Page 111

Chapter

7

Wiring Your I/O Modules

This chapter describes how to wire your I/O modules. It covers the following: • Defining sinking and sourcing • Preparing your wiring layout • Features of an I/O module • Recommendations for wiring I/O devices • Wiring your I/O modules • Octal label kit installation • Using removable terminal blocks

Defining Sinking and Sourcing

Sinking and sourcing are terms used to describe a current signal flow relationship between field input and output devices in a control system and their power supply. • Field devices connected to the positive side (+V) of the field power supply are sourcing field devices. • Field devices connected to the negative side (dc Common) of the field power supply are called sinking field devices. To maintain electrical compatibility between field devices and the programmable controller system, this definition is extended to the input/output circuits on the discrete I/O modules. • Sourcing I/O circuits supply (source) current to sinking field devices. • Sinking I/O circuits receive (sink) current from sourcing field devices. Europe: dc sinking input and sourcing output module circuits are the commonly used options.

111

Publication 1747-UM011G-EN-P - June 2008

Page 112

112

Wiring Your I/O Modules

Contact Output Circuits, ac or dc Relays can be used for either ac or dc output circuits and accommodate either sinking or sourcing field devices. These capabilities are a result of the output switch being a mechanical contact closure, not sensitive to current flow direction and capable of accommodating a broad range of voltages. This high degree of application flexibility makes contact output modules very popular and useful in control environments with a broad mix of electrical I/O circuit requirements.

Solid-State dc I/O Circuits The design of dc field devices typically requires that they be used in a specific sinking or sourcing circuit depending on the internal circuitry of the device. DC input and output field circuits are commonly used with field devices that have some form of internal solid state circuitry that need a dc signal voltage to function.

Sourcing Device with Sinking Input Module Circuit The field device is on the positive side of the power supply between the supply and the input terminal. When the field device is activated, it sources current to the input circuit. Field Device

I

Input dc Input Circuit

+ dc Power Supply _

Publication 1747-UM011G-EN-P - June 2008 dc Com

Page 113

Wiring Your I/O Modules

113

Sinking Device with Sourcing Input Module Circuit The field device is on the negative side of the power supply between the supply and the input terminal. When the field device is activated, it sinks current from the input circuit. Field Device

Input

I dc Input Circuit

_ dc Power Supply +

Vdc

Sinking Device with Sourcing Output Module Circuit The field device is on the negative side of the power supply between the supply and the output terminal. When the output is activated, it sources current to the field device. Vdc

+

Field Device dc Power Supply

I Out dc Output Circuit

_ dc Com

Sourcing Device with Sinking Output Module Circuit The field device is on the positive side of the power supply between the supply and the output terminal. When the output is activated, it sinks current from the field device.

+ dc Power Supply

Field Device

Vdc I Out dc Output Circuit

_ dc Com

Publication 1747-UM011G-EN-P - June 2008

Page 114

114

Wiring Your I/O Modules

Preparing Your Wiring Layout

Careful wire routing within the enclosure helps to cut down electrical noise between I/O lines. Follow these rules for routing your wires. • Route incoming power to the controller by a separate path from wiring to I/O devices. Where paths must cross, their intersection should be perpendicular. IMPORTANT

Do not run signal or communication wiring and power wiring in the same conduit.

• If wiring ducts are used, allow for at least 50.8 mm (2 in.) between I/O wiring ducts and the controller. If the terminal strips are used for I/O wiring, allow for at least two inches between the terminal strips and the controller. • Limit the cable length for the TTL input module to 15.24 m (50 ft) per point and 3.05 m (10 ft) per point for the TTL output module. Use low power dc I/O wiring even though it is less tolerant to electrical noise. ATTENTION

Handle the TTL module by its ends, not metallic surfaces. Electrostatic discharges can damage the module. Do not expose the TTL module to electrostatic charges.

