Page 111
Chapter
7
Wiring Your I/O Modules
This chapter describes how to wire your I/O modules. It covers the following: • Defining sinking and sourcing • Preparing your wiring layout • Features of an I/O module • Recommendations for wiring I/O devices • Wiring your I/O modules • Octal label kit installation • Using removable terminal blocks
Defining Sinking and Sourcing
Sinking and sourcing are terms used to describe a current signal flow relationship between field input and output devices in a control system and their power supply. • Field devices connected to the positive side (+V) of the field power supply are sourcing field devices. • Field devices connected to the negative side (dc Common) of the field power supply are called sinking field devices. To maintain electrical compatibility between field devices and the programmable controller system, this definition is extended to the input/output circuits on the discrete I/O modules. • Sourcing I/O circuits supply (source) current to sinking field devices. • Sinking I/O circuits receive (sink) current from sourcing field devices. Europe: dc sinking input and sourcing output module circuits are the commonly used options.
111
Publication 1747-UM011G-EN-P - June 2008
Page 112
112
Wiring Your I/O Modules
Contact Output Circuits, ac or dc Relays can be used for either ac or dc output circuits and accommodate either sinking or sourcing field devices. These capabilities are a result of the output switch being a mechanical contact closure, not sensitive to current flow direction and capable of accommodating a broad range of voltages. This high degree of application flexibility makes contact output modules very popular and useful in control environments with a broad mix of electrical I/O circuit requirements.
Solid-State dc I/O Circuits The design of dc field devices typically requires that they be used in a specific sinking or sourcing circuit depending on the internal circuitry of the device. DC input and output field circuits are commonly used with field devices that have some form of internal solid state circuitry that need a dc signal voltage to function.
Sourcing Device with Sinking Input Module Circuit The field device is on the positive side of the power supply between the supply and the input terminal. When the field device is activated, it sources current to the input circuit. Field Device
I
Input dc Input Circuit
+ dc Power Supply _
Publication 1747-UM011G-EN-P - June 2008 dc Com
Page 113
Wiring Your I/O Modules
113
Sinking Device with Sourcing Input Module Circuit The field device is on the negative side of the power supply between the supply and the input terminal. When the field device is activated, it sinks current from the input circuit. Field Device
Input
I dc Input Circuit
_ dc Power Supply +
Vdc
Sinking Device with Sourcing Output Module Circuit The field device is on the negative side of the power supply between the supply and the output terminal. When the output is activated, it sources current to the field device. Vdc
+
Field Device dc Power Supply
I Out dc Output Circuit
_ dc Com
Sourcing Device with Sinking Output Module Circuit The field device is on the positive side of the power supply between the supply and the output terminal. When the output is activated, it sinks current from the field device.
+ dc Power Supply
Field Device
Vdc I Out dc Output Circuit
_ dc Com
Publication 1747-UM011G-EN-P - June 2008
Page 114
114
Wiring Your I/O Modules
Preparing Your Wiring Layout
Careful wire routing within the enclosure helps to cut down electrical noise between I/O lines. Follow these rules for routing your wires. • Route incoming power to the controller by a separate path from wiring to I/O devices. Where paths must cross, their intersection should be perpendicular. IMPORTANT
Do not run signal or communication wiring and power wiring in the same conduit.
• If wiring ducts are used, allow for at least 50.8 mm (2 in.) between I/O wiring ducts and the controller. If the terminal strips are used for I/O wiring, allow for at least two inches between the terminal strips and the controller. • Limit the cable length for the TTL input module to 15.24 m (50 ft) per point and 3.05 m (10 ft) per point for the TTL output module. Use low power dc I/O wiring even though it is less tolerant to electrical noise. ATTENTION
Handle the TTL module by its ends, not metallic surfaces. Electrostatic discharges can damage the module. Do not expose the TTL module to electrostatic charges.
