SLC 500 Modular Hardware Style User Manual, pages 71 to 80

Pages 71 to 80 of 296

The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L524

Page 71

System Installation Recommendations

71

SLC 500 Operation with 24V dc User Power Overcurrent Condition

Power Supply Cat. No.

SLC Operation

Recovery Procedure

1746-P1 series A (made in Japan)

power supply shutdown, CPU fault

Reload user program

1746-P1 series A (made in Malaysia current production)

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P2 series A and B power supply shutdown, CPU fault

Reload user program

1746-P2 series C

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P4 series A power supply shutdown, CPU fault

Reload user program

1746-P5 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

1746-P6 series A

24V dc user shutdown, CPU continues

Correct overcurrent condition

ATTENTION

For 1746-P1 (made in Malaysia), 1746-P2 series C, 1746-P5 series A, and 1746-P6 series A power supply, to avoid unexpected operation due to 24V dc user power shutdown, monitor the 24V dc user output with a 24V dc input channel.

Publication 1747-UM011G-EN-P - June 2008

Page 72

72

System Installation Recommendations

Safety Considerations

Safety considerations are an important element of proper system installation. Actively thinking about the safety of yourself and others, as well as the condition of your equipment, is of primary importance.

Disconnecting Main Power Locate the main power disconnect switch where operators and maintenance personnel have quick and easy access to it. Ideally, the disconnect switch is mounted on the outside of the enclosure, so that it can be accessed without opening the enclosure. In addition to disconnecting electrical power, de-energize all other sources of power (pneumatic and hydraulic) before working on a machine or process controlled by an SLC controller.

Safety Circuits Circuits installed on the machine for safety reasons, like overtravel limit switches, stop push buttons, and interlocks, should always be hard-wired directly to the master control relay. These devices must be wired in series so that when any one device opens, the master control relay is de-energized thereby removing power to the machine. Never alter these circuits to defeat their function. Serious injury or machine damage could result.

Power Distribution There are some points about power distribution that you should be aware of. First, the master control relay must be able to inhibit all machine motion by removing power to the machine I/O devices when the relay is de-energized. Second, if you are using a dc power supply, interrupt the load side rather than the ac line power. This avoids the additional delay of power supply turn-on and turn-off. The dc power supply should be powered directly from the fused secondary of the transformer. Power to the dc input and output circuits is connected through a set of master control relay contacts.

Periodic Tests of Master Control Relay Circuit Any part can fail, including the switches in a master control relay circuit. The failure of one of these switches would most likely cause an open circuit, which would be a safe power-off failure. However, if one of these switches shorts

Publication 1747-UM011G-EN-P - June 2008

Page 73

System Installation Recommendations

73 out, it no longer provides any safety protection. These switches should be tested periodically to assure they will stop machine motion when needed.

Preventive Maintenance

The printed circuit boards of the controller must be protected from dirt, oil, moisture and other airborne contaminants. To protect these boards, the controller must be installed in an enclosure suitable for the environment. The interior of the enclosure should be kept clean and the enclosure door should be kept closed whenever possible. Regularly inspect your terminal connections for tightness. Loose connections may cause improper functioning of the controller or damage the components of the system. ATTENTION

To ensure personal safety and to guard against damaging equipment, inspect connections with incoming power off.

The National Fire Protection Association (NFPA) provides recommendations for electrical equipment maintenance. Refer to article 70B of the NFPA for general requirements regarding safety related work practices.

Publication 1747-UM011G-EN-P - June 2008

Page 74

74

System Installation Recommendations

Notes:

Publication 1747-UM011G-EN-P - June 2008

Page 75

Chapter

4

Mounting Your SLC 500 Control System This chapter provides mounting dimensions for: • 4, 7, 10, and 13-slot chassis. • link coupler (AIC). • Data Terminal Access Module (DTAM). • DTAM Plus Operator Interface. • DTAM Micro Operator Interface. • AIC+ Advanced Interface Converter. • DNI DeviceNet Network Interface. • ENI EtherNet Network Interface.

You can mount the modular hardware style units directly to the back panel of your enclosure using the mounting tabs and #10 or #12 screws. The torque requirement is 3.4 Nm (30 lb-in) maximum.

