Page 261
Appendix
H
Calculating Heat Dissipation for the SLC 500 Control System
This appendix will assist you in calculating the heat dissipation of your SLC 500 controller. It consists of: • a definition of key term. • a table and graph. • an example heat dissipation calculation. • a heat dissipation worksheet. To select an enclosure see page 40.
Definition of Key Terms
We use these terms throughout this appendix. Familiarize yourself with them before proceeding further. Watts per Point - maximum heat dissipation that can occur in each field wiring point when energized. Minimum Watts - amount of heat dissipation that can occur when there is no field power present. Total Watts - the watts per point plus the minimum watts (with all points energized).
Calculating Module Heat Dissipation
To calculate the heat dissipation of your SLC controller you must consider: • the maximum heat dissipated (with field power applied) by the processor, all I/O and specialty modules, and any peripheral devices for each chassis. • the heat dissipated by the power supply. This is determined by the maximum load on the power supply of the processor, each I/O and specialty module, peripheral device, and device drawing power directly off the power supply via the POWER OUT terminals.
261
Publication 1747-UM011G-EN-P - June 2008
Page 262
262
Calculating Heat Dissipation for the SLC 500 Control System
Calculated Watts vs. Total Watts You calculate maximum heat dissipation by using one of these methods. • Calculated watts method • Total watts method Use calculated watts if you know exactly how many outputs and inputs on each card are active at any given time. This method will give you a lower, more accurate heat dissipation calculation than the total watts method. With this method, use the formula below for calculating the heat dissipation of each module. Then use these values in step 1 of the Example Worksheet for Calculating Heat Dissipation on page 268. (points energized x watts per point) + minimum watts = heat dissipation of module Use total watts if you are not sure how many points on a module are energized at any time. Total watts is the watts per point (with all points energized) plus the minimum watts. Total watts generated by each module are provided in the table on page 263. Once you have determined which method you will use to calculate the heat dissipation of your modules, see the Example Worksheet for Calculating Heat Dissipation on page 268. This worksheet shows you how to calculate the heat dissipation for the example SLC control system on page 267.
Publication 1747-UM011G-EN-P - June 2008
Page 263
Calculating Heat Dissipation for the SLC 500 Control System
263
Power Supply Loading Reference Table Use the table to calculate the power supply loading and heat dissipation for each chassis in your SLC modular application.
Hardware Component
Cat. No.
Watts per Point
Minimum Watts
Total Watts
Processors
1747-L511
NA
1.75
1.75
1747-L514
NA
1.75
1.75
1747-L524
NA
1.75
1.75
1747-L531
NA
2.90
2.90
1747-L532
NA
2.90
2.90
1747-L533
NA
2.90
2.90
1747-L541
NA
4.00
4.00
1747-L542
NA
4.00
4.00
1747-L543
NA
4.00
4.00
1747-L551
NA
4.00
4.00
1747-L552
NA
4.00
4.00
Digital Input Modules
1747-L553
NA
4.00
4.00
1746-IA4
0.270
0.175
1.30
1746-IA8
0.270
0.250
2.40
1746-IA16
0.270
0.425
4.80
1746-IB8
0.200
0.250
1.90
1746-IB16
0.200
0.425
3.60
1746-IB32(1)
0.200
0.530
6.90
1746-IC16
0.220
0.425
3.95
1746-IG16
0.020
0.700
1.00
1746-IH16
0.320
0.217
5.17
1746-IM4
0.350
0.175
1.60
1746-IM8
0.350
0.250
3.10
1746-IM16
0.350
0.425
6.00
1746-IN16
0.350
0.425
6.00
1746-ITB16
0.200
0.425
3.625
1746-ITV16
0.200
0.425
3.625
1746-IV8
0.200
0.250
1.90
1746-IV16
0.200
0.425
3.60
1746-IV32(1)
0.200
0.530
6.90
Publication 1747-UM011G-EN-P - June 2008
Page 264
264
Calculating Heat Dissipation for the SLC 500 Control System
Hardware Component
Cat. No.
