Page 141

Chapter

10

Troubleshooting

In this chapter, you will learn about: • contacting Rockwell Automation for assistance. • tips for troubleshooting your control system. • troubleshooting the SLC 5/01 and SLC 5/02 processors. • troubleshooting the SLC 5/03, SLC 5/04, and SLC 5/05 processors. • troubleshooting your input modules. • troubleshooting your output modules.

Contacting Rockwell Automation for Assistance

If you need to contact Rockwell Automation or local distributor for assistance, it is helpful to obtain the following (prior to calling): • Processor type, series letter, operating system (OS) number (obtained from the status file), firmware (FRN) number (see label on side of processor module) • Processor status indicator status • Processor error codes (found in S:6 of status file) • Hardware types in system (I/O modules, chassis) • Revision of programming software • TechConnect serial number • RSLogix software serial number

141

Publication 1747-UM011G-EN-P - June 2008

Page 142

142

Troubleshooting

Tips for Troubleshooting Your Control System

When troubleshooting, pay careful attention to these general warnings. ATTENTION

Have all personnel remain clear of the controller and equipment when power is applied. The problem may be intermittent and sudden unexpected machine motion could result in injury. Have someone ready to operate an emergency-stop switch in case it becomes necessary to shut off power to the controller equipment. Also, see NFPA 70E Part II for additional guidelines for safety-related work practices. Never reach into a machine to actuate a switch since unexpected machine motion can occur and cause injury. Remove all electrical power at the main power disconnect switches before checking electrical connections or inputs/outputs causing machine motion.

The first step in the troubleshooting procedure is to identify the problem and its source. Locate the majority of faults by observing the diagnostic indicators on the front of the power supply, processor unit, and I/O modules. These indicators, along with error codes identified in the programming device user manual and software, help trace the source of the fault to the user’s input/output devices, wiring, or the controller. Faults which do not clear by either toggling the keyswitch from Program to Run or cycling power, cannot be diagnosed or corrected without programming software. A flashing fault status indicator may indicate the user program in the processor is corrupted and a copy of the program will be needed before contacting your local Allen-Bradley sales office or distributor for assistance.

Removing Power Before working on a SLC 500 modular system, always remove the power supply input power at the main power disconnect switch. The power status indicator on the power supply indicates that dc power is being supplied to the chassis. The status indicator could be off when incoming power is present.

Publication 1747-UM011G-EN-P - June 2008

Page 143

Troubleshooting

143

Replacing Fuses ATTENTION

When replacing a fuse, be sure to remove all power from the system. Replacing a blown fuse can rarely restore power supply operation, requiring the power supply to be replaced.

Program Alteration There are several causes of alteration to the user program, including extreme environmental conditions, Electromagnetic Interference (EMI), improper grounding, improper wiring connections, and unauthorized tampering. If you suspect the memory has been altered, check the program against a previously saved program on an EEPROM, UVPROM or Flash EPROM module.

Troubleshooting the SLC 5/01 and SLC 5/02 Processors

Follow these steps to receive the maximum benefit of this troubleshooting section. 1. Identify the status of your processor status indicators. See chapter 5 for a description of status indicators and their states. 2. Using the tables on the following pages, match your processor and power supply status indicators with the status indicators in the first column. 3. Once the status indicators are matched to the appropriate table, move across the table identifying error description and probable causes. 4. Follow the recommended action steps for each probable cause until the error is corrected. 5. If recommended actions do not correct the error, contact your local Rockwell Automation sales office or distributor.

Publication 1747-UM011G-EN-P - June 2008

Page 144

144

Troubleshooting

Identifying SLC 5/01 and SLC 5/02 Processor Errors The following status indicators and tables provide you with information regarding error messages, possible cause(s) for the error, and recommended action to resolve the error. SLC 5/01 and SLC 5/02 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• All status indicators are Inadequate system No line power. power off

1. Verify proper line voltage and connections on the power terminals.

• Status of SLC 5/02 Comm status indicator does not matter

2. Verify proper 120/240V power supply jumper selection. See page 106. Power supply fuse blown.

1. Check the incoming power fuse, check for proper incoming power connections. Replace fuse. 2. If fuse blows again, replace the power supply. See page 139 on fuse replacement.

Power supply overload.

1. Remove line power to power supply. Remove several output modules from the chassis. Wait five minutes. Reapply power. 2. If condition reoccurs, re-calculate module configuration power required and verify proper power supply selection. See page 36. This problem can occur intermittently if power supply is slightly overloaded when output loading and temperature varies.

Defective power supply.

1. Recheck other probable causes. 2. Monitor the line power to chassis power supply for possible transient or shorting. 3. Replace the power supply.

• CPU Fault status indicator is on • All other status indicators are off

Inadequate system Improper line power power voltage selection.

• Status of SLC 5/02 Comm status indicator does not matter

Publication 1747-UM011G-EN-P - June 2008

Verify proper 120/240V power supply jumper selection. See page 106.

