Page 221

Appendix

D

Setting Up the DH+ Network

This appendix provides an overview of the Data Highway Plus (DH+) communication protocol and explains how the SLC 5/04 processors support it. This appendix also provides: • a DH+communication protocol overview. • an SLC 5/04 processor and DH+communication. • wiring connectors for DH+communication for SLC 5/04. • a typical DH+network configuration.

Data Highway Plus Communication Protocol Overview

Data Highway Plus implements peer-to-peer communication with a token-passing scheme to rotate link mastership among a maximum of 64 nodes. Since this method does not require polling, it helps provide time-efficient reliable data transport. The DH+features: • remote programming of PLC-2, PLC-3, PLC-5 and SLC 500 processors on your network. • direct connections to PLC-5 processors and industrial programming terminals. • easy re-configuration and expansion if you want to add more nodes later. • a communication rate of 57.6 Kbaud, 115.2 Kbaud, or 230.4 Kbaud. The following table summarizes the type of termination resistor needed to communicate at the specified communication rate with the maximum cable length. Termination Resistor and Communication Link

221

Termination Link Resistor Value Ω

Communication Rate (Kbaud)

Maximum Cable Length m (ft)

150

57.6

3048 (10,000)

150

115

1542 (5000)

82

230.4

762 (2500)

Publication 1747-UM011G-EN-P - June 2008

Page 222

222

Setting Up the DH+ Network

SLC 5/04 Processors and DH+ Communication

The SLC 5/04 processors let you operate DH+communication protocol by means of the DH+communication channel 1. The SLC 5/04 processors also support DF1 full-duplex protocol, DF1 half-duplex master and slave protocol, ASCII, or DH-485 via its RS-232 port, channel 0. The 3-pin connector, provided with the SLC 5/04 processors, is for actual DH+communication and the 8-pin connector is for monitoring DH+communication.

DH+ Channel 1, 3-Pin Pin

Pin Name

1

DH+Data Line 1

2

Shield

3

DH+Data Line 2

DH+ Channel 1, 8-Pin

Publication 1747-UM011G-EN-P - June 2008

Pin

Pin Name

1

DH+Data Line 2

2

No Connection

3

Shield

4

No Connection

5

No Connection

6

DH+Data Line 1

7

No Connection

8

No Connection

Page 223

Setting Up the DH+ Network

223

Channel 1 Location SLC 5/04 CPU RUN FLT BATT

FORCE DH+ RS232

RUN REM PROG

DH+ Channel 1

Publication 1747-UM011G-EN-P - June 2008

Page 224

Setting Up the DH+ Network

224

Wiring Connectors for DH+ Communication for SLC 5/04 Processors

To connect Allen-Bradley devices with other devices over DH+, you must wire the 3-pin cable connectors so that communication can occur through the cabling. Each device requires its own node address.

PROG

BATT

R E M

PROC FORCE

RUN

COMM

SLC 5/04 CPU

SLC 5/04 CPU

RUN

FORCE

RUN

FORCE

FLT

DH+

FLT

BATT

RS232

BATT

DH+ RS232

RUN REM PROG

RUN REM PROG A

Connector 1

2

Terminating Resistor

Clear Shield Blue

B

Terminating Resistor

Connector Clear Shield Blue

1

2 PLC±5/20 PROGRAMMABLE CONTROLLER

Belden #9463 Cable

Connector Clear Shield Blue

1

2

Belden #9463 Cable

Terminate the DH+ link on both ends by connecting a 150 Ω, 1/2 W resistor between terminals 1 and 2 of the 3-pin connector when you are communicating at 57.6 Kbaud with a PLC-5 processor or 115.2 Kbaud with other SLC 5/04 processors. Use an 82 Ω, 1/2 W resistor if you are communicating at 230.4 Kbaud with other SLC 5/04 processors or series E enhanced PLC-5 processor.

Publication 1747-UM011G-EN-P - June 2008

Page 225

Setting Up the DH+ Network

225

Minimizing Noise To minimize the affect of noise on the SLC 5/04 processor, ground the cable shields to earth via 0.01μF capacitors as shown in the DH+ wiring example below. Only directly ground the shield at one point on the network.

PROG

BATT

R E M

PROC FORCE

RUN

COMM

SLC 5/04 CPU

SLC 5/04 CPU

RUN

FORCE

RUN

FORCE

FLT

DH+

FLT

BATT

RS232

DH+ RS232

Earth Ground

0.01μF

BATT

RUN REM PROG

1

2

RUN REM PROG

Connector Clear Shield Blue

Terminating Resistor

Shield

A

Terminating Resistor

Connector Clear 1 Shield 2 Blue

Shield (1)

B

PLC±5/20 PROGRAMMABLE CONTROLLER

Connector Clear Shield Blue

1

2

Shield 0.01μF

Earth Ground Earth Ground Belden #9463 Cable

Belden #9463 Cable

(1) To chassis ground directly at one point only in the network.