• Segregate I/O wiring by signal type. Bundle wiring with similar electrical characteristics together. Wires with different signal characteristics should be routed into the enclosure by separate paths. Refer to Allen-Bradley Programmable Controller Grounding and Wiring Guidelines, publication 1770-4.1. ATTENTION
Publication 1747-UM011G-EN-P - June 2008
If the controller is being installed within a potentially hazardous environment (that is, Class I, Division 2), all wiring must comply with the requirements stated in the National Electrical Code 501-4 (b).
Page 115
Wiring Your I/O Modules
Recommendations for Wiring I/O Devices
115
The following are general recommendations for wiring I/O devices. ATTENTION
Before you install and wire I/O devices, disconnect power from the controller and any other source to the I/O devices.
• Use acceptable wire gauge. The I/O wiring terminals are designed to accept two wires per terminal (maximum) of the following size wire: – Europe: 2 mm2 cross section or smaller – United States: 14 AWG or smaller stranded wires • See diagram on page 116 for maximum torque values for wiring terminal screws and terminal block screws. • Label wiring to I/O devices, power sources, and ground. Use tape, shrink-tubing, or other dependable means for labeling purposes. In addition to labeling, use colored insulation to identify wiring based on signal characteristics. For example, you may use blue for dc I/O wiring and red for ac I/O wiring. • Route the wires down and away from the module, securing them with the cable tie. • Bundle wiring for each similar I/O device together. If you use ducts, allow at least 5 cm (2 in.) between the ducts and the controller so there is sufficient room to wire the devices. • Terminal cover plates have a write-on area for each terminal. Use this area to identify your I/O devices. Label the removable terminal block if you have not already. ATTENTION
Calculate the maximum possible current in each power and common wire. Observe all local electrical codes dictating the maximum current allowable for each wire size. Current above the maximum ratings may cause wiring to overheat, which can cause damage. Capacitors on input modules have a stored charge that can cause a non-lethal shock. Avoid mounting the controller in a position where installation or service personnel would be in danger from startle reaction.
Publication 1747-UM011G-EN-P - June 2008
Page 116
116
Wiring Your I/O Modules
Features of an I/O Module
Below is an example of a combination I/O module.
OUTPUT
Color Band
INPUT
0
4
0
4
1
5
1
5
2
2
3
3
I/O Status Indicators Terminal Block Screw (maximum torque: 0.6 Nm (5.3 lb-in))
Input and Output Terminals Connected to Terminal Block
Terminal Block (may be color-coded and removable on some modules)
Hinged Wiring Terminal Door with Label
Terminal Wiring • 2 wires per terminal maximum • #14 AWG (2mm2) maximum • Maximum torque: 0.9 Nm (8 lb-in) Terminal Block Screw (maximum torque: 0.6 Nm (5.3 lb-in))
Tie Wire Wires Leading to Input and Output Devices
Wiring Your I/O Module
Terminals on the modules have self-lifting pressure plates that accept two 2 mm2 (14 AWG) wires. Series B 12-point and 16-point and analog modules are equipped with removable terminal blocks for ease of wiring. The plug for the removable terminals is also color coded: • red (ac) • blue (dc) • orange (relay) • green (specialty). Status indicators on the front of each module display the status of each I/O point. The status indicators illuminate when the proper signal to an input terminal is applied or when the processor commands an output to be energized. To locate the I/O module wiring diagrams, contact your Rockwell Automation sales office for the latest selection guide, publication 1747-SG001. Or, locate the installation instruction sheet that was sent with your I/O module. It also includes I/O wiring diagrams.
Publication 1747-UM011G-EN-P - June 2008
Page 117
Wiring Your I/O Modules
117
1. Install a tie wire to secure your wiring and keep it neat. (If you feed the tie into one hole, it is routed back out through the other.) 2. Cover any unused slots with card slot fillers (catalog number 1746-N2) to keep the chassis free from debris and dust.