• Segregate I/O wiring by signal type. Bundle wiring with similar electrical characteristics together. Wires with different signal characteristics should be routed into the enclosure by separate paths. Refer to Allen-Bradley Programmable Controller Grounding and Wiring Guidelines, publication 1770-4.1. ATTENTION

Publication 1747-UM011G-EN-P - June 2008

If the controller is being installed within a potentially hazardous environment (that is, Class I, Division 2), all wiring must comply with the requirements stated in the National Electrical Code 501-4 (b).

Page 115

Wiring Your I/O Modules

Recommendations for Wiring I/O Devices

115

The following are general recommendations for wiring I/O devices. ATTENTION

Before you install and wire I/O devices, disconnect power from the controller and any other source to the I/O devices.

• Use acceptable wire gauge. The I/O wiring terminals are designed to accept two wires per terminal (maximum) of the following size wire: – Europe: 2 mm2 cross section or smaller – United States: 14 AWG or smaller stranded wires • See diagram on page 116 for maximum torque values for wiring terminal screws and terminal block screws. • Label wiring to I/O devices, power sources, and ground. Use tape, shrink-tubing, or other dependable means for labeling purposes. In addition to labeling, use colored insulation to identify wiring based on signal characteristics. For example, you may use blue for dc I/O wiring and red for ac I/O wiring. • Route the wires down and away from the module, securing them with the cable tie. • Bundle wiring for each similar I/O device together. If you use ducts, allow at least 5 cm (2 in.) between the ducts and the controller so there is sufficient room to wire the devices. • Terminal cover plates have a write-on area for each terminal. Use this area to identify your I/O devices. Label the removable terminal block if you have not already. ATTENTION

Calculate the maximum possible current in each power and common wire. Observe all local electrical codes dictating the maximum current allowable for each wire size. Current above the maximum ratings may cause wiring to overheat, which can cause damage. Capacitors on input modules have a stored charge that can cause a non-lethal shock. Avoid mounting the controller in a position where installation or service personnel would be in danger from startle reaction.

Publication 1747-UM011G-EN-P - June 2008

Page 116

116

Wiring Your I/O Modules

Features of an I/O Module

Below is an example of a combination I/O module.

OUTPUT

Color Band

INPUT

0

4

0

4

1

5

1

5

2

2

3

3

I/O Status Indicators Terminal Block Screw (maximum torque: 0.6 Nm (5.3 lb-in))

Input and Output Terminals Connected to Terminal Block

Terminal Block (may be color-coded and removable on some modules)

Hinged Wiring Terminal Door with Label

Terminal Wiring • 2 wires per terminal maximum • #14 AWG (2mm2) maximum • Maximum torque: 0.9 Nm (8 lb-in) Terminal Block Screw (maximum torque: 0.6 Nm (5.3 lb-in))

Tie Wire Wires Leading to Input and Output Devices

Wiring Your I/O Module

Terminals on the modules have self-lifting pressure plates that accept two 2 mm2 (14 AWG) wires. Series B 12-point and 16-point and analog modules are equipped with removable terminal blocks for ease of wiring. The plug for the removable terminals is also color coded: • red (ac) • blue (dc) • orange (relay) • green (specialty). Status indicators on the front of each module display the status of each I/O point. The status indicators illuminate when the proper signal to an input terminal is applied or when the processor commands an output to be energized. To locate the I/O module wiring diagrams, contact your Rockwell Automation sales office for the latest selection guide, publication 1747-SG001. Or, locate the installation instruction sheet that was sent with your I/O module. It also includes I/O wiring diagrams.

Publication 1747-UM011G-EN-P - June 2008

Page 117

Wiring Your I/O Modules

117

1. Install a tie wire to secure your wiring and keep it neat. (If you feed the tie into one hole, it is routed back out through the other.) 2. Cover any unused slots with card slot fillers (catalog number 1746-N2) to keep the chassis free from debris and dust.

