Page 101
Installing Your Hardware Components
Installing Your Processor
101
The processor always occupies the first slot of the first chassis. You can only install one processor per system. ATTENTION
Never install, remove, or wire any module while power is applied. Also, do not expose processor modules to surfaces or other areas that may typically hold an electrostatic charge. Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the power supplies. • Touch a grounded object to discharge static potential. • Do not touch the backplane connector or connector pins. • Do not touch circuit components inside the power supply. • Use a static-safe work station if available. • Keep the power supplies in their static-shield packaging when not in use.
IMPORTANT
IMPORTANT
If the equipment is not installed and used as described in this manual, the protection provided by the equipment may be impaired. If your processor has a battery, the battery is an option for the SLC 5/01 (1747-L511) processor, make sure it is connected before installing your processor into the chassis. This provides memory backup for your processor should the controller power supply fail.
Publication 1747-UM011G-EN-P - June 2008
Page 102
102
Installing Your Hardware Components
Install Modules
Follow the steps below to install your modules. 1. Align the circuit board of the module with the card guide in the chassis. Retainer Clip
Side View
Retainer Clip
2. Gently slide the module in until both top and bottom retainer clips are secured.
3. Install a wire tie to secure your wiring and keep it neat. (If you feed the tie into one hole, it will be routed back out through the other.) 4. Cover any unused slots with card slot fillers (catalog number 1746-N2) to keep the chassis free from debris and dust. 5. To remove the module, press the retaining clips at the top and bottom of the module and slide the module out.
Publication 1747-UM011G-EN-P - June 2008
Page 103
Installing Your Hardware Components
Install Your Memory Module
103
Always turn off power to the controller before removing the processor or inserting or removing the memory module. This guards against possible damage to the module and also undesired processor faults. Memory modules are mounted in carriers or have connectors that are keyed to guard against improper installation. ATTENTION
To avoid potential damage to the memory modules, handle them by the ends of the carrier or edges of the plastic housing. Skin oil and dirt can corrode metallic surfaces, inhibiting electrical contact. Also, do not expose memory modules to surfaces or areas that may typically hold an electrostatic charge. Electrostatic charges can alter or destroy memory.
1. If the processor module is installed in the chassis, remove the module by pressing the retainer clips at both the top and bottom of the module and sliding it out. 2. Locate the socket (or connector if you have an SLC 5/03, SLC 5/04, or SLC 5/05 processor) on the processor board. Then place the memory module into the socket or onto the connector and press firmly in place.
Side View of SLC Processor 1747-L511, 1747 -L514, and 1747-L524
Side View of SLC Processor 1747-L531, 1747-L532, 1747-L533, 1747-L541, 1747-L542, 1747-L543, 1747-L551, 1747-L552, and 1747-L553
Memory Module Socket
Jumper J1 (Note: Jumper J1 not on 1747-L511.)
Memory Module Connector
Publication 1747-UM011G-EN-P - June 2008
Page 104
104
Installing Your Hardware Components
3. Place jumper J1 as shown below. Processor Type
1747-M1, -M2, -M3
1747-M4
Invalid Settings
No Jumper J1
No Jumper J1
No Jumper J1
1747-L514, 1747-L524
1747-L511, 1747-L531, 1747-L532, 1747-l533, 1747-L541, 1747-L542, 1747-L543, 1747-L551, 1747-L552, 1747-L553
4. Install the processor module into the chassis. 5. Restore power to the controller.
Remove the Memory Module Follow this procedure to remove the memory module. 1. Remove power and pull out the processor. 2. Grasp the carrier tabs (or connector for the SLC 5/03, SLC 5/04, and SLC 5/05 processor) with your thumb and index fingers, then gently but firmly lift upwards on either end of the memory module carrier. 3. When the end is partially raised, begin lifting the other end in the same manner. Repeat this until the memory module has been completely removed from the socket.
Install Your Power Supply
If you have multiple chassis configurations, install the chassis interconnect cable before installing the power supply. See Install Your Chassis Interconnect Cable on page 108. Also, the power supply terminals accept two 2 mm2 (#14 AWG) wires and are marked as shown in the figure on page 106.
Publication 1747-UM011G-EN-P - June 2008
Page 105
Installing Your Hardware Components
105
Perform this procedure to install the power supply. 1. Align the circuit board with the card guide on the left side of the chassis. Slide the power supply in until it is flush with the chassis.
1.2 Nm (11 lb-in) maximum torque
2. Fasten the power supply to the chassis with the two Phillips head screws. 3. Place the jumper to match the input voltage. (This does not apply to 1746-P3, 1746-P5, 1746-P6, or 1746-P7 power supply which do not have a jumper.) ATTENTION
Make jumper selection before applying power. Hazardous voltage is present on exposed pins when power is applied.
