Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 27 of 30

SLC 500 Modular Hardware Style User Manual, pages 261 to 270

Pages 261 to 270 of 296

The original document is the PDF (3.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L524

Page 261

Appendix

H

Calculating Heat Dissipation for the SLC 500 Control System

This appendix will assist you in calculating the heat dissipation of your SLC 500 controller. It consists of: • a definition of key term. • a table and graph. • an example heat dissipation calculation. • a heat dissipation worksheet. To select an enclosure see page 40.

Definition of Key Terms

We use these terms throughout this appendix. Familiarize yourself with them before proceeding further. Watts per Point - maximum heat dissipation that can occur in each field wiring point when energized. Minimum Watts - amount of heat dissipation that can occur when there is no field power present. Total Watts - the watts per point plus the minimum watts (with all points energized).

Calculating Module Heat Dissipation

To calculate the heat dissipation of your SLC controller you must consider: • the maximum heat dissipated (with field power applied) by the processor, all I/O and specialty modules, and any peripheral devices for each chassis. • the heat dissipated by the power supply. This is determined by the maximum load on the power supply of the processor, each I/O and specialty module, peripheral device, and device drawing power directly off the power supply via the POWER OUT terminals.

261

Publication 1747-UM011G-EN-P - June 2008

Page 262

262

Calculating Heat Dissipation for the SLC 500 Control System

Calculated Watts vs. Total Watts You calculate maximum heat dissipation by using one of these methods. • Calculated watts method • Total watts method Use calculated watts if you know exactly how many outputs and inputs on each card are active at any given time. This method will give you a lower, more accurate heat dissipation calculation than the total watts method. With this method, use the formula below for calculating the heat dissipation of each module. Then use these values in step 1 of the Example Worksheet for Calculating Heat Dissipation on page 268. (points energized x watts per point) + minimum watts = heat dissipation of module Use total watts if you are not sure how many points on a module are energized at any time. Total watts is the watts per point (with all points energized) plus the minimum watts. Total watts generated by each module are provided in the table on page 263. Once you have determined which method you will use to calculate the heat dissipation of your modules, see the Example Worksheet for Calculating Heat Dissipation on page 268. This worksheet shows you how to calculate the heat dissipation for the example SLC control system on page 267.

Publication 1747-UM011G-EN-P - June 2008

Page 263

Calculating Heat Dissipation for the SLC 500 Control System

263

Power Supply Loading Reference Table Use the table to calculate the power supply loading and heat dissipation for each chassis in your SLC modular application.

Hardware Component

Cat. No.

Watts per Point

Minimum Watts

Total Watts

Processors

1747-L511

NA

1.75

1.75

1747-L514

NA

1.75

1.75

1747-L524

NA

1.75

1.75

1747-L531

NA

2.90

2.90

1747-L532

NA

2.90

2.90

1747-L533

NA

2.90

2.90

1747-L541

NA

4.00

4.00

1747-L542

NA

4.00

4.00

1747-L543

NA

4.00

4.00

1747-L551

NA

4.00

4.00

1747-L552

NA

4.00

4.00

Digital Input Modules

1747-L553

NA

4.00

4.00

1746-IA4

0.270

0.175

1.30

1746-IA8

0.270

0.250

2.40

1746-IA16

0.270

0.425

4.80

1746-IB8

0.200

0.250

1.90

1746-IB16

0.200

0.425

3.60

1746-IB32(1)

0.200

0.530

6.90

1746-IC16

0.220

0.425

3.95

1746-IG16

0.020

0.700

1.00

1746-IH16

0.320

0.217

5.17

1746-IM4

0.350

0.175

1.60

1746-IM8

0.350

0.250

3.10

1746-IM16

0.350

0.425

6.00

1746-IN16

0.350

0.425

6.00

1746-ITB16

0.200

0.425

3.625

1746-ITV16

0.200

0.425

3.625

1746-IV8

0.200

0.250

1.90

1746-IV16

0.200

0.425

3.60

1746-IV32(1)

0.200

0.530

6.90

Publication 1747-UM011G-EN-P - June 2008

Page 264

264

Calculating Heat Dissipation for the SLC 500 Control System

Hardware Component

Cat. No.

