Page 81

Chapter

5

Identifying the Components of Your Processor

This chapter covers the following: • SLC 5/01 hardware features • SLC 5/02 hardware features • SLC 5/03 hardware features • SLC 5/04 hardware features • SLC 5/05 hardware features • Keyswitch for the SLC 5/03, SLC 5/04, and SLC 5/05 processors

SLC 5/01 Processor Hardware Features

The SLC 5/01 processor provides: • two choices of program memory size - 1 K or 4 K instructions. • control of up to 3840 input and output points. • powerful ladder logic programming instruction set. • subroutines. • a DH-485 communication channel (peer-to-peer communication response to message commands only). • capacitor backup for the 1747-L511 module; battery backup for the 1747-L514 module. • program using your programming software. • UL listed to US and Canadian Safety Standards, CE compliant, C-Tick marked. The figure on page 82 shows the hardware components of the SLC 5/01 processor (1747-L511 and 1747-L514).

81

Publication 1747-UM011G-EN-P - June 2008

Page 82

82

Identifying the Components of Your Processor

SLC 5/01 Hardware Components SLC 5/01 CPU Memory Module and Socket

PC RUN CPU FAULT FORCED I/O BATTERY LOW

Battery (provides back-up power for the CMOS RAM) Left Side View

Serial Number and Catalog Number

DH-485 Channel 1 Front View

The table below provides a general explanation of the SLC 5/01 processor status indicators. SLC 5/01 Status Indicators Processor When It Is Status Indicator(1) PC RUN (Color: red)

On (steady)

The processor is in the Run mode.

Off

The processor is in a mode other than Run.

CPU FAULT (Color: red)

Flashing (at power up)

The processor has not been configured.

Flashing (during operation)

The processor detects a major error either in the processor, chassis or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.

Flashing

One or more input or output addresses have been forced to an On or Off state but the forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

On (steady)

The battery voltage has fallen below a threshold level or the battery and the battery jumper are missing.

Off

The battery is functional, or the battery jumper is present.

FORCED I/O (Color: red)

BATTERY LOW (Color: red)

(1)

Publication 1747-UM011G-EN-P - June 2008

Indicates that

See chapter 10 for more information on status indicator status.

Page 83

Identifying the Components of Your Processor

SLC 5/02 Processor Hardware Features

83

The SLC 5/02 processor offers an enhanced instruction set, increased diagnostic capabilities, and expanded communication capabilities beyond the SLC 5/01 processors and fixed controllers. The SLC 5/02 processor provides: • program memory size of 4 K instructions. • control of up to 4096 input and output points. • PID - used to provide closed loop process control. • indexed addressing. • interrupt capability. • user fault routines. • ability to handle 32-bit signed math functions. • built-in DH-485 communication channel (initiation of peer-to-peer communication). • battery-backed RAM. • communication status indicator; when on, the status indicator indicates that there is communication activity on the DH-485 network. • program using your programming software. • UL listed to US and Canadian Safety Standards, CE compliant, C-Tick marked. The figure on page 84 shows some of the hardware components of the SLC 5/02 processor.

Publication 1747-UM011G-EN-P - June 2008

Page 84

84

Identifying the Components of Your Processor

SLC 5/02 Hardware Components SLC 5/02 CPU COMM RUN CPU FAULT FORCED I/O BATTERY LOW

Memory Module and Socket

Front View

Left Side View Serial Number and Catalog Number

Battery (provides back-up power for the CMOS RAM)

DH-485 Channel 1

The table below provides a general explanation of each processor status indicator (for both the SLC 5/02 series B and C processor). SLC 5/02 Status Indicators Processor When It Is Status Indicator(1) RUN (Color: red)

On (steady)

The processor is in the Run mode.

Off

The processor is in a mode other than Run.

CPU FAULT (Color: red)

Flashing (at power up)

The processor has not been configured.

Flashing (during operation)

The processor detects a major error either in the processor, expansion chassis or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.

Flashing

One or more input or output addresses have been forced to an On or Off state but the forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

FORCED I/O (Color: red)

Publication 1747-UM011G-EN-P - June 2008

Indicates that

Page 85

Identifying the Components of Your Processor

Processor Status Indicator(1)

When It Is

BATTERY LOW On (steady) (Color: red) COMM (Color: red)

(1)

85

Indicates that

The battery voltage has fallen below a threshold level or the battery is missing or not connected.

