Page 231

Appendix

F

Control Networks

This appendix provides a brief introduction about control networks. For more information on using control networks, see the following publications. Control Network Publication

Publication Number

Remote I/O

Direct Communication Module User Manual

1747-6.8

RIO Scanner User Manual

1747-UM013

DeviceNet Scanner Configuration Manual

1747-UM655

DeviceNet Interface User Manual

1761-UM005

SLC ControlNet Scanner Reference Manual

1747-RM623

DeviceNet ControlNet

SLC 500 ControlNet RS-232 Interface Module 1747-5.34 User Manual

The Allen-Bradley Remote I/O Network is a master/slave control network that enables chassis of I/O, operator interface terminals, push-button panels, I/O blocks, message displays, and drives to be great distances from the host PLC processor. The SLC 500 fixed, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processors can interface to this network through the 1747-DCM module for distributed control. The DCM lets the SLC 500 processor look like another slave device on the network.

Allen-Bradley Remote I/O Network

Below is an example of the Allen-Bradley Remote I/O Network.

PLC-5 or SLC 5/02 and later processors with 1747-SN scanner SLC Fixed Controller

1747-DCM Module

1747-DCM Module

SLC 5/01 Processor

1747-DCM Module SLC 5/03 Processor

1771 Remote I/O Network PanelView Operator Terminal

With an SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processor, a 1747-SN Remote I/O Scanner can be used as the master of a remote I/O network. 231

Publication 1747-UM011G-EN-P - June 2008

Page 232

232

Control Networks

Remote I/O Network

1747-SN Module

1771 Remote I/O Network 1747-ASB Module

1747-ASB Module

Block I/O

PanelView Operator Terminal

Each 1747-SN scanner supports 4 logical racks of 256 I/O each per logical rack. If large amounts of data need to be transferred to a device such as a PanelView operator interface, the 1747-SN series B scanner supports block transfer of up to 64 words of data. Up to 16 devices can be connected to a single remote I/O network. The SLC system supports multiple 1747-SN scanners if more devices are required to be controlled by a single SLC processor.

Remote I/O Passthru Remote I/O passthru enables communication between a personal computer on the same network as an SLC 5/03, 5/04, or 5/05 processor to devices on the remote I/O network. For example, a personal computer running PanelBuilder32 software and communicating on the DH+ network could upload and download applications from a PanelView operator terminal communicating on the remote I/O network. This feature eliminates the need to physically connect the personal computer to the PanelView operator terminal when you need to change the application. This capability is available on the 1747-SN series B scanner, and the 1747-BSN backup scanner. Remote I/O Passthru Personal Computer running PanelView Software

SLC 5/04 Processor

SLC 5/02 Processor

1747-SN, Series B Module

1771 Remote I/O Network DH+ Network Block I/O

PanelView Operator Terminal

Publication 1747-UM011G-EN-P - June 2008

1747-DCM Module

Page 233

Control Networks

TIP

DeviceNet Network

233

The SLC 5/03 OS302 or later, SLC 5/04 OS401 or later, and SLC 5/05 processor support remote I/O passthru via both their communication ports.

A DeviceNet network connects plant floor devices directly to the control system (for example, SLC 500 controller) reducing the number of I/O interfaces and wiring associated with a typical hard-wired solution. The DeviceNet communication network is a completely open device network and has the support of industry’s leading sensor, actuator, and control manufacturers.

The 1747-SDN DeviceNet Scanner In a typical configuration, the 1747-SDN DeviceNet Scanner acts as an interface between DeviceNet devices and the SLC 5/02, SLC 5/03, SLC 5/04, and SLC 5/05 processors. The scanner communicates with DeviceNet devices over the network to: • read inputs from a device. • write outputs to a device. • download configuration data. • monitor a device’s operational status. The scanner communicates with the SLC 500 processors to exchange I/O data. Information exchanged includes: • device I/O data. • status information. • configuration data. A single scanner (master) can communicate with up to 63 nodes (slaves) on DeviceNet. The SLC system supports multiple scanners if more devices are required to be controlled by a single SLC 500 processor.

Publication 1747-UM011G-EN-P - June 2008

Page 234

234

Control Networks

DeviceNet Network 1747-SDN Scanner 1770-KFD Interface

SLC 5/02 or later processor

RS-232 cable

DeviceNet Network

Personal Computer with RSNetworx for DeviceNet Software

Flex I/O Controller RediSTATION Panel 1305 Drive

DeviceNet Devices

The 1761-NET-DNI DeviceNet Interface The DeviceNet Interface (DNI) is an intelligent DeviceNet-to-DF1 protocol conversion device that let existing DF1 devices communicate on DeviceNet network. The DF1 device is able to exchange I/O data with a master device and is able to initiate and receive DF1 encapsulated DeviceNet messages across a DeviceNet network. The DNI provides a single DeviceNet connection point and a single RS-232 connection. The DeviceNet port is isolated from the DNI digital logic and RS-232 port. The primary functions of the DNI are: • to collect and receive input data from the DF1 device connected on its RS-232 port and forward that data to a connected master on a DeviceNet network. • to monitor output data received from the DeviceNet master and write that data to the DF1 device. • to let DF1 devices send and receive messages across the DeviceNet network. The DNI can be used to interconnect: • MicroLogix controllers. • PLC-5 programmable controllers. • operator interface devices. • SLC 5/03, SLC 5/04, and SLC 5/05 processors.

