Page 151

Troubleshooting

151

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors If the status indicators indicate

The following error exists

• FLT status indicator is on

Inadequate system Improper line power power voltage selection.

Verify proper 120/240V power supply jumper selection. See page 106.

Processor not in run mode

1. Verify selected processor mode.

• All other status indicators are off

Probable Cause

Recommended Action

• Status of any Communication status indicator does not matter • Power status indicator is on • All other status indicators are off

Either improper mode selected or user program logic error.

• Status of any Communication status indicator does not matter

2. If in program or test mode, try to enter run mode. a. If the keyswitch is in the REM position and there is no key, use the programmer. b. If the keyswitch is in the REM or PROG position and you have the key, toggle to the RUN position. 3. If in suspend mode, check user program logic for suspend instructions.

Line power out of operating range.

1. Check proper 120/240V power supply jumper selection and incoming power connections. 2. Monitor for proper line voltage at the incoming power connections.

Improper seating of power supply and/or processor in the chassis.

1. Remove power and inspect the power supply and processor chassis connections. 2. Re-install the devices and re-apply power. IMPORTANT The processor only operates in slot 0 of the first chassis.

Defective processor, power supply, or chassis.

1. Attempt to put processor in run mode in existing chassis. a. If the keyswitch is in the REM position and there is no key, use the programmer. b. If the keyswitch is in the REM or PROG position and you have the key, toggle to the RUN position. 2. Place the processor in another chassis. Apply power, reconfigure, and attempt to put processor in run mode. If unsuccessful, replace the processor. 3. Place the power supply in another chassis and test. If unsuccessful, replace the power supply. If successful, replace the original chassis.

Publication 1747-UM011G-EN-P - June 2008

Page 152

152

Troubleshooting

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors If the status indicators indicate

The following error exists

• Power status indicator is on

System inoperable, User program logic error. no major CPU faults detected

• Run status indicator is on • All other status indicators are Off

Probable Cause

Recommended Action 1. Monitor logic in Run mode and verify desired I/O status. 2. Check for minor CPU faults.

Defective I/O devices or I/O wiring.

Test inputs and outputs according to I/O troubleshooting procedures starting on page 163.

CPU memory error.

Cycle power.

Faulty memory module.

1. Remove power and then remove the memory module from the processor.

• Status of any Communication status indicator does not matter • Power status indicator is on

CPU fault

• CPU Fault status indicator is on

2. Re-install the processor and re-apply power to the power supply. If steady CPU Fault status indicator changes to flashing, replace the existing memory module with a replacement module.

• All other status indicators are off • Status of any Communication status indicator does not matter

Refer to 6 for removing and installing memory modules. Faulty processor or power supply.

1. Place the processor in another chassis not in the existing system and cycle power. If steady CPU Fault status indicator reappears, replace the processor. 2. If CPU Fault status indicator clears, monitor the line power going to the power supply in existing system. Replace existing system power supply if line power checks OK.

Processor firmware installed incorrectly.

Publication 1747-UM011G-EN-P - June 2008

If upgrading the processor to a different firmware level, verify that the firmware chip orientation matches the upgrade kit directions.

Page 153

Troubleshooting

153

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• Power status indicator is on

CPU major fault

Initial CPU factory power-up condition.

1. See page 121 and follow the start-up procedures.

Hardware/software major fault detected.

1. If the error occurred during the download of a new program to the processor, check the position of the J4 jumper. See page 159. If the jumper is not in the protected position:

• CPU Fault status indicator is flashing • All other status indicators are off • Status of any Communication status indicator does not matter

(erratic, repetitive power cycling can cause a processor major hardware fault)

2. Clear processor memory to get rid of the flashing CPU Fault status indicator.

a. Place the jumper in the protected position b. Re-download a valid user program to the processor 2. Use programmer to monitor and clear the fault (or if keyswitch in REM position): a. Monitor Status File word S:6 for major error code. b. Refer to your programming software documentation or the SLC 500 Instruction Set Reference Manual, publication 1747-RM001, for error codes and additional troubleshooting information. c. Remove hardware/software condition causing fault. d. Clear Status File S:1/13 major error bits, if set. e. Clear Status File S:5 major error bits, if set. f. Clear Status File S:6 major error code (optional). g. Attempt to put processor in run mode. If unsuccessful, repeat recommended action steps above. 3. Use the keyswitch to clear the fault. Toggle the keyswitch to PROG and back to RUN. (See page 149). If fault occurs again, use programmer to get error code and determine the source of the problem.

Publication 1747-UM011G-EN-P - June 2008

Page 154

154

Troubleshooting

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• Power status indicator is on

System does not operate per ladder logic

User forced I/O is disabling operation.

1. Monitor program file on-line and identify forced I/O.

System does not operate per programmed forces

User programmed forces are not enabled.

1. Monitor program file on-line and identify programmed forces.

CPU major error with low or no battery back-up

Loss of RAM during power-down.

1. Verify battery is connected. See page 137.

• Run status indicator is on

2. Disable appropriate forces and test system conditions again.

• Force status indicator is on • All other status indicators are off • Status of any Communication status indicator does not matter • Power status indicator is on • Run status indicator is on • Force status indicator is flashing

2. Enable appropriate forces and test system conditions again. Once forces are enabled, the Force status indicator turns on (steady).