Watts per Point
Minimum Watts
Total Watts
Digital Output Modules
1746-OA8
1.000
0.925
9.00
1746-OA16
0.462
1.850
9.30
1746-OAP12
1.000
1.850
10.85
1746-OB6EI
0.440
0.230
2.90
1746-OB8
0.775
0.675
6.90
1746-OB16
0.150
0.675
3.07
1746-OB16E
0.338
1.400
7.60
1746-OB32(1)
0.078
2.260
4.80
1746-OB32E
0.078
2.260
4.80
1746-OBP8
0.300
0.675
3.08
1746-OBP16
0.310
1.250
6.21
1746-OG16
0.033
0.900
1.50
1746-OV8
0.775
0.675
6.90
1746-OV16
0.388
1.400
7.60
1746-OV32(1)
0.078
2.260
4.80
1746-OVP16
0.310
1.250
6.21
1746-OW4
0.133
1.310
1.90
1746-OW8
0.138
2.590
3.70
1746-OW16
0.033
5.170
5.70
1746-OX8
0.825
2.590
8.60
1746-IO4
0.270 per input pt. 0.133 per output pt.
0.750
1.60
1746-IO8
0.270 per input pt. 0.133 per output pt.
1.380
3.00
1746-IO12
0.270 per input pt. 0.133 per output pt.
2.130
4.60
1746-IO12DC
0.200 per input pt. 0.133 per output pt.
1.840
3.90
1746-NI4
NA
2.170
2.20
1746-NI8
NA
3.4
3.4
1746-NI16I
NA
2.43
2.43
1746-NI16V
NA
3.760
3.80
1746-NO4I
NA
4.960
5.00
1746-NO4V
NA
3.780
3.80
1746-NO8I
NA
2.44
6.6
1746-NO8V
NA
1.98
4.44
1746-FIO4I
NA
3.760
3.800
1746-FIO4V
NA
3.040
3.100
1746-NIO4I
NA
3.760
3.80
1746-NIO4V
NA
3.040
3.10
Digital Combination Modules
Analog Input Modules
Analog Output Modules
Analog Combination Modules
Publication 1747-UM011G-EN-P - June 2008
Page 265
Calculating Heat Dissipation for the SLC 500 Control System
265
Hardware Component
Cat. No.
Watts per Point
Minimum Watts
Total Watts
Specialty Modules
1746-BAS
NA
3.750
3.800
1746-BLM
NA
5.00
5.00
1746-BTM
NA
2.59
2.59
1746-HSCE
NA
1.600
1.600
1746-HSCE2
NA
1.25
1.25
1746-HSRV
NA
1.50
1.50
1746-HSTP1
NA
1.50
1.50
1746-INT4
NA
1.26
1.26
1746-NR4
NA
1.500
1.500
1746-NR8
NA
1.82
1.82
1746-NT4
NA
0.800
0.800
1746-NT8
NA
2.28
2.28
1746-QS
NA
9.80
9.80
Communication Modules
Peripheral Devices
1746-QV
NA
1.075
1.075
1747-ACN15
NA
4.5
4.5
1747-ACNR15
NA
4.5
4.5
1747-ASB
NA
1.875
1.875
1747-BSN
NA
4.0
4.0
1747-DCM
NA
1.800
1.800
1747-KE
NA
3.750
3.800
1747-KFC15
NA
3.200
3.200
1747-SCNR
NA
4.5
4.5
1747-SDN
NA
2.5
2.5
1747-SN
NA
4.500
4.500
1747-AIC
NA
2.000
2.000
1747-DTAM
NA
2.500
2.500
1747-PIC
NA
2.000
2.000
NA
NA
NA
NA
2.500
2.500
1761-NET-DNI
NA
2.500
2.500
1761-NET-ENI(W)(2)
NA
2.000
2.000
1747-PSD 1761-NET-AIC
(2)
(1)
Power supply loading for Series D and later modules.
