Page 211
RS-232 Communication Interface
211
DCD (Data Carrier Detect) - this is an input signal from the DCE that indicates a carrier signal is being received and that presumably data is to be received for forwarding to the DTE connected.
Wiring Connectors for RS-232 Communication
To connect Allen-Bradley devices with other devices over RS-232, you must wire the cable connectors so that communication can occur through the cabling, which provide the interface between devices.
Types of RS-232 Connectors The figures below show male connectors, and their pinout locations, for Allen-Bradley devices.
5 4 3 2 1
8 7 6 5 4 3 2 1
9 8 7 6
9-Pin Connector (male)
13 12 11 10 9 8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
15-Pin Connector (male)
25 24 23 22 21 20 19 18 17 16 15 14
25-Pin Connector (male)
DTE Pinout Channel 0 is configured as DTE for all SLC 5/03, SLC 5/04, and SLC 5/05 processors. The pinouts are the same as the 9-pin personal computer port. DTE 9 Pinout
Signal is Equivalent Equivalent DTE 15 Pinout DTE 25 Pinout
Pin
Description
1
DCD Data Carrier Detect
Input
8
8
2
RXD Received Data
Input
3
3
3
TXD Transmitted Data
Output
2
2
4
DTR Data Terminal Ready
Output
11
20
5
COM Common Return (Signal Ground)
Shared
7
7
6
DSR Data Set Ready
Input
6
6
Publication 1747-UM011G-EN-P - June 2008
Page 212
212
RS-232 Communication Interface
DTE 9 Pinout
Signal is Equivalent Equivalent DTE 15 Pinout DTE 25 Pinout
Pin
Description
7
RTS Request to Send
Output
4
4
8
CTS Clear to Send
Input
5
5
9
NC No Connection
Input
22 (RI Ring Indicator)
DCE Pinout Devices such as a modem are DCE. The pinouts on these terminals are wired to interface with DTE. DCE 9 Pinout
Equivalent DCE 25 Pinout
Pin
Description
1
DCD Data Carrier Detect
Input
8
2
RXD Received Data
Input
3
3
TXD Transmitted Data
Output
2
4
DTR Data Terminal Ready
Output
20
5
COM Common Return (Signal Ground)
Shared
7
6
DSR Data Set Ready
Input
6
7
RTS Request to Send
Output
4
8
CTS Clear to Send
Input
5
9
RI Ring Indicator
Input
22
IMPORTANT
Publication 1747-UM011G-EN-P - June 2008
Signal is
DCE signal names are viewed from a DTE perspective. For example, TXD is a DTE output and also a DCE input.
Page 213
RS-232 Communication Interface
213
Pin Assignments for Wiring Connectors Use the following pin assignments to wire the connectors of Allen-Bradley control devices with modems and peripheral devices that support RS-232 communication. See the table below to find the wiring diagram that you need. To connect this device
To this Device
Remarks
See this page
Personal computer
Modem
Hardware handshaking enabled
213
Peripheral DTE
Hardware handshaking disabled
214
Hardware handshaking enabled SLC 5/03, SLC 5/04, Modem and SLC 5/05 Peripheral DTE Hardware handshaking disabled processors Personal Computer Using a 1747-CP3 cable
214 215
1747-KE module 1746-BAS module 2760-RB module PLC-5 (channel 0)
215
Modem
Hardware handshaking enabled
216
Peripheral DTE
Hardware handshaking disabled
216
Modem
Hardware handshaking enabled
217
Peripheral DTE
Hardware handshaking disabled
217
Modem
Hardware handshaking enabled
218
Peripheral DTE
Hardware handshaking disabled
218
Modem
Hardware handshaking enabled
219
Peripheral DTE
Hardware handshaking disabled
219
Personal Computer to a Modem (Hardware Handshaking Enabled)
25-Pin
9-Pin
PC
8
1
DCD
3
2
2
3
20
4
7
Modem 9-Pin GND
(1)
25-Pin 1
DCD
1
8
RXD
RXD
2
3
TXD
TXD
3
2
DTR
DTR
4
20
5
COM
COM
5
7
6
6
DSR
DSR
6
6
4
7
RTS
RTS
7
4
5
8
CTS
CTS
8
5
22
9
RI
RI
9
22
DTE
DCE
(1) Connect to the shield of the cable.