Publication 1747-UM011G-EN-P - June 2008

Page 226

226

Setting Up the DH+ Network

The following figure illustrates a possible configuration for the SLC 5/04 processor on a DH+network. You can also use an SLC 500, SLC 5/01, SLC 5/02, SLC 5/03, or SLC 5/05 processor in place of the SLC 5/04 processor on the DH+network if the 1785-KA5 card is used with a PLC-5 processor.

Typical DH+ Network Configuration

Personal Computer with 1784-KTXD or 1784-PKTX(D) Interface

APS

PLC-5/15 Processor

DH+ Network

PLC-5/15 Processor with a 1785-KA5 Card The PLC-5 Processor and 1785-KA5 Card are daisy chained together.

1747-NET-AIC Interface Converter

SLC 5/04 Modular Controller

1747-AIC Converter

1747-AIC Converter

1747-AIC Converter

1747-AIC Converter

SLC 5/02 Modular Controller

SLC 5/03 Modular Controller

The DH+protocol uses factory set timeouts to restart token-passing communication if the token is lost because of a defective node. Other devices that use the DH+ network include those in the table below. Catalog Number

Description

Installation Requirement

Function

Publication Number

1784-PCMK

PCMCIA interface card

PCMCIA slot in computer

Provides DH+ or DH-485 connection

1784-UM519

1784-PKTX(D)

Personal computer DH+ interface card

PCI bus

Provides DH+ or DH-485 connection

1784-UM527

Publication 1747-UM011G-EN-P - June 2008

Page 227

Appendix

E

Power Supply Worksheet

Power Supply Loading

Use the table below to calculate the power supply loading for each chassis in your SLC modular application. Hardware Component Cat. No. Processors

Digital Input Modules

Maximum Current (A) at 5V dc at 24V dc

1747-L511

0.090

0

1747-L514

0.090

0

1747-L524

0.090

0

1747-L531

0.500

0.175

1747-L532

0.500

0.175

1747-L533

0.500

0.175

1747-L541

1.000

0

1747-L542

1.000

0

1747-L543

1.000

0

1747-L551

1.000

0

1747-L552

1.000

0

1747-L553

1.000

0

1746-IA4

0.035

-

1746-IA8

0.050

-

1746-IA16

0.085

-

1746-IB8

0.050

-

0.050

-

0.050

-

1746-IC16

0.050

-

1746-IG16

0.140

-

1746-IH16

0.085

-

1746-IM4

0.035

-

1746-IM8

0.050

-

1746-IM16

0.085

-

1746-IN16

0.085

-

1746-ITB16

0.050

-

1746-ITV16

0.085

-

1746-IV8

0.050

-

1746-IV16

0.085

-

1746-IV32(1)

0.050

-

1746-IB16 1746-IB32

227

(1)

Publication 1747-UM011G-EN-P - June 2008

Page 228

228

Power Supply Worksheet

Hardware Component Cat. No.

Maximum Current (A) at 5V dc at 24V dc

1746-OA8

0.185

-

1746-OA16

0.370

-

1746-OAP12

0.370

-

1746-OB6EI

0.046

-

1746-OB8

0.135

-

1746-OB16

0.280

-

1746-OB16E

0.135

-

1746-OB32(1)

0.190

-

1746-OB32E

0.190

-

1746-OBP8

0.135

-

1746-OBP16

0.250

-

1746-OG16

0.180

-

1746-OV8

0.135

-

1746-OV16

0.270

-

1746-OV32(1)

0.190

-

1746-OVP16

0.250

-

1746-OW4

0.045

0.045

1746-OW8

0.085

0.090

1746-OW16

0.170

0.180

1746-OX8

0.085

0.090

1746-IO4

0.030

0.025

1746-IO8

0.060

0.045

1746-IO12

0.090

0.070

1746-IO12DC

0.080

0.060

1746-NI4

0.025

0.085

1746-NI8

0.200

0.100

1746-NI16I

0.125

0.075

1746-NI16V

0.125

0.075

Analog Output Modules 1746-NO4I

0.055

0.195

1746-NO4V

0.055

0.145

1746-NO8I

0.120

0.250(2)

Digital Output Modules

Digital Combination Modules

Analog Input Modules

0(3) 1746-NO8V

0.120

0.160(2) 0(3)

Analog Combination Modules

Publication 1747-UM011G-EN-P - June 2008

1746-FIO4I

0.055

0.150

1746-FIO4V

0.055

0.120

1746-NIO4I

0.055

0.145

1746-NIO4V

0.055

0.115

Page 229

Power Supply Worksheet

Hardware Component Cat. No.