Octal Label Kit Installation
The octal label kit consists of an octal filter label and a door label. Use these octal labels to replace the decimal labels that are attached to the I/O modules. The kits can be obtained through your Allen-Bradley distributor. (The octal label kit is applicable when using 1746 I/O with PLC-5 processors via a 1747-ASB Remote I/O Adapter.)
Apply the Octal Filter Label 1. Remove the octal filter label from its paper carrier. 2. Align the octal filter label numbers horizontally to the module color bar and over the decimal filter numbers, as shown in the illustration below. 3. Apply the octal label to the filter. 4. Press firmly to ensure proper adhesion of the label.
Apply the Octal Door Label 1. Remove the octal door label from its paper carrier. 2. Align it over the decimal door label on the inside of the door. 3. Press firmly to ensure proper adhesion of the label.
Publication 1747-UM011G-EN-P - June 2008
Page 118
118
Wiring Your I/O Modules
Decimal Filter Label
Module Color Bar
Octal Filter Label
Octal Door Label
Decimal Door Label
Octal Kit and I/O Module Information
Publication 1747-UM011G-EN-P - June 2008
I/O Module Cat. No.
Octal Kit Cat. No.
I/O Module Cat. No.
Octal Kit Cat. No.
1746-IA16
1746-RL40
1746-OV16
1746-RL53
1746-IB16
1746-RL41
1746-OW16
1746-RL54
1746-IG16
1746-RL42
1746-OBP16
1746-RL55
1746-IM16
1746-RL43
1746-OVP16
1746-RL56
1746-IN16
1746-RL44
1746-OAP12
1746-RL57
1746-IV16
1746-RL45
1746-IC16
1746-RL58
1746-ITB16
1746-RL46
1746-IH16
1746-RL59
1746-ITV16
1746-RL47
1746-IB32
1746-RL60
1746-OA16
1746-RL50
1746-IV32
1746-RL61
1746-OB16
1746-RL51
1746-OB32 1746-OB32E
1746-RL70
1746-OG16
1746-RL52
1746-OV32
1746-RL71
1746-OB16E
1746-RL72
Page 119
Wiring Your I/O Modules
Using the Removable Terminal Block (RTB)
119
The Removable Terminal Block (RTB) is provided on all 12-point and 16-point discrete I/O modules and analog modules. They allow for faster and more convenient wiring of the I/O modules. The modules and the RTB are color-coded. Color
Type of I/O Removable Terminal Block
Red ac inputs/outputs
Blue dc inputs/outputs
Orange relay outputs
Green specialty modules
Replacement terminal blocks are available if they are lost or damaged. See the replacement part list in chapter 11.
Remove the RTB Below are guidelines for removing the I/O Removable Terminal Block. ATTENTION
Never install or remove I/O modules or terminal blocks while the SLC chassis is powered.
1. If the I/O module is already installed in the chassis, remove power to the SLC chassis. 2. Unscrew the upper right and lower left terminal block release screws. 3. Grasp the RTB with your thumb and forefinger and pull straight out. 4. Label the RTB with appropriate slot, chassis, and module identification. Terminal Block Release Screw
Terminal Block Release Screw
Dot indicates Terminal Number 0 (or top of I/O wiring).
Publication 1747-UM011G-EN-P - June 2008
Page 120
120
Wiring Your I/O Modules
Install the RTB Below are guidelines for installing the RTB. 1. Be sure the color of the RTB matches the color band on the module. ATTENTION
Inserting a wired RTB on an incorrect module can damage the module circuitry when power is applied.
2. Write the appropriate slot, chassis, and module type on the RTB label. ATTENTION
Disconnect power before attempting to install or remove I/O modules or their terminal blocks.
3. Disconnect power. 4. Align the terminal block release screws with the mating connector in the module. 5. Press the RTB firmly onto the connector contacts. 6. Tighten the terminal block release screws. To avoid cracking the terminal block, alternate the tightening of the screws.
Terminal Block Release Screws Maximum Torque: 0.9 Nm (8 lb-in)
Publication 1747-UM011G-EN-P - June 2008