• All other status indicators are off • Status of any Communication status indicator does not matter • Power status indicator is on • FLT status indicator is flashing • Batt status indicator is on • All Other status indicators are off • Status of any Communication status indicator does not matter

Publication 1747-UM011G-EN-P - June 2008

2. Replace the battery if you want RAM battery backup. See page 137. 3. Refer to processor major fault recommended action steps.

Page 155

Troubleshooting

155

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 Processor Communication Errors SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors If the status indicators indicate

The following error exists

• Power status indicator is Fatal error and no communication on

Probable Cause

Recommended Action

Inadequate system power.

1. Check line power.

Communication channel is shut down.

Check communication channel configuration with your programming software. Also, see page 161 to return the processor to initial factory conditions.

Communication channel is damaged.

Replace the processor.

Inadequate system power.

1. Check line power.

Communication channel is shut down.

Check communication channel configuration with your programming software. Also, see page 161 to return the processor to initial factory conditions.

communication channel is damaged.

Replace the processor.

Channel configured for DF1 or User mode.

See your programming software documentation for channel configuration information.

• DH-485, DH+, or ENET status indicator is off • FLT status indicator is off or flashing • Status of Run, Force, Batt, and RS232 status indicators do not matter

• Power status indicator is Fatal error and no communication on • RS232 status indicator is off • FLT status indicator is off or flashing • Status of Run; Force; DH-485, DH+, or ENET; or Batt status indicators do not matter

2. Check 120/240V power supply jumper selection. See page 106. Also, see the recommended actions for inadequate system power on page 150.

2. Check 120/240V power supply jumper selection. See page 106. Also, see the recommended actions for inadequate system power on page 150.

Publication 1747-UM011G-EN-P - June 2008

Page 156

156

Troubleshooting

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors If the status indicators indicate

The following error exists

• Power status indicator is The SLC 5/03 or SLC 5/04 on processor is trying • DH-485, DH+, or ENET to establish status indicator is communication, flashing but cannot find • FLT status indicator is off other active nodes. or flashing (The DH-485 or DH+ status • Status of Run, Force, Batt, and RS232 status indicator is indicators do not matter flashing green.)

Probable Cause

Recommended Action

DH-485 or DH+ communication parameters are improperly set up.

1. Check communication parameters of programmer. Programmer and processor communication rate must match. Programmer and processor node addresses must be different. 2. Try different combinations of: a. communication rate (default is 19.2 K for DH-485 and 57.6 K for DH+) b. node address (default is 1) 3. Try to increase the maximum node address. (default is 31 for DH-485)

Bad connection of communication device.

1. Check cable continuity. 2. Check cable connections between programmer and processor. 3. Check communication device (for example, the 1747-PIC interface). Replace if necessary.

Low or no power to communication device.

1. Verify proper power supply selection and backplane loading. (1747-PIC and 1747-AIC interface draw power off the backplane.) 2. Verify proper 120/240V power supply jumper selection. See page 106.

Duplicate drop is detected. (The DH+ status indicator is flashing red.)

Another DH+ device is already on the DH+ network at this node address.

1. Remove this device from the DH+ network.

An ENET fault is being reported via a code. (The ENET status indicator is flashing red.)

A hardware or software fault has occurred.

Contact Rockwell Automation for assistance.

Publication 1747-UM011G-EN-P - June 2008

2. Cycle power. 3. Reset the node address to an unused node before reconnecting device to the DH+ network. (Can perform reset if on-line via channel 0 RS-232 port without disconnecting from DH+.)

Page 157

Troubleshooting

157

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors If the status indicators indicate

The following error exists

• Power status indicator is The processor is trying to establish on • RS232 status indicator is communication, but cannot find flashing other active nodes • FLT status indicator is off or flashing

Probable Cause

Recommended Action

DH-485 communication parameters are set up improperly.

1. Check communication parameters of programmer. Programmer and processor communication rate must match. Programmer and processor node addresses must be different. 2. Try different combinations of: a. communication rate (default is 19.2 K for DH-485)

• Status of Run; Force; DH-485, DH+, or ENET; or Batt status indicators do not matter b. node address (default is 1) 3. Try to increase the maximum node address. (default is 31 for DH-485) Bad connection of communication Device.

1. Check cable continuity. 2. Check cable connections between programmer and processor. 3. Check communication device (for example, the 1747-PIC interface). replace if necessary.

Low or no power to communication device.

1. Verify proper power supply selection and backplane loading. (1747-PIC and 1747-AIC interface draw power off the backplane.) 2. Verify proper 120/240V power supply jumper selection. See page 106.

Publication 1747-UM011G-EN-P - June 2008

Page 158

158

Troubleshooting

SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors If the status indicators indicate

The following error exists

• Power status indicator is The processor is not transmitting on • RS232 status indicator is off • FLT status indicator is off or flashing • Status of Run; Force; DH-485, DH+, or ENET; or Batt status indicators do not matter

Probable Cause

Recommended Action

Channel is configured for DH-485 mode.

