For the Allen-Bradley 1747-L524

Page 91

Identifying the Components of Your Processor

Processor Status Indicator(1)(2)

When It Is

Indicates that

BATT (Color: red)

On (steady)

The battery voltage has fallen below a threshold level, or the battery is missing or not connected.

Off

The battery is functional.

Flashing

One or more input or output addresses have been forced to an On or Off state but the forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

FORCE (Color: amber)

On (steady) DH+ (Color: green or red)

RS-232 (Color: green)

91

The Communications Active bit (S:1/7) is set in the System Status file and the processor is actively communicating on the DH+ network.

Flashing green

The processor is trying to establish communication, but there are no other active nodes on the DH+ network.

Flashing red

There are duplicate nodes on the link with the same node address.

On (steady) DF1/Modbus RTU Master/ASCII mode

The SLC 5/04 processor is transmitting on the network.

Off DF1/Modbus RTU Master/ASCII mode

The SLC 5/04 processor is not transmitting on the network.

On (steady) DH-485 mode

The Communications Active bit (S:33/4) is set in the System Status file and the processor is actively communicating on the DH-485 network.

Flashing DH-485 mode

The processor is trying to establish communication, but there are no other active nodes on the DH-485 network.

Off DH-485 mode

A fatal error is present (no communication).

(1)

If the status indicators on the SLC 5/04 processor turn on in a predefined sequence, the SLC 5/04 processor is in the process of downloading a new operating system.

(2)

See chapter 10 for more information on status indicator status.

Publication 1747-UM011G-EN-P - June 2008

Page 92

92

Identifying the Components of Your Processor

SLC 5/05 Processor Hardware Features

Publication 1747-UM011G-EN-P - June 2008

The SLC 5/05 processors offer: • program memory sizes of 16 K, 32 K, or 64 K. • high-speed performance - 0.90 ms/K typical. • control of up to 4096 input and output points. • online programming (includes runtime editing). • built-in 10/100Base-T Ethernet channel, supporting: – high-speed computer communication using TCP/IP. – messaging capabilities with SLC 5/05, PLC-5, and ControlLogix processors on Ethernet. – SNMP for standard Ethernet network management. – BOOTP for optional dynamic IP address assignment. • built-in RS-232 channel, supporting: – DF1 full-duplex for point-to-point communication; remotely via a modem, or direct connection to programming or operator interface devices. (Use a 1747-CP3, 1761-CBL-AC00, or 1761-CBL-AP00 cable for direct connection.). – DF1 radio modem for radio modem (peer-to-peer) communication. – DF1 half-duplex master/slave for SCADA type (point-to-multipoint) communication. – DH-485 (Use a 1761-NET-AIC with a 1747-CP3 cable to connect to the DH-485 network.). – Modbus RTU Master communication with Modbus RTU slave devices. – ASCII I/O for connection to other ASCII devices, such as bar code readers, serial printers, and weigh scales. • Channel-to-channel passthru (Ethernet to DF1 full-duplex, DF1 half-duplex Master, DF1 radio modem, or DH-485). • remote I/O and DeviceNet passthru. • built-in real-time clock/calendar. • 1 ms Selectable Timed Interrupt (STI). • 0.50 ms Discrete Input Interrupt (DII). • advanced math features - trigonometric, PID, exponential, floating point, and the compute instruction. • indirect addressing. • logical ASCII addressing in PLC-5 type messages. • flash PROM provides firmware upgrades without physically changing EPROMS through the Ethernet port. • optional flash EPROM memory module available. • keyswitch - RUN, REMote, PROGram (clear faults). • battery-backed RAM. • additional instructions such as swap and scale with parameters

Page 93

Identifying the Components of Your Processor

93

• multi-point list. • UL listed to US and Canadian Safety Standards, CE compliant, C-Tick marked. The figure below shows some of the hardware components of the SLC 5/05 processors (1747-L551, 1747-L552, and 1747-L553). SLC 5/05 Hardware Components SLC 5/05 CPU RUN FLT BATT

FORCE ENET RS232

RUN REM PROG

Battery (provides back-up power for the CMOS RAM)

_______ . _______ . _______ . _______

Memory Module

Ethernet Hardware Address xx:xx:xx Operating System Download Protection Jumper – do not move unless updating processor Operating System firmware.

Keyswitch

Channel 1 Ethernet (10Base-T) Channel 0 RS 232 (DH-485, DF1, or ASCII)

Write-on area for IP Address Serial Number and Catalog Number

Left Side View

Front View

The table below provides a general explanation of the processor status indicators. SLC 5/05 Status Indicators When It Is Processor Status Indicator RUN (Color: green)

FLT (Color: red)

Indicates that

On (steady)

The processor is in the Run mode.

Flashing (during operation)

The processor is transferring a program from RAM to the memory module.

Off

The processor is in a mode other than Run.

Flashing (at power up)

The processor has not been configured.

Flashing (during operation)

The processor detects a major error either in the processor, chassis, or memory.

On (steady)

A fatal error is present (no communication).

Off

There are no errors.

Publication 1747-UM011G-EN-P - June 2008

Page 94

94

Identifying the Components of Your Processor

Processor Status Indicator

When It Is

Indicates that

BATT (Color: red)

On (steady)

The battery voltage has fallen below a threshold level, or the battery is missing or not connected.