Watts per Point

Minimum Watts

Total Watts

Digital Output Modules

1746-OA8

1.000

0.925

9.00

1746-OA16

0.462

1.850

9.30

1746-OAP12

1.000

1.850

10.85

1746-OB6EI

0.440

0.230

2.90

1746-OB8

0.775

0.675

6.90

1746-OB16

0.150

0.675

3.07

1746-OB16E

0.338

1.400

7.60

1746-OB32(1)

0.078

2.260

4.80

1746-OB32E

0.078

2.260

4.80

1746-OBP8

0.300

0.675

3.08

1746-OBP16

0.310

1.250

6.21

1746-OG16

0.033

0.900

1.50

1746-OV8

0.775

0.675

6.90

1746-OV16

0.388

1.400

7.60

1746-OV32(1)

0.078

2.260

4.80

1746-OVP16

0.310

1.250

6.21

1746-OW4

0.133

1.310

1.90

1746-OW8

0.138

2.590

3.70

1746-OW16

0.033

5.170

5.70

1746-OX8

0.825

2.590

8.60

1746-IO4

0.270 per input pt. 0.133 per output pt.

0.750

1.60

1746-IO8

0.270 per input pt. 0.133 per output pt.

1.380

3.00

1746-IO12

0.270 per input pt. 0.133 per output pt.

2.130

4.60

1746-IO12DC

0.200 per input pt. 0.133 per output pt.

1.840

3.90

1746-NI4

NA

2.170

2.20

1746-NI8

NA

3.4

3.4

1746-NI16I

NA

2.43

2.43

1746-NI16V

NA

3.760

3.80

1746-NO4I

NA

4.960

5.00

1746-NO4V

NA

3.780

3.80

1746-NO8I

NA

2.44

6.6

1746-NO8V

NA

1.98

4.44

1746-FIO4I

NA

3.760

3.800

1746-FIO4V

NA

3.040

3.100

1746-NIO4I

NA

3.760

3.80

1746-NIO4V

NA

3.040

3.10

Digital Combination Modules

Analog Input Modules

Analog Output Modules

Analog Combination Modules

Publication 1747-UM011G-EN-P - June 2008

Page 265

Calculating Heat Dissipation for the SLC 500 Control System

265

Hardware Component

Cat. No.

Watts per Point

Minimum Watts

Total Watts

Specialty Modules

1746-BAS

NA

3.750

3.800

1746-BLM

NA

5.00

5.00

1746-BTM

NA

2.59

2.59

1746-HSCE

NA

1.600

1.600

1746-HSCE2

NA

1.25

1.25

1746-HSRV

NA

1.50

1.50

1746-HSTP1

NA

1.50

1.50

1746-INT4

NA

1.26

1.26

1746-NR4

NA

1.500

1.500

1746-NR8

NA

1.82

1.82

1746-NT4

NA

0.800

0.800

1746-NT8

NA

2.28

2.28

1746-QS

NA

9.80

9.80

Communication Modules

Peripheral Devices

1746-QV

NA

1.075

1.075

1747-ACN15

NA

4.5

4.5

1747-ACNR15

NA

4.5

4.5

1747-ASB

NA

1.875

1.875

1747-BSN

NA

4.0

4.0

1747-DCM

NA

1.800

1.800

1747-KE

NA

3.750

3.800

1747-KFC15

NA

3.200

3.200

1747-SCNR

NA

4.5

4.5

1747-SDN

NA

2.5

2.5

1747-SN

NA

4.500

4.500

1747-AIC

NA

2.000

2.000

1747-DTAM

NA

2.500

2.500

1747-PIC

NA

2.000

2.000

NA

NA

NA

NA

2.500

2.500

1761-NET-DNI

NA

2.500

2.500

1761-NET-ENI(W)(2)

NA

2.000

2.000

1747-PSD 1761-NET-AIC

(2)

(1)

Power supply loading for Series D and later modules.