Mounting Modular Hardware Style Units

4-slot Modular Chassis 11 Dia. (0.433)

(3)

70 (2.76)

1.0 (0.04)

5.5 Dia. (0.217)

(2) (1)

158 (6.22)

140 171 (5.51) (6.73)

171 (6.73)

140 (5.51)

14 (0.55) 5.5 Dia (0.217)

215 (8.46) 235 (9.25) 261 (10.28)

45 (1.77)

145 (5.71)

millimeters (inches)

Front View

Left Side View (1) Dimensions for 1746-P1 power supply. (2) Dimensions for 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies. (3) Dimensions for 1746-P4 power supply.

75

Publication 1747-UM011G-EN-P - June 2008

Page 76

76

Mounting Your SLC 500 Control System

7-slot Modular Chassis 11 Dia. (0.433)

(3)

. Dia. (0.217)

175 (6.89)

1.0 (0.04)

(2) (1)

140 (5.51)

158 (6.22)

140 (5.51) 171 (6.73) 171 (6.73)

14 (0.55) 45 (1.77)

5.5 Dia (0.217)

145 (5.71)

320 (12.60) 340 (13.39)

Front View

366 (14.41)

millimeters (inches)

Left Side View

10-slot Modular Chassis

11 Dia. (0.433)

(3)

5.5 Dia. (0.217)

140 (5.51)

1.0 (0.04)

55 (2.17)

(2) (1) 140 (5.51) 140 171 (5.51) (6.73)

158 (6.22)

14 (0.55) 5.5 Dia (0.217)

140 (5.51)

145 (5.71)

435 (17.13) 455 (17.91) 481 (18.94)

Front View millimeters (inches)

(1) Dimensions for 1746-P1 power supply. (2) Dimensions for 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies. (3) Dimensions for 1746-P4 power supply.

Publication 1747-UM011G-EN-P - June 2008

Left Side View

Page 77

Mounting Your SLC 500 Control System

77

13-slot Modular Chassis 11 Dia. (0.433)

(3)

5.5 Dia. (0.217)

105 (4.13)

55 (2.17)

140 (5.51)

(2) (1)

158 (6.22)

140 (5.51)

5.5 Dia (0.217)

171 (6.73)

14 (0.55)

140 (5.51) 540 (21.26) 560 (22.05)

586 (23.07)

1.0 (0.04)

Front View millimeters (inches)

171 (6.73)

140 (5.51)

145 (5.71)

Left Side View (1) Dimensions for 1746-P1 power supply. (2) Dimensions for 1746-P2, 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies. (3) Dimensions for 1746-P4 power supply.

Publication 1747-UM011G-EN-P - June 2008

Page 78

78

Mounting Your SLC 500 Control System

Link Coupler (AIC) R 2.74 (0.11)

146 (5.75)

R 5.5 (0.22)

172 (6.75) 159 (6.24)

137 (5.41)

14 (0.55) 7.1 (0.28)

38 (1.50)

Front View

Publication 1747-UM011G-EN-P - June 2008

5.5 Dia. (0.216)

millimeters (inches)

4.3 (0.17)

Right Side View

Page 79

Mounting Your SLC 500 Control System

79

Data Table Access Module (DTAM, DTAM Plus, and DTAM Micro) C

A

D

B Front View

Data Table Access Module

Right Side View

Dimensions in millimeters (inches) A

B

C

D

DTAM

152 (6.0)

140 (5.5)

69 (2.76)

127 (5.0)

DTAM Plus

215.9 (8.5)

165.1 (6.5)

45.7 (1.8)

193 (7.6)

DTAM Micro

137.2 (5.4

175.3 (6.9)

45.7 (1.8)

99.1 (3.9)

Publication 1747-UM011G-EN-P - June 2008

Page 80

80

Mounting Your SLC 500 Control System

AIC+ Advanced Interface Converter (1761-NET-AIC) DeviceNet Interface (1761-NET-DNI) Ethernet Interface (1761-NET-ENI) 52.07 mm (2.05 in.)

118 mm (4.64 in.)

107 mm (4.20 in.) 6.6 mm (0.26 in.)

Allow 15 mm (0.6 in.) clearance for DIN rail latch movement during installation and removal.

Publication 1747-UM011G-EN-P - June 2008

27.7 mm (1.09 in.)

71.4 mm (2.81 in.)