Page 145

Troubleshooting

145

SLC 5/01 and SLC 5/02 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• Power status indicator is on

Processor not in run mode

Either improper mode selected or user program logic error.

1. Verify selected processor mode.

Line power out of operating range.

1. Check proper 120/240V power supply jumper selection and incoming power connections.

• All other status indicators are off • Status of SLC 5/02 Comm status indicator does not matter

2. If in program or test mode, try to enter run mode. 3. If in suspend mode, check user program logic for suspend instructions.

2. Monitor for proper line voltage at the incoming power connections. Improper seating of power supply and/or processor in the chassis.

1. Remove power and inspect the power supply and processor chassis connections. 2. Re-install the devices and re-apply power. IMPORTANT The processor only operates in slot 0 of the first chassis.

Defective processor, power supply, or chassis.

1. Attempt to put processor in run mode in existing chassis. 2. Place the processor in another chassis. Apply power, reconfigure, and attempt to put processor in run mode. If unsuccessful, replace the processor. 3. Place the power supply in another chassis and test. If unsuccessful, replace the power supply. If successful, replace the original chassis.

• Power status indicator is on • Run status indicator is on • All other status indicators are off

System inoperable, User program logic error. no major CPU faults detected Defective I/O devices or I/O wiring.

1. Monitor logic in Run mode and verify desired I/O status. 2. Check for minor CPU faults. Test inputs and outputs according to I/O troubleshooting procedures starting on page 163.

• Status of SLC 5/02 Comm status indicator does not matter

Publication 1747-UM011G-EN-P - June 2008

Page 146

146

Troubleshooting

SLC 5/01 and SLC 5/02 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• Power status indicator on

CPU fault

CPU memory error.

Cycle power.

Faulty memory module.

1. Remove power and then remove the memory module from the processor.

• CPU Fault status indicator is on

2. Re-install the processor and re-apply power to the power supply. If steady CPU Fault status indicator changes to flashing, replace the existing memory module with a replacement module.

• All other status indicators are off • Status of SLC 5/02 Comm status indicator does not matter

See chapter 6 for removing and installing memory modules. Faulty processor or power supply.

1. Place the processor in another chassis not in the existing system and cycle power. If steady CPU Fault status indicator reappears, replace the processor. 2. If CPU Fault status indicator clears, monitor the line power going to the power supply in existing system. Replace existing system power supply if line power checks OK.

Processor firmware If upgrading the processor to a different firmware level, verify that the firmware chip orientation matches the upgrade kit installed directions. incorrectly. • Power status indicator is on

CPU major fault

• CPU Fault status indicator is flashing • All other status indicators are off • Status of SLC 5/02 Comm status indicator does not matter

Initial CPU factory power-up condition.

1. See chapter 8 and follow the start-up procedures.

Hardware/software major fault detected.

1. Monitor Status File word S:6 for major error code.

(erratic, repetitive power cycling can cause a processor major hardware fault)

2. Clear processor memory to get rid of the flashing CPU Fault status indicator.

2. Refer to the SLC 500 Instruction Set Reference Manual, publication 1747-RM001, for error codes and additional troubleshooting information. 3. Remove hardware/software condition causing fault. 4. Clear Status File S:1/13 major error bits, if set. 5. Clear Status File S:5 major error bits, if set. 6. Clear Status File S:6 major error code (optional). 7. Attempt to put processor in run mode. If unsuccessful, repeat recommended action steps above.

Publication 1747-UM011G-EN-P - June 2008

Page 147

Troubleshooting

147

SLC 5/01 and SLC 5/02 Processor Errors If the status indicators indicate

The following error exists

Probable Cause

Recommended Action

• Power status indicator is on

System does not operate per ladder logic

User forced I/O is disabling operation.

1. Monitor program file on-line and identify forced I/O.

System does not operate per programmed forces

User programmed forces are not enabled.

1. Monitor program file on-line and identify programmed forces.

CPU major error with low or no battery back-up

Loss of RAM during power-down.

1. Verify battery is connected. See page 136.

• Run status indicator is on

2. Disable appropriate forces and test system conditions again.

• Forced I/O status indicator is on • All other status indicators are off • Status of SLC 5/02 Comm status indicator does not matter • Power status indicator is on • Run status indicator is on • Forced I/O status indicator is flashing

2. Enable appropriate forces and test system conditions again. Once forces are enabled, the Forced I/O status indicator turns On (steady).

• All other status indicators are off • Status of SLC 5/02 Comm status indicator does not matter • Power status indicator is on • CPU Fault status indicator is flashing • Battery Low status indicator is on • All other status indicators are off

2. Replace the battery if you want RAM battery backup. See page 136. If you want to back up RAM with the capacitor in a SLC 5/01 (1747-L511), add or replace the Battery Low status indicator jumper. 3. Refer to processor major fault recommended action steps.

