Page 231
Appendix
F
Control Networks
This appendix provides a brief introduction about control networks. For more information on using control networks, see the following publications. Control Network Publication
Publication Number
Remote I/O
Direct Communication Module User Manual
1747-6.8
RIO Scanner User Manual
1747-UM013
DeviceNet Scanner Configuration Manual
1747-UM655
DeviceNet Interface User Manual
1761-UM005
SLC ControlNet Scanner Reference Manual
1747-RM623
DeviceNet ControlNet
SLC 500 ControlNet RS-232 Interface Module 1747-5.34 User Manual
The Allen-Bradley Remote I/O Network is a master/slave control network that enables chassis of I/O, operator interface terminals, push-button panels, I/O blocks, message displays, and drives to be great distances from the host PLC processor. The SLC 500 fixed, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processors can interface to this network through the 1747-DCM module for distributed control. The DCM lets the SLC 500 processor look like another slave device on the network.
Allen-Bradley Remote I/O Network
Below is an example of the Allen-Bradley Remote I/O Network.
PLC-5 or SLC 5/02 and later processors with 1747-SN scanner SLC Fixed Controller
1747-DCM Module
1747-DCM Module
SLC 5/01 Processor
1747-DCM Module SLC 5/03 Processor
1771 Remote I/O Network PanelView Operator Terminal
With an SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processor, a 1747-SN Remote I/O Scanner can be used as the master of a remote I/O network. 231
Publication 1747-UM011G-EN-P - June 2008
Page 232
232
Control Networks
Remote I/O Network
1747-SN Module
1771 Remote I/O Network 1747-ASB Module
1747-ASB Module
Block I/O
PanelView Operator Terminal
Each 1747-SN scanner supports 4 logical racks of 256 I/O each per logical rack. If large amounts of data need to be transferred to a device such as a PanelView operator interface, the 1747-SN series B scanner supports block transfer of up to 64 words of data. Up to 16 devices can be connected to a single remote I/O network. The SLC system supports multiple 1747-SN scanners if more devices are required to be controlled by a single SLC processor.
Remote I/O Passthru Remote I/O passthru enables communication between a personal computer on the same network as an SLC 5/03, 5/04, or 5/05 processor to devices on the remote I/O network. For example, a personal computer running PanelBuilder32 software and communicating on the DH+ network could upload and download applications from a PanelView operator terminal communicating on the remote I/O network. This feature eliminates the need to physically connect the personal computer to the PanelView operator terminal when you need to change the application. This capability is available on the 1747-SN series B scanner, and the 1747-BSN backup scanner. Remote I/O Passthru Personal Computer running PanelView Software
SLC 5/04 Processor
SLC 5/02 Processor
1747-SN, Series B Module
1771 Remote I/O Network DH+ Network Block I/O
PanelView Operator Terminal
Publication 1747-UM011G-EN-P - June 2008
1747-DCM Module
Page 233
Control Networks
TIP
DeviceNet Network
233
The SLC 5/03 OS302 or later, SLC 5/04 OS401 or later, and SLC 5/05 processor support remote I/O passthru via both their communication ports.
A DeviceNet network connects plant floor devices directly to the control system (for example, SLC 500 controller) reducing the number of I/O interfaces and wiring associated with a typical hard-wired solution. The DeviceNet communication network is a completely open device network and has the support of industry’s leading sensor, actuator, and control manufacturers.
The 1747-SDN DeviceNet Scanner In a typical configuration, the 1747-SDN DeviceNet Scanner acts as an interface between DeviceNet devices and the SLC 5/02, SLC 5/03, SLC 5/04, and SLC 5/05 processors. The scanner communicates with DeviceNet devices over the network to: • read inputs from a device. • write outputs to a device. • download configuration data. • monitor a device’s operational status. The scanner communicates with the SLC 500 processors to exchange I/O data. Information exchanged includes: • device I/O data. • status information. • configuration data. A single scanner (master) can communicate with up to 63 nodes (slaves) on DeviceNet. The SLC system supports multiple scanners if more devices are required to be controlled by a single SLC 500 processor.