Off

The battery is functional.

On (steady)

The SLC 5/02 processor is connected to an active DH485 network.

Off

The SLC 5/02 processor is not receiving data.

See chapter 10 for more information on status indicator status.

Publication 1747-UM011G-EN-P - June 2008

Page 86

86

Identifying the Components of Your Processor

SLC 5/03 Processor Hardware Features

Publication 1747-UM011G-EN-P - June 2008

The SLC 5/03 processor offers: • program memory size of 8 K, 16 K, 32 K. • control of up to 4096 input and output points. • online programming (includes runtime editing). • built-in DH-485 channel. • built-in RS-232 channel, supporting: – DF1 full-duplex for point-to-point communication; remotely via a modem, or direct connection to programming or operator interface devices. (Use a 1747-CP3 cable for direct connection.). – DF1 radio modem for radio modem (peer-to-peer) communication. – DF1 half-duplex master/slave for SCADA type (point-to-multipoint) communication. – DH-485 (Serves as a second DH-485 channel. Use a 1761-NET-AIC interface with a 1747-CP3, 1761-CBL-AC00, or 1761-CBL-AP00 cable to connect to the DH-485 network.). – Modbus RTU Master communication with Modbus RTU slave devices. – ASCII I/O for connection to other ASCII devices, such as bar code readers, serial printers, and weigh scales. • channel-to-channel passthru (DH-485 to DF1 full-duplex, DF1 half-duplex Master, DF1 radio modem, or DH-485). • remote I/O passthru. • DeviceNet passthru. • built-in real-time clock/calendar. • 2 ms Selectable Timed Interrupt (STI). • 0.50 ms Discrete Input Interrupt (DII). • advanced math features - trigonometric, PID, exponential, floating-point, and the compute instruction. • indirect addressing. • logical ASCII addressing in PLC-5 type messages. • flash PROM provides firmware upgrades without physically changing EPROMS. • optional flash EPROM memory module available. • keyswitch - RUN, REMote, PROGram (clear faults). • battery-backed RAM. • additional instructions such as swap and scale with parameters (SLC 5/03 OS302 processor or later). • multi-point list (SLC 5/03 OS302 processor or later). • UL listed to US and Canadian Safety Standards, CE compliant, C-Tick marked.

Page 87

Identifying the Components of Your Processor

87

The figure on page 87 shows some of the hardware components of the SLC 5/03 processors (1747-L531, 1747-L532, and 1747-L533). SLC 5/03 Hardware Components SLC 5/03 CPU RUN FLT BATT

FORCE DH485 RS232

RUN REM PROG

Battery (provides back-up power for the CMOS RAM)

Memory Module Keyswitch DH-485 Channel 1

DH-485, DF1, or ASCII Channel 0 Operating System Download Protection Jumper – do not move unless updating processor Operating System firmware.

Left Side View

Serial Number and Catalog Number

Front View

The table below provides a general explanation of each processor status indicator on the SLC 5/03 processor. SLC 5/03 Status Indicators Processor When It Is Status Indicator(1)(2)

Indicates that

RUN (Color: green)

On (steady)

The processor is in the Run mode.

Flashing (during operation)

The processor is transferring a program from RAM to the memory module.

Off

The processor is in a mode other than Run.

Flashing (at power up)

The processor has not been configured.

Flashing (during operation)

The processor detects a major error either in the processor, chassis or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.

On (steady)

The battery voltage has fallen below a threshold level, or the battery is missing or not connected.

Off

The battery is functional.

FLT (Color: red)

BATT (Color: red)

Publication 1747-UM011G-EN-P - June 2008

Page 88

88

Identifying the Components of Your Processor

Processor When It Is Status Indicator(1)(2)

Indicates that

FORCE (Color: amber)

Flashing

One or more input or output addresses have been forced to an On or Off state but the forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

On (steady)

The Communication Active bit (S:1/7) is set in the System Status file and the processor is actively communicating on the DH-485 network.

Flashing

The processor is trying to establish communication, but there are no other active nodes on the DH-485 network.