Publication 1747-UM011G-EN-P - June 2008
Page 214
214
RS-232 Communication Interface
Personal Computer to SLC 5/03, SLC 5/04, or SLC 5/05 Processor, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking Disabled) (1) Modem (2)
(2)
9-Pin
25-Pin
DCD
1
8
RXD
RXD
3
2
3
TXD
TXD
2
3
4
DTR
DTR
4
20
7
5
COM
COM
5
7
6
6
DSR
DSR
6
6
4
7
RTS
RTS
7
4
5
8
CTS
CTS
8
5
22
9
RI
25-Pin
9-Pin
PC
GND (3)
8
1
DCD
3
2
2 20
1
DCE
DTE
(1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect to the shield of the cable.
SLC 5/03, SLC 5/04, or SLC 5/05 Processor Connected to a Modem (Hardware Handshaking Enabled) Modem
9-Pin
SLC 5/03
1
DCD
DCD
1
8
2
RXD
RXD
2
3
3
TXD
TXD
3
2
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DSR
6
6
7
RTS
RTS
7
4
8
CTS
CTS
8
5
9
NC
RI
9
22
DTE (1) Connect to the shield of the cable.
Publication 1747-UM011G-EN-P - June 2008
9-Pin
GND (1)
25-Pin 1
DCE
(2)
(2)
Page 215
RS-232 Communication Interface
215
SLC 5/03, SLC 5/04, or SLC 5/05 Processor to another SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal Computer, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking Disabled) (1)
(2)
(2)
Peripheral 9-Pin Device
25-Pin
9-Pin
SLC 5/03
1
DCD
DCD
1
8
2
TXD
TXD
3
2
3
RXD
RXD
2
3
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DSR
6
6
7
RTS
RTS
7
4
8
CTS
CTS
8
5
9
NC
GND
(3)
1 (2)
(2)
DCE
DTE
(1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect to the shield of the cable.
SLC 5/03, SLC 5/04, or SLC 5/05 Processor Connected to a Personal Computer with a 1747-CP3 Cable 9-Pin SLC 5/03
PC
9-Pin
1
DCD
DCD
1
2
RXD
TXD
3
3
TXD
RXD
2
4
DTR
DSR
6
5
COM
COM
5
6
DSR
DTR
4
7
RTS
CTS
8
8
CTS
RTS
9
NC
7
DCE
DTE
Publication 1747-UM011G-EN-P - June 2008
Page 216
216
RS-232 Communication Interface
1747-KE Module to a Modem (Hardware Handshaking Enabled) Peripheral Device 9-Pin 1747-KE
GND
9-Pin
25-Pin
(1)
1
1
NC
DSR
6
6
2
RXD
RXD
2
3
3
TXD
TXD
3
2
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DCR
1
8
7
RTS
RTS
7
4
8
CTS
CTS
8
5
NC
RI
9
22
9
DTE
DCE
(1) Connect to the shield of the cable.
1747-KE Module to a SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal Computer, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking Disabled) (1) Peripheral Device
(2)
(2)
9-Pin
25-Pin
DCD
1
8
RXD
TXD
3
2
3
TXD
RXD
2
3
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DSR
6
6
7
RTS
RTS
7
4
8
CTS
CTS
8
5
9
NC
9-Pin
1747-KE
GND
1
NC
2
(3)
1
DTE
DTE (1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect to the shield of the cable.
Publication 1747-UM011G-EN-P - June 2008
(2)
(2)
Page 217
RS-232 Communication Interface
217
1746-BAS Module to a Modem (Hardware Handshaking Enabled)
Peripheral Device 9-Pin
25-Pin
9-Pin
1746-BAS
GND (1)
1
NC
DSR
6
6
2
RXD
RXD
2
3
3
TXD
TXD
3
2
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DCD
1
8
7
RTS
RTS
7
4
8
CTS
CTS
8
5
9
NC
RI
9
22
1
DTE
DCE
(1) Connect to the shield of the cable.