Publication 1747-UM011G-EN-P - June 2008
Page 234
234
Control Networks
DeviceNet Network 1747-SDN Scanner 1770-KFD Interface
SLC 5/02 or later processor
RS-232 cable
DeviceNet Network
Personal Computer with RSNetworx for DeviceNet Software
Flex I/O Controller RediSTATION Panel 1305 Drive
DeviceNet Devices
The 1761-NET-DNI DeviceNet Interface The DeviceNet Interface (DNI) is an intelligent DeviceNet-to-DF1 protocol conversion device that let existing DF1 devices communicate on DeviceNet network. The DF1 device is able to exchange I/O data with a master device and is able to initiate and receive DF1 encapsulated DeviceNet messages across a DeviceNet network. The DNI provides a single DeviceNet connection point and a single RS-232 connection. The DeviceNet port is isolated from the DNI digital logic and RS-232 port. The primary functions of the DNI are: • to collect and receive input data from the DF1 device connected on its RS-232 port and forward that data to a connected master on a DeviceNet network. • to monitor output data received from the DeviceNet master and write that data to the DF1 device. • to let DF1 devices send and receive messages across the DeviceNet network. The DNI can be used to interconnect: • MicroLogix controllers. • PLC-5 programmable controllers. • operator interface devices. • SLC 5/03, SLC 5/04, and SLC 5/05 processors.
Publication 1747-UM011G-EN-P - June 2008
Page 235
Control Networks
235
1747-SDN Scanner
SLC 5/03 or later processor
Master/Slave I/O Peer-to-Peer Messaging DeviceNet Network Node 3 Personal Computer with RSLogix500 and/or RSNetWorx for DeviceNet
DNI Module
Node 1 KFD
Node 2
MicroLogix Controller
DeviceNet Network Length The DeviceNet network lengths are listed below. Network Length
Communication Rate
100 m (328.08 ft)
500 Kbaud
200 m (656.16 ft)
250 Kbaud
500 m (1640.42 ft)
125 Kbaud
Publication 1747-UM011G-EN-P - June 2008
Page 236
236
Control Networks
ControlNet Network
ControlNet systems are designed to: • provide high-speed, repeatable, deterministic I/O transmission. • let control and message information co-exist on the same physical media. • make sure that I/O data transfers are not affected by programming terminal activity or interscanner message activity on the network.
The 1747-SCNR ControlNet Scanner Module The 1747-SCNR scanner provides the capability for SLC processors to produce or consume scheduled I/O to and from a ControlNet network. Scheduled messaging lets the SLC processor program control I/O events in real time over the ControlNet network. The module connects to a ControlNet network via the standard BNC connectors.
The 1747-KFC15 ControlNet Messaging Module The 1747-KFC15 module provides the capability for SLC 5/03 and later processors to send or receive unscheduled ControlNet messages. With unscheduled messages, the SLC processor program can send peer-to-peer messages or be accessed and edited over the ControlNet network using RSLogix 500 software. The 1747-KFC15 module connects to the ControlNet network via the standard BNC connectors and links to the SLC processor via a standard RS-232 cable. Other programming interfaces can connect to the ControlNet network through the 1747-KFC15 module’s network access port.
Publication 1747-UM011G-EN-P - June 2008
Page 237
Appendix
G
Communicating with Devices on an Ethernet Network
This appendix: • describes SLC 5/05 processors and Ethernet communication. • describes SLC 5/05 performance considerations. • describes Ethernet network connections and media. • explains how the SLC 5/05 establishes node connections. • lists Ethernet configuration parameters and procedures. • describes configuration for subnet masks and gateways.