• Status of SLC 5/02 Comm status indicator does not matter

Publication 1747-UM011G-EN-P - June 2008

Page 148

148

Troubleshooting

Identifying SLC 5/02 Processor Communication Errors SLC 5/02 Processor Communication Errors If the status indicators indicate

The following error exists

• Power status indicator is The SLC 5/02 processor is not on • Comm status indicator is receiving data and is not off communicating • CPU Fault status with the indicator is off or programmer flashing

Probable Cause

Recommended Action

DH-485 communication parameters are improperly set up.

1. Check communication parameters of programmer. Programmer and processor communication rate must match. Programmer and processor node addresses must be different. 2. Try different combinations of: a. communication rate (default is 19.2 K)

• Status of Run, Forced I/O, and Battery Low status indicators does not matter b. node address (default is 1) 3. Try to increase the maximum node address. (default is 31) Bad connection of communication device.

1. Check cable continuity. 2. Check cable connections between programmer and processor. 3. Check communication device (for example, the 1747-PIC interface). Replace if necessary.

Low or no power to communication device.

1. Verify proper power supply selection and backplane loading. (The 1747-PIC and 1747-AIC interface draw power off the backplane.) 2. Verify proper 120/240V power supply jumper selection. See page 106.

• Power status indicator is The SLC 5/02 processor is on • Comm status indicator is receiving data, but is not on communicating • CPU Fault status with the indicator is off or programmer flashing

DH-485 communication parameters are set up improperly.

2. Try different combinations of: a. communication rate (default is 19.2 K)

• Status of Run, Forced I/O, and Battery Low status indicators does not matter • Power status indicator is A fatal error has occurred on • CPU Fault status indicator is on • Status of all other status indicators does not matter

1. Check communication parameters of programmer. Programmer and processor communication rate must match. Programmer and processor node addresses must be different.

b. node address (default is 1) 3. Try to increase the maximum node address. (default is 31) Excessive noise or a faulty SLC 5/02 processor.

1. Cycle power to obtain flashing CPU Fault status indicator and default program. 2. Examine the error code following the power cycle. Take appropriate action. 3. Reload the program. 4. Contact your local Rockwell Automation representative if the error persists.

Publication 1747-UM011G-EN-P - June 2008

Page 149

Troubleshooting

Troubleshooting the SLC 5/03, SLC 5/04, and SLC 5/05 Processors

149

Between the time you apply power to an SLC 5/03, SLC 5/04, or SLC 5/05 processor and the communication are established via a connected programming device, the only form of communication between you and the processor is through the status indicator display. When power is applied, all of the status indicators flash on and then off while the processor conducts hardware tests. This is part of the normal powerup sequence. Following the selftest by the processor, all the status indicators again flash on momentarily. If a user program is in a running state, the RUN status indicator will be on. If a fault exists within the processor, the FLT status indicator is on. Follow these steps to receive the maximum benefit of this troubleshooting section. 1. Identify the status of your processor status indicators. See chapter 5 for description of status indicators and their different states. 2. Using the tables on the following pages, match your processor and power supply status indicators with the status indicators in the first column. 3. Once the status indicators are matched to the appropriate table, move across the table identifying error description and probable causes. 4. Then follow the recommended action steps for each probable cause until the cause is identified. 5. If recommended actions do not identify the trouble cause, contact your local Rockwell Automation sales office or distributor.

Clearing SLC 5/03, SLC 5/04, and SLC 5/05 Processor Faults Using the Keyswitch Toggle the keyswitch from RUN to PROG and then back to RUN; this will clear some faults. If the keyswitch is left in the RUN position, the processor mode cannot be changed from a programmer/operator interface device. If you return the keyswitch to the REM position, you

Publication 1747-UM011G-EN-P - June 2008

Page 150

150

Troubleshooting can then use a programmer/operator interface device to change the processor mode. ATTENTION

If you clear a processor fault using the keyswitch, the processor immediately enters the Run mode.

Identifying SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors The following status indicators and tables provide you with information regarding error messages, possible cause(s) for the error, and recommended action to resolve the error. SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors If the status indicators indicate

The following error exists

• All status indicators are off

Inadequate system No line power. power

• Status of any Communication status indicator does not matter

Probable Cause

Recommended Action 1. Verify proper line voltage and connections on the power terminals. 2. Verify proper 120/240V power supply jumper selection. See page 106.

Power supply fuse blown.

1. Check the incoming power fuse, check for proper incoming power connections. Replace fuse. 2. If fuse blows again, replace the power supply. See page 139 on fuse replacement.

Power supply overload.

1. Remove line power to power supply. remove several output modules from the chassis. wait five minutes. reapply power. 2. If condition reoccurs, re-calculate module configuration power required and verify proper power supply selection. See page 36. This problem can occur intermittently if power supply is slightly overloaded when output loading and temperature varies.

Defective power supply.

1. Recheck other probable causes. 2. Monitor the line power to chassis power supply for possible transient or shorting. 3. Replace the power supply.

Publication 1747-UM011G-EN-P - June 2008