(2)
Current for the 1761-NET-AIC and 1761-NET-ENI may be supplied from the SLC power supply or from an external 24V dc source.
Publication 1747-UM011G-EN-P - June 2008
Page 266
266
Calculating Heat Dissipation for the SLC 500 Control System
Power Supply Heat Dissipation Graphs
1746-P1 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0 5 10 15 20 25 Power Supply Loading (Watts)
Power Supply Dissipation (Watts)
Power Supply Dissipation (Watts)
Use the graphs below for determining the power supply dissipation in step 2 of the Example Worksheet for Calculating Heat Dissipation.
25 20 15 10 5 0
1746-P4 Power Supply Change in Power Dissipation due to Output Loading Power Supply Dissipation (Watts)
Power Supply Dissipation (Watts)
1746-P3 Power Supply Change in Power Dissipation due to Output Loading
0 5 10 15 20 25 30 35 Power Supply Loading (Watts)
10
20
30
40
50
Power Supply Dissipation (Watts)
Power Supply Loading (Watts)
Publication 1747-UM011G-EN-P - June 2008
60
25 20 15 10 5 0
0 10 20 30 40 50 60 70 80 Power Supply Loading (Watts)
1746-P6 Power Supply Change in Power Dissipation due to Output Loading Power Supply Dissipation (Watts)
Power Supply Dissipation (Watts)
1746-P5 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0
1746-P2 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0 10 20 30 40 50 60 Power Supply Loading (Watts)
25 20 15 10 5 0
0 10 20 30 40 50 60 Power Supply Loading (Watts)
1746-P7 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0
24V input 12V input
0 20 40 60 80 100 Power Supply Loading (Watts)
Page 267
Calculating Heat Dissipation for the SLC 500 Control System
Example Heat Dissipation Calculation
267
If your controller consisted of the following hardware components, you would calculate heat dissipation as shown in the worksheet on page 268.
DTAM
Chassis 1
Chassis 2
Peripheral Device
Slot
0
1
2
Slot
3
4
5
6
7 User Power to Peripheral
The following table details the total watts dissipated by the modules and peripheral devices in the above SLC 500 controller. The numbers were taken from the tables on page 263. Chassis 1
Chassis 2
Slot Number
Cat. No.
Min Watts
Max Watts
Slot Number
Cat. No.
Min Watts
Max Watts
0
1747-L511
1.75
1.75
4
1746-IA16
0.425
4.800
1
1746-BAS
3.750
3.80
5
1746-IA16
0.425
4.800
2
1746-IA8
0.250
2.40
6
1746-OW16
5.170
5.500(2)
3
1746-OV8
0.675
6.90
7
1746-OW16
5.170
5.700
Peripheral Device
1747-DTAM
2.500
2.50
NA
NA
NA
NA
User Power to Peripheral
NA
NA
NA
NA
NA
2.400(1)
NA
(1)
The user power on the 1746-P1 power supply for chassis 2 is being used to power a peripheral (100 mA at 24V dc).
(2)
This output card uses 5.5 W because only 10 points are on at any one time. Using the calculated watts formula - (number of points energized x watts per point) + minimum watts = heat dissipation of module - the calculated watts for the 1746-OW16 module is 5.5 W: (10 points x.33) + 5.17 = 5.5 W.
Publication 1747-UM011G-EN-P - June 2008
Page 268
Calculating Heat Dissipation for the SLC 500 Control System
268
Example Worksheet Procedure for calculating the total heat dissipation for the controller 1. Write in the total watts dissipated by the processor, I/O, and speciality modules, and any peripheral devices attached to the processor.
Chassis Number 1 Slot
Chassis Number 2
Cat. No.
Heat Dis Slot (Watts)
Chassis Number 3
Cat. No.