Octal Label Kit Installation

The octal label kit consists of an octal filter label and a door label. Use these octal labels to replace the decimal labels that are attached to the I/O modules. The kits can be obtained through your Allen-Bradley distributor. (The octal label kit is applicable when using 1746 I/O with PLC-5 processors via a 1747-ASB Remote I/O Adapter.)

Apply the Octal Filter Label 1. Remove the octal filter label from its paper carrier. 2. Align the octal filter label numbers horizontally to the module color bar and over the decimal filter numbers, as shown in the illustration below. 3. Apply the octal label to the filter. 4. Press firmly to ensure proper adhesion of the label.

Apply the Octal Door Label 1. Remove the octal door label from its paper carrier. 2. Align it over the decimal door label on the inside of the door. 3. Press firmly to ensure proper adhesion of the label.

Publication 1747-UM011G-EN-P - June 2008

Page 118

118

Wiring Your I/O Modules

Decimal Filter Label

Module Color Bar

Octal Filter Label

Octal Door Label

Decimal Door Label

Octal Kit and I/O Module Information

Publication 1747-UM011G-EN-P - June 2008

I/O Module Cat. No.

Octal Kit Cat. No.

I/O Module Cat. No.

Octal Kit Cat. No.

1746-IA16

1746-RL40

1746-OV16

1746-RL53

1746-IB16

1746-RL41

1746-OW16

1746-RL54

1746-IG16

1746-RL42

1746-OBP16

1746-RL55

1746-IM16

1746-RL43

1746-OVP16

1746-RL56

1746-IN16

1746-RL44

1746-OAP12

1746-RL57

1746-IV16

1746-RL45

1746-IC16

1746-RL58

1746-ITB16

1746-RL46

1746-IH16

1746-RL59

1746-ITV16

1746-RL47

1746-IB32

1746-RL60

1746-OA16

1746-RL50

1746-IV32

1746-RL61

1746-OB16

1746-RL51

1746-OB32 1746-OB32E

1746-RL70

1746-OG16

1746-RL52

1746-OV32

1746-RL71

1746-OB16E

1746-RL72

Page 119

Wiring Your I/O Modules

Using the Removable Terminal Block (RTB)

119

The Removable Terminal Block (RTB) is provided on all 12-point and 16-point discrete I/O modules and analog modules. They allow for faster and more convenient wiring of the I/O modules. The modules and the RTB are color-coded. Color

Type of I/O Removable Terminal Block

Red ac inputs/outputs

Blue dc inputs/outputs

Orange relay outputs

Green specialty modules

Replacement terminal blocks are available if they are lost or damaged. See the replacement part list in chapter 11.

Remove the RTB Below are guidelines for removing the I/O Removable Terminal Block. ATTENTION

Never install or remove I/O modules or terminal blocks while the SLC chassis is powered.

1. If the I/O module is already installed in the chassis, remove power to the SLC chassis. 2. Unscrew the upper right and lower left terminal block release screws. 3. Grasp the RTB with your thumb and forefinger and pull straight out. 4. Label the RTB with appropriate slot, chassis, and module identification. Terminal Block Release Screw

Terminal Block Release Screw

Dot indicates Terminal Number 0 (or top of I/O wiring).

Publication 1747-UM011G-EN-P - June 2008

Page 120

120

Wiring Your I/O Modules

Install the RTB Below are guidelines for installing the RTB. 1. Be sure the color of the RTB matches the color band on the module. ATTENTION

Inserting a wired RTB on an incorrect module can damage the module circuitry when power is applied.

2. Write the appropriate slot, chassis, and module type on the RTB label. ATTENTION

Disconnect power before attempting to install or remove I/O modules or their terminal blocks.

3. Disconnect power. 4. Align the terminal block release screws with the mating connector in the module. 5. Press the RTB firmly onto the connector contacts. 6. Tighten the terminal block release screws. To avoid cracking the terminal block, alternate the tightening of the screws.

Terminal Block Release Screws Maximum Torque: 0.9 Nm (8 lb-in)