Off

A fatal error is present (no communication).

On (flashing) DF1/Modbus RTU Master/ASCII mode

The SLC 5/03 processor is transmitting on the network.

Off DF1/Modbus RTU Master/ASCII mode

The SLC 5/03 processor is not transmitting on the network.

On (steady) DH-485 mode

The Communications Active bit (S:33/4) is set in the System Status file and the processor is actively communicating on the DH-485 network.

Flashing DH-485 mode

The processor is trying to establish communication, but there are no other active nodes on the DH-485 network.

Off DH-485 mode

A fatal error is present (no communication).

DH-485 (Color: green)

RS-232 (Color: green)

(1)

If the status indicators on the SLC 5/03 processor turn on in a predefined sequence, the SLC 5/03 processor is in the process of downloading a new operating system.

(2)

See chapter 10 for more information on status indicator status.

Publication 1747-UM011G-EN-P - June 2008

Page 89

Identifying the Components of Your Processor

SLC 5/04 Processor Hardware Features

89

The SLC 5/04 processors offer: • program memory sizes of 16 K, 32 K, or 64 K. • high-speed performance - 0.90 ms/K typical. • control of up to 4096 input and output points. • online programming (includes runtime editing). • built-in DH+channel, supporting: – high-speed communication (57.6 Kbaud, 115.2 Kbaud, and 230.4 Kbaud). – messaging capabilities with SLC 500, PLC-2, PLC-5, and ControlLogix processors. • built-in RS-232 channel, supporting: – DF1 full-duplex for point-to-point communication; remotely via a modem, or direct connection to programming or operator interface devices. (Use a 1747-CP3, 1761-CBL-AC00, or 1761-CBL-AC00 cable for direct connection.). – DF1 radio modem for radio modem (peer-to-peer) communication. – DF1 half-duplex Master/Slave for SCADA type (point-to-multipoint) communication. – DH-485 (Use a 1761-NET-AIC with a 1747-CP3 cable to connect to the DH-485 network.). – Modbus RTU Master communication with Modbus RTU slave devices. – ASCII I/O for connection to other ASCII devices, such as bar code readers, serial printers, and weigh scales. • channel-to-channel passthru (DH+ to DF1 full-duplex, DF1 half-duplex Master, DF1 radio modem, or DH-485). • remote I/O passthru. • DeviceNet passthru. • built-in real-time clock/calendar. • 1 ms Selectable Timed Interrupt (STI). • 0.50 ms Discrete Input Interrupt (DII). • advanced math features - trigonometric, PID, exponential, floating point, and the compute instruction. • indirect addressing. • logical ASCII addressing in PLC-5 type messages. • flash PROM provides firmware upgrades without physically changing EPROMS. • optional flash EPROM memory module available. • keyswitch - RUN, REMote, PROGram (clear faults). • battery-backed RAM. • additional instructions such as swap and scale with parameters. Publication 1747-UM011G-EN-P - June 2008

Page 90

90

Identifying the Components of Your Processor

• multi-point list. • UL listed to US and Canadian Safety Standards, CE compliant, C-Tick marked. This figure below shows some of the hardware components of the SLC 5/04 processors (1747-L541, 1747-L542, or 1747-L543). SLC 5/04 Hardware Components SLC 5/04 CPU RUN FLT BATT

FORCE DH+ RS232

RUN REM PROG

Battery (provides back-up power for the CMOS RAM)

Memory Module DH+ Channel 1

Keyswitch

DH-485, DF1, or ASCII Channel 0 Operating System Download Protection Jumper – do not move unless updating processor Operating System firmware.

Serial Number and Catalog Number

Left Side View

Front View

The table below provides a general explanation of each processor status indicator on the SLC 5/04 processors. SLC 5/04 Status Indicators Processor When It Is Status Indicator(1)(2) RUN (Color: green)

FLT (Color: red)

Publication 1747-UM011G-EN-P - June 2008

Indicates that

On (steady)

The processor is in the Run mode.

Flashing (during operation)

The processor is transferring a program from RAM to the memory module.

Off

The processor is in a mode other than Run.

Flashing (at power up)

The processor has not been configured.

Flashing (during operation)

The processor detects a major error either in the processor, chassis, or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.