1746-BAS Module to a SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal Computer, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking Disabled) (1) Peripheral Device 9-Pin 9-Pin 1746-BAS
(2)
(2)
GND
(3)
25-Pin 1
1
NC
NC
1
8
2
RXD
TXD
3
2
3
TXD
RXD
2
3
4
DTR
DTR
4
20
5
COM
COM
5
7
6
DSR
DSR
6
6
7
RTS
RTS
7
4
8
CTS
CTS
8
5
9
NC
(2)
(2)
DTE
DTE (1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect to the shield of the cable.
Publication 1747-UM011G-EN-P - June 2008
Page 218
218
RS-232 Communication Interface
2760-RB Module to a Modem (Hardware Handshaking Enabled) Modem 25-Pin 2760-RB
9-Pin
25-Pin
GND (1)
1
GND (1)
DCD
1
8
2
TXD
TXD
3
2
3
RXD
RXD
2
3
4
RTS
RTS
7
4
5
CTS
CTS
8
5
6
DSR
DSR
6
6
7
COM
COM
5
7
20
DTR
DTR
4
20
9
22
1
DTE
RI
DCE (1) Connect the shield of the cable to the GND pin on one end only. Leave the other end open.
2760-RB Module to a SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal Computer, 1770-KF3 Module, or PLC-5 Processor (Hardware Handshaking Disabled) Peripheral Device 9-Pin
(2)
(2)
25-Pin
25-Pin
2760-RB
GND (3)
1
GND (3)
DCD
1
8
2
TXD
RXD
3
2
3
RXD
TXD
2
3
4
RTS
DTR
7
4
5
CTS
COM
8
5
6
DSR
DSR
6
6
7
COM
RTS
5
7
20
DTR
CTS
4
20
DTE
1
DTE
(1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect the shield of the cable to the GND pin on one end only. Leave the other end open.
Publication 1747-UM011G-EN-P - June 2008
(2)
(2)
Page 219
RS-232 Communication Interface
219
PLC-5 Processor (Channel 0) to a Modem (Hardware Handshaking Enabled) Modem 25-Pin PLC-5, CH0
9-Pin
25-Pin
GND (1)
1
8
DCD
DCD
1
8
3
RXD
RXD
2
3
2
TXD
TXD
3
2
20
DTR
DTR
4
20
7
COM
COM
5
7
6
DSR
DSR
6
6
4
RTS
RTS
7
4
5
CTS
CTS
8
5
22
NC
RI
9
22
DTE
DCE
(1) Connect to the shield of the cable.
PLC-5 Processor (Channel 0) to a SLC 5/03, SLC 5/04, or SLC 5/05 Processor, Personal Computer, 1770-KF3 Module, PLC-5 Processor, 1747-KE Module, or 1746-BAS Module (Hardware Handshaking Disabled) (1) Peripheral Device 9-Pin 25-Pin PLC-5, CH0 (2)
(2)
8
DCD
GND(3)
25-Pin 1
DCD
1
8 2 3
3
RXD
TXD
3
2
TXD
RXD
2
20
DTR
DTR
4
20
7
COM
COM
5
7
6
DSR
DSR
6
6
4
RTS
RTS
7
4
5
CTS
CTS
8
5
22
NC
DTE
(2)
(2)
DTE
(1) You can also use the 1747-CP3 cable. (2) Jumpers are only needed if you cannot disable the hardware handshaking on the port. (3) Connect to the shield of the cable.
Publication 1747-UM011G-EN-P - June 2008
Page 220
220
RS-232 Communication Interface
Applications for the RS-232 Communication Interface
The figures below illustrate different applications for the RS-232 communication interface.
DF1 Full-duplex Peer-to-peer
Modem
Modem
SLC 5/03 Modular Controller
SLC 5/03 Modular Controller
Half-duplex with Slave-to-slave Routing IMPORTANT
The 1747-KE module does not support slave-to-slave transfers.
WINtelligent Linx or RSLinx Running DF1 Half-duplex Protocol (Master)
Modem
Modem
SLC 5/03 Modular Controller
Publication 1747-UM011G-EN-P - June 2008
Modem
SLC 5/03 Modular Controller