Off

The battery is functional.

Flashing

One or more input or output addresses have been forced to an On or Off state but the forces have not been enabled.

On (steady)

The forces have been enabled.

Off

No forces are present or enabled.

Solid green

The Ethernet port is functioning properly and is connected to an active Ethernet network.

Flashing green

The Ethernet port is functioning properly, connected to an active Ethernet network, and is transmitting packets.

Flashing red

A hardware or software fault has occurred and is being reported via a code. Contact Allen-Bradley for assistance.

Off

No Ethernet connection or processor halted.

On (steady) DF1/Modbus RTU Master/ASCII mode

The SLC 5/05 processor is transmitting on the network.

Off DF1/Modbus RTU Master/ASCII mode

The SLC 5/05 processor is not transmitting on the network.

On (steady) DH-485 mode

The Channel 0 Communications Active bit (S:33/4) is set in the System Status file and the processor is actively communicating on the network.

Flashing DH-485 mode

The processor is trying to establish communication, but there are no other active nodes on the DH-485 network.

Off DH-485 mode

A fatal error is present (no communication).

FORCE (Color: amber)

ENET Channel 1 (Color: green or red)

RS-232 Channel 0 (Color: green)

Publication 1747-UM011G-EN-P - June 2008

Page 95

Identifying the Components of Your Processor

Keyswitch for the SLC 5/03, SLC 5/04, and SLC 5/05 Processors

95

The SLC 5/03, SLC 5/04, and SLC 5/05 processors include a 3-position keyswitch on the front panel that lets you select one of three modes of operation: RUN, PROGram, and REMote. You can remove the key in each of the three positions. ATTENTION

IMPORTANT

Depending on the size of your user program, the processor can take up to 2.5 s to change modes when you change the position of the keyswitch from RUN to PROG or to REM. Do not use the keyswitch in place of a hardwired master control relay or an emergency-stop switch. The SLC 5/01 and SLC 5/02 processors do not have a keyswitch. Therefore, all modes must be changed via the communication channels.

RUN Position This position places the processor in the Run mode. The processor scans/executes the ladder program, monitors input devices, energizes output devices, and acts on enabled I/O forces. You can only change the processor mode by changing the keyswitch position. You cannot perform online program editing. To change the processor mode to Run, toggle the keyswitch from PROG or REM to RUN. When the keyswitch is left in the RUN position, you cannot use a programmer/operator interface device to change the processor mode.

PROG Position This position places the processor in the Program mode. The processor does not scan/execute the ladder program, and the controller outputs are de-energized. You can perform online program editing. You can only change the processor mode by changing the keyswitch position. To change the processor mode to Program, toggle the keyswitch from REM or RUN to PROG. When the keyswitch is left in the PROG position, you cannot use a programmer/operator interface device to change the processor mode.

Publication 1747-UM011G-EN-P - June 2008

Page 96

96

Identifying the Components of Your Processor

REM Position This position places the processor in the Remote mode: either the REMote Run, REMote Program, or REMote Test mode. You can change the processor mode by changing the keyswitch position or by changing the mode from a programmer/operator interface device. You can perform online program editing in this position. To change the processor mode to REM, toggle the keyswitch from RUN or PROG to REM. When the keyswitch is in the REM position, you can use a programmer/operator interface device to change the processor mode.

Publication 1747-UM011G-EN-P - June 2008

Page 97

Chapter

6

Installing Your Hardware Components

This chapter shows you how to install the following hardware components: • Chassis • Processor • Modules • Memory module • Power supply • Chassis interconnect cable

Compliance to European Union Directives

This product is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive The analog modules are tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2 EMC – Generic Emission Standard, Part 2 - Industrial Environment • EN 50082-2 EMC – Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.

97

Publication 1747-UM011G-EN-P - June 2008

Page 98

98

Installing Your Hardware Components

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the industrial Automation, Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1.

The power supply support panel (left end panel) has screws as indicated in the following illustration. The center and right end panels are held in position by a molded latch and do not require screws.

Install Your Chassis

Screw

Latch Latch

Screw Latch

Latch

Perform this procedure to install your chassis. 1. Drill holes in the back panel of the enclosure for chassis mounting tabs. ATTENTION

Publication 1747-UM011G-EN-P - June 2008

Be careful of metal chips when drilling mounting holes for the SLC chassis. Do not drill holes above an SLC chassis if a processor and I/O modules are installed.

Page 99

Installing Your Hardware Components

99

2. Install the hardware for the top mounting tabs. M4 or M5 (#10 or #12) phillips screw and star washer (or SEM screw)

TIP

Scrape paint off the back panel for an electrical connection between the chassis and back panel.

3. Slide the chassis over the installed hardware and tighten the screws. ATTENTION

If the chassis mounting tabs do not lay flat before the screws are tightened, use additional washers as shims so the chassis will not warp when tightening the screws. Warping the chassis could damage the backplane and cause poor connections.

Publication 1747-UM011G-EN-P - June 2008

Page 100

100

Installing Your Hardware Components

4. Leaving far-left and far-right tabs open for grounding, install the remaining tab hardware (for a four-slot chassis, leave both tabs open).

Publication 1747-UM011G-EN-P - June 2008