catalog number 1492-IFM40x (used with 32-point I/O modules).

1746-N3

Replacement Processor to Peripheral Programming/Communication Cable - This 1.8 m (6 ft) cable is used to connect the interface converter to the SLC 500 controller when using personal computer interface software. This cable is also used to connect the Hand-held Terminal to the SLC 500 controller and to connect the Data Table Access Module to the SLC 500 controller.

1747-C10

Replacement Processor to Isolated Link Coupler Cable - This 304.8 mm (12 in.) cable is used to connect the SLC 500 controller to the isolated link coupler.

1747-C11

Communication Module to Isolated Link Coupler Cable - This 914.4 mm (36 in.) cable is used to connect communication 1747-C13 modules (for example, 1746-BAS, 1747-KE, and 1747-UIC interface) to the isolated link coupler. The isolated link coupler must be powered by an external power supply or connected to a device with a 1747-C10 or 1747-C11 cable. Replacement Processor to Peripheral Programming/Communication Cable - This 6.09 m (20 ft) cable is used to connect the interface converter to the SLC 500 controller when using personal computer interface software. This cable is used to connect the Data Table Access Module to the SLC 500 controller.

1747-C20

SLC 5/03, SLC 5/04, and SLC 5/05 RS-232 Programmer Cable - This 3.96 m (12 ft) cable has two 9-pin DTE connectors and is used to connect the SLC processor RS-232 channel (channel 0) to a personal computer serial port.

1747-CP3

SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 45 cm (17.7 in.) cable has two 9-pin DTE connectors and 1761-CBL-AC00 is used to connect the SLC processor RS-232 channel (channel 0) to port 1 of the 1761-NET-AIC advanced interface converter. SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 2 m (6.5 in.) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC advanced interface converter.

1761-CBL-PM02

SLC 5/03, SLC 5/04, and SLC 5/05 Communication Cable - This 45 cm (17.7 in.) cable has a 9-pin DTE and an 8-pin mini DIN connector and is used to connect the SLC processor RS-232 channel (channel 0) to port 2 of the 1761-NET-AIC advanced interface converter.

1761-CBL-AP00

169

Publication 1747-UM011G-EN-P - June 2008

Page 170

170

Replacement Parts

Description

Cat. No.

RJ45 to 6-Pin Phoenix Connector Communication Cable - This 3 m (9.8 ft) cable is used to connect the SLC 500 fixed, SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the 1761-NET-AIC advanced interface converter.

1761-CBL-AS03

RJ45 to 6-Pin Phoenix Connector Communication Cable - This 9.5 m (31.2 ft) cable is used to connect the SLC 500 fixed, 1761-CBL-AS09 SLC 5/01, SLC 5/02, and SLC 5/03 processor RJ45 port to port 3 of the 1761-NET-AIC advanced interface converter. Catalog 1492 pre-wired interface cables

1492

Cable Connectivity Summary For Connectivity Between These Devices

Preferred Cable Cat. No.

These Cables May Be Used

1746-A4, 1746-A7, 1746-A10, or 1746-A13 chassis

1746-A4, 1746-A7, 1746-A10, or 1746-A13 chassis

1746-C7 1746-C9 1746-C16

-

1747-PIC Personal Interface Converter 1747-DTAM-E Data Table Access module 2707-Lxxx, 2707-Vxxx DTAM Plus

1747-AIC Isolated Link Coupler SLC 500 processors (DH-485 channel)

1747-C10

1747-C11 1747-C20

1747-AIC Isolated Link Coupler

SLC 500 processors (DH-485 channel)

1747-C11

1747-C10 1747-C13 1747-C20

1747-KE DH-485/RS-232C interface module 1746-BAS BASIC module

1747-AIC Isolated Link Coupler

1747-C13

1747-C11 1747-C10

1746-xx32 32 point I/O modules

1492-IFM40x

1492-CABLExH

-

SLC 5/03 processor (RS-232 channel 0) SLC 5/04 processor (RS-232 channel 0) SLC 5/05 processor (RS-232 channel 0)

Personal computer serial port (9-Pin DTE) 1747-UIC RS-232 port

1747-CP3

-

1746-I/O

1492-IFMxx interface modules

1492-CABLExx

-

Belden 9463

-

Remote I/O network 1747-SN Remote I/O Scanner 1747-DCM Direct Communication Module 1747-ASB SLC Remote I/O Adapter module SLC 5/04 processors (1747-L541, 1747-542, and 1747-543) 1747-AIC Isolated Link Coupler 1770-KF3 DH-485 communication interface

1747-AIC Isolated Link Coupler

Belden 9842 or 3106A

-

1747-UIC RJ-485 port

SLC 500 processors (DH-485 channel)

1747-C13

-

Publication 1747-UM011G-EN-P - June 2008