Publication 1747-UM011G-EN-P - June 2008
Page 106
106
Installing Your Hardware Components
If you connect or disconnect the wiring to the terminal blocks or if you insert or remove the power supply while the power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous. Failure to remove power could cause injury to personnel and/or equipment.
ATTENTION
POWER
POWER
Fuse
Fuse
Jumper Selection
User
100/120 Volts 200/240 Volts
PWR OUT +24V dc PWR OUT COM
Not Used Not Used
120/240V ac
+24V dc
V ac NEUT
V dc NEUT
Chassis Ground
Chassis Ground
1746-P1 and P2
1746-P3
1746-P5 Jumper Selection
POWER
User
PWR OUT +24V dc PWR OUT COM
85 to 132V ac 170 to 250V ac
POWER
User Power
PWR OUT +24V dc PWR OUT COM +125V dc
85 to 132V ac
V dc NEUT
Jumper
Chassis Ground
170 to 250V ac 1746-P6 L1: 85 to 132 /170 to 250V ac 1746-P4
L2: NEUT
User Power 1746-P5, -P6, and -P7
PWR OUT +24V dc PWR OUT COM +48V dc V dc NEUT
Chassis Ground
Chassis Ground
User Power
1746-P7 Not Used Not Used +12/24V dc V dc NEUT Chassis Ground
Publication 1747-UM011G-EN-P - June 2008
Page 107
Installing Your Hardware Components
IMPORTANT
107
Terminal screws on the 1746-P1, 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supply should be tightened with a maximum torque of 1 Nm (8.8 lb-in). Terminal screws on the 1746-P4 power supply should be tightened with a max torque of 0.8 Nm (7 lb-in).
4. Connect the ground screw of the power supply to the nearest ground or ground bus. Use a #14 AWG 75 Deg. Copper wire (Category 1 per Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1) and keep the leads as short as possible. The 1746-P4 is shown below.
Chassis Ground Tighten terminal screws to 0.8 Nm (7 lb-in)
Nearest Ground Bus
5. Remove the warning label from the top of the power supply. 6. Connect line power to the power supply. ATTENTION
ATTENTION
If you have a 1746-P3 power supply, see page 64 for special grounding considerations.
Your SLC 500 power supply can be damaged by voltage surges when switching inductive loads such as motors, motor starters, solenoids, and relays. To avoid damage to your SLC 500 power supply in these applications, use an isolation transformer to isolate the power supply from harmful voltage surges.
For the 1746-P1, 1746-P2, 1746-P4, 1746-P5, and 1746-P6 power supplies, use PWR OUT +24V dc and PWR OUT COM terminals to Publication 1747-UM011G-EN-P - June 2008
Page 108
108
Installing Your Hardware Components power 24V dc sensors and loads. The terminals on the 1746-P1, 1746-P2, 1746-P5, and 1746-P6 power supply provide an isolated, nonfused 200 mA, 24V dc power supply. The terminals on the 1746-P4 power supply provide an isolated, nonfused 1 A, 24V dc power supply. (The 1746-P3 and 1746-P7 power supplies do not provide for an external power source.)
Install Your Chassis Interconnect Cable
Three cables are available to link modular hardware chassis. Catalog number 1746-C7 cable is 152.4 mm (6 in.) in length and is used when connecting chassis side-by-side. Catalog number 1746-C9 is 914.4 mm (36 in.) in length and 1746-C16 is 1.27 m (50 in.) in length and are used to link one chassis below the other. IMPORTANT
1746-C9 and 1746-C16 cables have a rigid, unbendable shrink wrap applied at the end of each connector, which provides strain relief. When using these cables, provide at least 101.6 mm (4 in.) of clearance at the side of the chassis to allow for proper bend radius of the cable.
. ATTENTION
Do not use any cables other than those provided. Longer cables could affect the integrity of data communication between the chassis, possibly causing unsafe operation. Also, make sure the cable is properly secured to protect against the effects of shock and vibration.
In multiple chassis configurations, install the chassis interconnect cable before installing the power supply. The cables are keyed for proper installation. The end of the cable that plugs into the right socket in the chassis has the key on the top of the connector. The opposite end of the cable has the key on the inside of the connector for insertion into the expansion chassis.
Publication 1747-UM011G-EN-P - June 2008
Page 109
Installing Your Hardware Components
109
Chassis Connections SLC chassis where processor will be installed
To remove the cable, move the tabs on the socket outward and the connector pops out. ATTENTION
The expansion cable must always exit the right end of the chassis with the processor and connect to the left end of the next I/O chassis.
Publication 1747-UM011G-EN-P - June 2008
Page 110
110
Installing Your Hardware Components
Notes:
Publication 1747-UM011G-EN-P - June 2008