Heat Dis Slot (Watts)
0
1747-L511
1.75
4
1746-IA16
4.8
1
1746-BAS
3.8
5
1746-IA16
4.8
2
1746-IA8
2.4
6
1746-OW16
5.5
3
1746-OV8
6.9
7
1746-OW16
5.7
Peripheral Dev
1747-DTAM
2.5
Peripheral Dev
Peripheral Dev
Peripheral Dev
Peripheral Dev
Peripheral Dev 2.Add the heat dissipation values together for your total chassis heat dissipation.
17.35
2.Add the heat dissipation values together for your total chassis heat dissipation.
20.8
Cat. No.
Heat Dis (Watts)
2.Add the heat dissipation values together for your total chassis heat dissipation.
3.Calculate the power supply loading for each chassis (minimum watts) for each device.(1) Chassis Number 1 Slot
Chassis Number 2
Cat. No.
Heat Dis Slot (Watts) 1.75
0
1747-L511
1
1746-BAS
3.75
2
1746-IA8
0.25
3
1746-OV8
0.675
7
User Power Peripheral Dev
Chassis Number 3
Cat. No. 4
Heat Dis Slot (Watts)
1746-IA16
0.425
5
1746-IA16
0.425
6
1746-OW16
5.17
1746-OW16
5.17
User Power
2.4
Cat. No.
Heat Dis (Watts)
User Power
1747-DTAM
2.5
Peripheral Dev
4.Add the heat dissipation values together for your power supply loading.
8.925
4.Add the heat dissipation values together for your power supply loading.
13.59
Peripheral Dev 4.Add the heat dissipation values together for your power supply loading.
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
13.0
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
15.0
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
30.35
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
35.8
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
7.Add the values together from step 6 across to the right.
66.15
8.Covert the value from step 7 to BTUs/hr by multiplying the total heat dissipation of your controller by 3.414.
225.84
(1)
If you have a device connected to user power, multiply 24V dc by the amount of current used by that device. Include user power in the total power supply loading.
Publication 1747-UM011G-EN-P - June 2008
Page 269
Calculating Heat Dissipation for the SLC 500 Control System
269
Blank Worksheet Procedure for calculating the total heat dissipation for the controller 1. Write in the total watts dissipated by the processor, I/O, and speciality modules, and any peripheral devices attached to the processor.
Chassis Number 1 Slot
Catalog No.
Chassis Number 2 Heat Dis Slot (Watts)
Catalog No.
Chassis Number 3 Heat Dis Slot (Watts)
Catalog No.
Peripheral Dev
Peripheral Dev
Peripheral Dev
Peripheral Dev
Peripheral Dev
Peripheral Dev
2.Add the heat dissipation values together for your total chassis heat dissipation.
2.Add the heat dissipation values together for your total chassis heat dissipation.
2.Add the heat dissipation values together for your total chassis heat dissipation.
Heat Dis (Watts)
3.Calculate the power supply loading for each chassis (minimum watts) for each device.(1) Chassis Number 1 Slot
Catalog No.
Chassis Number 2 Heat Dis Slot (Watts)
Catalog No.
Chassis Number 3 Heat Dis Slot (Watts)
Catalog No.
User Power
User Power
User Power
Peripheral Dev
Peripheral Dev
Peripheral Dev
4.Add the heat dissipation values together for your power supply loading.
4.Add the heat dissipation values together for your power supply loading.
4.Add the heat dissipation values together for your power supply loading.
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).
Heat Dis (Watts)
7.Add the values together from step 6 across to the right. 8.Covert the value from step 7 to BTUs/hr by multiplying the total heat dissipation of your controller by 3.414. (1)
If you have a device connected to user power, multiply 24V dc by the amount of current used by that device. Include user power in the total power supply loading.
Publication 1747-UM011G-EN-P - June 2008
Page 270
270
Calculating Heat Dissipation for the SLC 500 Control System
Notes:
Publication 1747-UM011G-EN-P - June 2008