(2)

Current for the 1761-NET-AIC and 1761-NET-ENI may be supplied from the SLC power supply or from an external 24V dc source.

Publication 1747-UM011G-EN-P - June 2008

Page 266

266

Calculating Heat Dissipation for the SLC 500 Control System

Power Supply Heat Dissipation Graphs

1746-P1 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0 5 10 15 20 25 Power Supply Loading (Watts)

Power Supply Dissipation (Watts)

Power Supply Dissipation (Watts)

Use the graphs below for determining the power supply dissipation in step 2 of the Example Worksheet for Calculating Heat Dissipation.

25 20 15 10 5 0

1746-P4 Power Supply Change in Power Dissipation due to Output Loading Power Supply Dissipation (Watts)

Power Supply Dissipation (Watts)

1746-P3 Power Supply Change in Power Dissipation due to Output Loading

0 5 10 15 20 25 30 35 Power Supply Loading (Watts)

10

20

30

40

50

Power Supply Dissipation (Watts)

Power Supply Loading (Watts)

Publication 1747-UM011G-EN-P - June 2008

60

25 20 15 10 5 0

0 10 20 30 40 50 60 70 80 Power Supply Loading (Watts)

1746-P6 Power Supply Change in Power Dissipation due to Output Loading Power Supply Dissipation (Watts)

Power Supply Dissipation (Watts)

1746-P5 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0

1746-P2 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0 0 10 20 30 40 50 60 Power Supply Loading (Watts)

25 20 15 10 5 0

0 10 20 30 40 50 60 Power Supply Loading (Watts)

1746-P7 Power Supply Change in Power Dissipation due to Output Loading 20 18 16 14 12 10 8 6 4 2 0

24V input 12V input

0 20 40 60 80 100 Power Supply Loading (Watts)

Page 267

Calculating Heat Dissipation for the SLC 500 Control System

Example Heat Dissipation Calculation

267

If your controller consisted of the following hardware components, you would calculate heat dissipation as shown in the worksheet on page 268.

DTAM

Chassis 1

Chassis 2

Peripheral Device

Slot

0

1

2

Slot

3

4

5

6

7 User Power to Peripheral

The following table details the total watts dissipated by the modules and peripheral devices in the above SLC 500 controller. The numbers were taken from the tables on page 263. Chassis 1

Chassis 2

Slot Number

Cat. No.

Min Watts

Max Watts

Slot Number

Cat. No.

Min Watts

Max Watts

0

1747-L511

1.75

1.75

4

1746-IA16

0.425

4.800

1

1746-BAS

3.750

3.80

5

1746-IA16

0.425

4.800

2

1746-IA8

0.250

2.40

6

1746-OW16

5.170

5.500(2)

3

1746-OV8

0.675

6.90

7

1746-OW16

5.170

5.700

Peripheral Device

1747-DTAM

2.500

2.50

NA

NA

NA

NA

User Power to Peripheral

NA

NA

NA

NA

NA

2.400(1)

NA

(1)

The user power on the 1746-P1 power supply for chassis 2 is being used to power a peripheral (100 mA at 24V dc).

(2)

This output card uses 5.5 W because only 10 points are on at any one time. Using the calculated watts formula - (number of points energized x watts per point) + minimum watts = heat dissipation of module - the calculated watts for the 1746-OW16 module is 5.5 W: (10 points x.33) + 5.17 = 5.5 W.

Publication 1747-UM011G-EN-P - June 2008

Page 268

Calculating Heat Dissipation for the SLC 500 Control System

268

Example Worksheet Procedure for calculating the total heat dissipation for the controller 1. Write in the total watts dissipated by the processor, I/O, and speciality modules, and any peripheral devices attached to the processor.

Chassis Number 1 Slot

Chassis Number 2

Cat. No.

Heat Dis Slot (Watts)

Chassis Number 3

Cat. No.