Maximum Current (A) at 5V dc at 24V dc

1746-BAS (-T)

0.150

0.040(4)

1746-BLM

1.000

-

1746-BTM

0.110

0.085

1746-HSCE

0.320

-

1746-HSCE2

0.250

-

1746-HSRV

0.300

-

1746-HSTP1

0.300

-

1746-INT4

0.110

0.085

1746-NR4

0.050

0.050

1746-NR8

0.100

0.055

1746-NT4

0.060

0.040

1746-NT8

0.120

0.070

1746-QS

1.000

0.200

1746-QV

0.215

-

Communication Modules 1747-ACN15

0.900

-

1747-ACNR15

0.900

-

1747-ASB

0.375

-

1747-BSN

0.800

0

1747-DCM

0.360

-

1747-KE

0.150

0.040(4)

1747-KFC15

0.640

0

1747-SCNR

0.900

-

1747-SDN

0.500

-

1747-SN

0.600

-

1747-AIC

0

0.085

1747-DTAM

0

(5)

1747-PIC

0

(5)

1747-PSD

NA

NA

1747-UIC(6)

NA

NA

1761-NET-AIC(7)

NA

NA

Specialty Modules

Peripheral Devices

229

(1)

Power supply loading for Series D and later modules.

(2)

J4 jumper set to RACK.

(3)

J4 jumper set to EXT.

(4)

When using the 1746-BAS or 1747-KE modules to supply power to an AIC draws its power through the module. Add 0.085 A (the current loading for the 1761-AIC interface) to the 1746-BAS or 1747-KE module’s power supply loading value at 24V dc.

(5)

The 24V dc loading values of the 1747-PIC and 1747-DTAM interfaces are included in the 24V dc loading value of the processor.

(6)

USB power consumption is less than 100 mA.

(7)

Current for the 1761-NET-AIC must be supplied from an external 24V dc source. No current is consumed from the controller when an external source is used.

Publication 1747-UM011G-EN-P - June 2008

Page 230

230

Power Supply Worksheet

Blank Worksheet Procedure 1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents. Also include the power consumption of any peripheral devices that may be connected to the processor other than a 1747-DTAM or 1747-PIC interface-the power consumption of these devices is accounted for in the power consumption of the processor.

Chassis Number Slot Number

Cat. No.

Maximum Currents

Chassis Number at 5V dc

Slot Number at 24V dc

Maximum Currents Cat. No.

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Slot

Peripheral Device

Peripheral Device

Peripheral Device

Peripheral Device

2.Add the loading currents of all the system devices at 5 and 24V dc to determine the Total Current.

2.Add the loading currents of all the system devices at 5 and 24V dc to determine the Total Current.

at 5V dc at 24V dc

3.For 1746-P4 power supplies, calculate the total power consumption of all system devices. If you are not using a 1746-P4 power supply, go to step 4.

Current

Multiply by = Watts

Current

Multiply by

Total Current at 5V dc

5V

Total Current at 5V dc

5V

Total Current at 24V dc

24V

Total Current at 24V dc

24V

User Current at 24V dc

24V

User Current at 24V dc

24V

Add the Watts values to determine Total Power

Add the Watts values to determine Total Power

(cannot exceed 70 Watts)

(cannot exceed 70 Watts)

= Watts

4.Choose the power supply from the list of catalog numbers shown below. Compare the Total Current required for the chassis with the Internal Current capacity of the power supplies. Be sure that the Total Current consumption for the chassis is less than the Internal Current Capacity for the power supply, for both 5V and 24V loads.

Cat. No.

Internal Current Capacity at 5V dc at 24V dc

1746-P1

2.0A

0.46A

1746-P2

5.0A

1746-P3

3.6A

1746-P4 (see step 3) 1746-P5 at 24V dc

1746-P1

2.0A

0.46A

0.96A

1746-P2

5.0A

0.96A

0.87A

1746-P3

3.6A

0.87A

10.0A

2.88A

1746-P4 (see step 3)

10.0A

2.88A

5.0A

0.96A

1746-P5

5.0A

0.96A

5.0A

0.96A

1746-P6

2.0A

0.46A

24V Input

3.6A

0.87A

1746-P7 (See page 37 for current capacity.)

Required Power Supply Publication 1747-UM011G-EN-P - June 2008

Internal Current Capacity at 5V dc

12V Input

1746-P6 1746-P7 (See page 37 for current capacity.)

Cat. No.

5.0A

0.96A

12V Input

2.0A

0.46A

24V Input

3.6A

0.87A

Required Power Supply