SLC 5/05 Processors and Ethernet Communication
Ethernet is a local area network that provides communication between various devices at 10/100 Mbps. The physical communication media options for the SLC 5/05 are: • built-in. – twisted-pair (10/100Base-T) • with media converters or hubs. – fiber optic – broadband – thick-wire coaxial cable (10Base-5) – thin-wire coaxial cable (10Base-2) See the following page for more information on Ethernet physical media. The SLC 5/05 processor supports Ethernet communication via the Ethernet communication channel 1 shown in the drawing page 238.
237
Publication 1747-UM011G-EN-P - June 2008
Page 238
238
Communicating with Devices on an Ethernet Network
Communication Channels SLC 5/05 CPU RUN FLT
FORCE ENET
BATT
RS232
RUN REM PROG
Channel 1 Ethernet (10Base-T) Channel 0 RS-232 (DH485, DF1, or ASCII)
SLC 5/05 Performance Considerations
Actual performance of an SLC 5/05 processor varies according to: • size of Ethernet messages. • frequency of Ethernet messages. • network loading. • the implementation and performance of your processor application program. Optimal Performance: RSLinx to SLC 5/05 Processor (2-node Ethernet network)
Publication 1747-UM011G-EN-P - June 2008
Operation
Words MSG per Second
Words per Second
Single Typed Read
1
105
105
Single Typed Reads
20
99
1980
Single Typed Reads
100
86
8600
Single Typed Reads
256
71
18,176
Page 239
Communicating with Devices on an Ethernet Network
SLC 5/05 Processor and Personal Computer Connections to the Ethernet Network
239
The SLC 5/05 Ethernet connector conforms to ISO/IEC 8802-3 STD 802.3 and utilizes 10/100Base-T media. Connections are made directly from the SLC 5/05 to an Ethernet hub. The network setup is simple and cost effective. Typical network topology is pictured below.
Ethernet Network Topology Ethernet Hub
To PC Ethernet Card
IMPORTANT
RJ45 Connectors (both ends of cable (10/100Base-T))
To SLC 5/05 Channel 1
The SLC 5/05 processor contains a 10/100Base-T, RJ45 Ethernet connector which connects to standard Ethernet hubs via 8-wire twisted-pair straight-through cable. To access other Ethernet mediums, use 10/100Base-T media converters or Ethernet hubs that can be connected together via fiber, thin-wire, or thick-wire coaxial cables, or any other physical media commercially available with Ethernet hubs.
Publication 1747-UM011G-EN-P - June 2008
Page 240
240
Communicating with Devices on an Ethernet Network
Ethernet Channel 1 8-pin 10Base-T Connector The Ethernet connector is an RJ45, 10Base-T connector. The pin-out for the connector is shown below. Pin
Pin Name
1
TD+
2
TD-
3
RD+
4 not used by 10BASE-T
5 not used by 10BASE-T
6
RD-
7 not used by 10BASE-T
8 not used by 10BASE-T
When to use straight-through and cross-over pin-out: • SLC 5/05 Ethernet port to 10/100Base-T Ethernet hub cables utilize a straight-through pin-out (1-1, 2-2, 3-3, 6-6). • Direct point-to-point 10/100Base-T cables connecting the SLC 5/05 Ethernet port directly to another SLC 5/05 Ethernet port (or a computer 10/100Base-T port) require a cross-over pin-out (1-3, 2-6, 3-1, 6-2).
Cables Shielded and non-shielded twisted-pair 10/100Base-T cables with RJ45 connectors are supported. The maximum cable length between an SLC 5/05 Ethernet port and a 10/100Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (323 ft). However, in an industrial application, cable length should be kept to a minimum.
Ethernet Connections
TCP/IP is the mechanism used to transport Ethernet messages. On top of TCP, the Client/Server Protocol is required to establish sessions and to send the MSG commands. Connections can be initiated by either a client program (INTERCHANGE or RSLinx application) or a processor. The client program or processor must first establish a connection to the SLC 5/05 processor to enable the SLC 5/05 processor to receive solicited messages from a client program or another processor.
Publication 1747-UM011G-EN-P - June 2008