Heat Dis Slot (Watts)

0

1747-L511

1.75

4

1746-IA16

4.8

1

1746-BAS

3.8

5

1746-IA16

4.8

2

1746-IA8

2.4

6

1746-OW16

5.5

3

1746-OV8

6.9

7

1746-OW16

5.7

Peripheral Dev

1747-DTAM

2.5

Peripheral Dev

Peripheral Dev

Peripheral Dev

Peripheral Dev

Peripheral Dev 2.Add the heat dissipation values together for your total chassis heat dissipation.

17.35

2.Add the heat dissipation values together for your total chassis heat dissipation.

20.8

Cat. No.

Heat Dis (Watts)

2.Add the heat dissipation values together for your total chassis heat dissipation.

3.Calculate the power supply loading for each chassis (minimum watts) for each device.(1) Chassis Number 1 Slot

Chassis Number 2

Cat. No.

Heat Dis Slot (Watts) 1.75

0

1747-L511

1

1746-BAS

3.75

2

1746-IA8

0.25

3

1746-OV8

0.675

7

User Power Peripheral Dev

Chassis Number 3

Cat. No. 4

Heat Dis Slot (Watts)

1746-IA16

0.425

5

1746-IA16

0.425

6

1746-OW16

5.17

1746-OW16

5.17

User Power

2.4

Cat. No.

Heat Dis (Watts)

User Power

1747-DTAM

2.5

Peripheral Dev

4.Add the heat dissipation values together for your power supply loading.

8.925

4.Add the heat dissipation values together for your power supply loading.

13.59

Peripheral Dev 4.Add the heat dissipation values together for your power supply loading.

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

13.0

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

15.0

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

30.35

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

35.8

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

7.Add the values together from step 6 across to the right.

66.15

8.Covert the value from step 7 to BTUs/hr by multiplying the total heat dissipation of your controller by 3.414.

225.84

(1)

If you have a device connected to user power, multiply 24V dc by the amount of current used by that device. Include user power in the total power supply loading.

Publication 1747-UM011G-EN-P - June 2008

Page 269

Calculating Heat Dissipation for the SLC 500 Control System

269

Blank Worksheet Procedure for calculating the total heat dissipation for the controller 1. Write in the total watts dissipated by the processor, I/O, and speciality modules, and any peripheral devices attached to the processor.

Chassis Number 1 Slot

Catalog No.

Chassis Number 2 Heat Dis Slot (Watts)

Catalog No.

Chassis Number 3 Heat Dis Slot (Watts)

Catalog No.

Peripheral Dev

Peripheral Dev

Peripheral Dev

Peripheral Dev

Peripheral Dev

Peripheral Dev

2.Add the heat dissipation values together for your total chassis heat dissipation.

2.Add the heat dissipation values together for your total chassis heat dissipation.

2.Add the heat dissipation values together for your total chassis heat dissipation.

Heat Dis (Watts)

3.Calculate the power supply loading for each chassis (minimum watts) for each device.(1) Chassis Number 1 Slot

Catalog No.

Chassis Number 2 Heat Dis Slot (Watts)

Catalog No.

Chassis Number 3 Heat Dis Slot (Watts)

Catalog No.

User Power

User Power

User Power

Peripheral Dev

Peripheral Dev

Peripheral Dev

4.Add the heat dissipation values together for your power supply loading.

4.Add the heat dissipation values together for your power supply loading.

4.Add the heat dissipation values together for your power supply loading.

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

5.Use the power supply loading (step 4) for each chassis and the graphs on page 266 to determine power supply dissipation.

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

6.Add the chassis dissipation (step 2) to the power supply dissipation (step 5).

Heat Dis (Watts)

7.Add the values together from step 6 across to the right. 8.Covert the value from step 7 to BTUs/hr by multiplying the total heat dissipation of your controller by 3.414. (1)

If you have a device connected to user power, multiply 24V dc by the amount of current used by that device. Include user power in the total power supply loading.

Publication 1747-UM011G-EN-P - June 2008

Page 270

270

Calculating Heat Dissipation for the SLC 500 Control System

Notes:

Publication 1747-UM011G-EN-P - June 2008