Check communication parameters of channel configuration. Also, refer to your programming software documentation.

Check the following communication parameters of programmer RS232/DF1 parameters are set and channel configuration. up improperly. 1. communication rate - programmer and processor communication rates must match 2. DF1 node addresses (default is 1 for half-duplex, and 9 for full-duplex) - programmer and processor addresses must be different 3. error checking 4. number of data bits Hardware problem.

1. Check cable connections. 2. Check cable pinouts. Also, see appendix C for RS-232 pinouts.

• Power status indicator is A fatal error has occurred on • FLT status indicator is on • Status of all other status indicators do not matter

Excessive noise or a faulty processor.

1. Cycle power to obtain flashing FLT status indicator and default program. 2. Examine the error code following the power cycle. Take appropriate action. 3. Reload the program. 4. Contact your local Rockwell Automation representative if the error persists.

Publication 1747-UM011G-EN-P - June 2008

Page 159

Troubleshooting

Identifying Processor Errors while Downloading an Operating System

159

The download process of the operating system by the SLC 5/03, SLC 5/04, and SLC 5/05 processors takes up to 2.5 minutes. While the download is in progress, the RUN and FLT status indicators remain off. The other four status indicators - RS232, DH485 (DH+on the SLC 5/04 and ENET on the SLC 5/05), FORCE, and BATT - turn on and off in a walking bit sequence. If the download is successful, these four status indicators remain on together. Jumper J4, on the bottom corner of the motherboard, provides write-protection from any download of a new operating system. The out of the box position of this jumper is PROTECT, or write-protect. Without the jumper, the processors are write-protected. Do not place the jumper to the program position during normal processor use.

ATTENTION

Jumper Placement

Catalog and Serial Number Label

Place the operating system upgrade label here.

The SLC 5/03, SLC 5/04, and SLC 5/05 processors are protected from the operating system download when jumper J4 is in this position: OR The SLC 5/03, SLC 5/04, and SLC 5/05 processors accept the operating system download when jumper J4 is in this position:

CAT

SLC 500 PLACE OS UPGRADE LABEL HERE PROCESSOR UNIT OPERATING SYSTEM INFO FAC OS # SER SER FRN

CURRENT REQUIREMENTS: PROTECT WHITE RED

SERIAL NO.

PROC. REV.

+ -

BATTERY

1

IND. CONT. EQ. UL LISTED FOR HAZ. LOC. A196 SA ®

1A @ 5 VDC 200mA @ 24 VDC

CLASS 1, GROUPS A, B, C AND D, DIV. 2 OPERATING TEMPERATURE CODE T3C

3 PROGRAM J4

MADE IN USA

Daughter Board

Mother Board Operating System Upgrade/Memory Module Socket

Jumper J4

If the download is not successful, the FLT status indicator turns on and a combination of status indicators flash on and off indicating an error condition. The following table provides you with information regarding error messages, possible cause(s) for the error, and recommended action to resolve the error.

Publication 1747-UM011G-EN-P - June 2008

Page 160

160

Troubleshooting

On Off On On On Off On Hardware Watchdog Timeout

Major hardware failure due to noise, improper grounding, or poor power source.

Cycle power and see if the error repeats itself. If the error clears, you should be able to download the operating system. If the error persists, contact your Rockwell Automation representative.

On Off On On On Off Off Fatal Hardware Error

Major hardware failure due to noise, improper grounding, or poor power source.

Cycle power and see if the error repeats itself. If the error clears, you should be able to download the operating system. If the error persists, contact your Rockwell Automation representative.

On Off Off On Off On On Corrupted Operating System Memory Module

The operating system on the Flash EPROM is corrupt.

Cycle power and see if the error repeats itself. If the error persists, either contact your Rockwell Automation representative for a new operating system memory module, or download the old operating system.

On Off On On Off On Off Flash EPROM Failure

The processor flash is corrupt.

Cycle power and see if the error repeats itself. If the error clears, you should be able to download the operating system. If the error persists, contact your Rockwell Automation representative.

On Off On On On On Off Corrupt or Missing Operating System

The operating system is missing or has been corrupted.

Cycle power and see if the error repeats itself. If the error clears, you should be able to download the operating system. If the error persists, contact your Rockwell Automation representative for a new operating system.

On Off On On Off On On Downloadable Operating System Failure

Failure during transmission of downloadable operating system.

Download the operating system.

On Off Off On On On Off Incompatible Platform

The upgrade of the operating system is incompatible with the processor hardware.

Use an operating system that is compatible with your processor hardware.

On Off Off On On On On Memory Write-Protected

An attempt was made to download the operating system onto write-protected memory.

Change the jumper on the processor to the program position.

RS232

The following error exists

BATT

Cycle power and see if the error repeats itself. If the error clears, you should be able to download the operating system. If the error persists, contact your Rockwell Automation representative.

DH485/DH+/ENET

Major hardware failure due to noise, improper grounding, or poor power source.

FLT

On Off Off On Off On Off NVRAM error

FORCE

Recommended Action

RUN

Probable Cause

POWER

Status Indicator

Publication 1747-UM011G-EN-P - June 2008