Publication 1747-UM011G-EN-P - June 2008

Page 235

Control Networks

235

1747-SDN Scanner

SLC 5/03 or later processor

Master/Slave I/O Peer-to-Peer Messaging DeviceNet Network Node 3 Personal Computer with RSLogix500 and/or RSNetWorx for DeviceNet

DNI Module

Node 1 KFD

Node 2

MicroLogix Controller

DeviceNet Network Length The DeviceNet network lengths are listed below. Network Length

Communication Rate

100 m (328.08 ft)

500 Kbaud

200 m (656.16 ft)

250 Kbaud

500 m (1640.42 ft)

125 Kbaud

Publication 1747-UM011G-EN-P - June 2008

Page 236

236

Control Networks

ControlNet Network

ControlNet systems are designed to: • provide high-speed, repeatable, deterministic I/O transmission. • let control and message information co-exist on the same physical media. • make sure that I/O data transfers are not affected by programming terminal activity or interscanner message activity on the network.

The 1747-SCNR ControlNet Scanner Module The 1747-SCNR scanner provides the capability for SLC processors to produce or consume scheduled I/O to and from a ControlNet network. Scheduled messaging lets the SLC processor program control I/O events in real time over the ControlNet network. The module connects to a ControlNet network via the standard BNC connectors.

The 1747-KFC15 ControlNet Messaging Module The 1747-KFC15 module provides the capability for SLC 5/03 and later processors to send or receive unscheduled ControlNet messages. With unscheduled messages, the SLC processor program can send peer-to-peer messages or be accessed and edited over the ControlNet network using RSLogix 500 software. The 1747-KFC15 module connects to the ControlNet network via the standard BNC connectors and links to the SLC processor via a standard RS-232 cable. Other programming interfaces can connect to the ControlNet network through the 1747-KFC15 module’s network access port.

Publication 1747-UM011G-EN-P - June 2008

Page 237

Appendix

G

Communicating with Devices on an Ethernet Network

This appendix: • describes SLC 5/05 processors and Ethernet communication. • describes SLC 5/05 performance considerations. • describes Ethernet network connections and media. • explains how the SLC 5/05 establishes node connections. • lists Ethernet configuration parameters and procedures. • describes configuration for subnet masks and gateways.

SLC 5/05 Processors and Ethernet Communication

Ethernet is a local area network that provides communication between various devices at 10/100 Mbps. The physical communication media options for the SLC 5/05 are: • built-in. – twisted-pair (10/100Base-T) • with media converters or hubs. – fiber optic – broadband – thick-wire coaxial cable (10Base-5) – thin-wire coaxial cable (10Base-2) See the following page for more information on Ethernet physical media. The SLC 5/05 processor supports Ethernet communication via the Ethernet communication channel 1 shown in the drawing page 238.

237

Publication 1747-UM011G-EN-P - June 2008

Page 238

238

Communicating with Devices on an Ethernet Network

Communication Channels SLC 5/05 CPU RUN FLT

FORCE ENET

BATT

RS232

RUN REM PROG

Channel 1 Ethernet (10Base-T) Channel 0 RS-232 (DH485, DF1, or ASCII)

SLC 5/05 Performance Considerations

Actual performance of an SLC 5/05 processor varies according to: • size of Ethernet messages. • frequency of Ethernet messages. • network loading. • the implementation and performance of your processor application program. Optimal Performance: RSLinx to SLC 5/05 Processor (2-node Ethernet network)

Publication 1747-UM011G-EN-P - June 2008

Operation

Words MSG per Second

Words per Second

Single Typed Read

1

105

105

Single Typed Reads

20

99

1980

Single Typed Reads

100

86

8600

Single Typed Reads

256

71

18,176

Page 239

Communicating with Devices on an Ethernet Network

SLC 5/05 Processor and Personal Computer Connections to the Ethernet Network

239

The SLC 5/05 Ethernet connector conforms to ISO/IEC 8802-3 STD 802.3 and utilizes 10/100Base-T media. Connections are made directly from the SLC 5/05 to an Ethernet hub. The network setup is simple and cost effective. Typical network topology is pictured below.

Ethernet Network Topology Ethernet Hub

To PC Ethernet Card

IMPORTANT

RJ45 Connectors (both ends of cable (10/100Base-T))

To SLC 5/05 Channel 1

The SLC 5/05 processor contains a 10/100Base-T, RJ45 Ethernet connector which connects to standard Ethernet hubs via 8-wire twisted-pair straight-through cable. To access other Ethernet mediums, use 10/100Base-T media converters or Ethernet hubs that can be connected together via fiber, thin-wire, or thick-wire coaxial cables, or any other physical media commercially available with Ethernet hubs.

Publication 1747-UM011G-EN-P - June 2008

Page 240

240

Communicating with Devices on an Ethernet Network

Ethernet Channel 1 8-pin 10Base-T Connector The Ethernet connector is an RJ45, 10Base-T connector. The pin-out for the connector is shown below. Pin

Pin Name

1

TD+

2

TD-

3

RD+

4 not used by 10BASE-T

5 not used by 10BASE-T

6

RD-

7 not used by 10BASE-T

8 not used by 10BASE-T

When to use straight-through and cross-over pin-out: • SLC 5/05 Ethernet port to 10/100Base-T Ethernet hub cables utilize a straight-through pin-out (1-1, 2-2, 3-3, 6-6). • Direct point-to-point 10/100Base-T cables connecting the SLC 5/05 Ethernet port directly to another SLC 5/05 Ethernet port (or a computer 10/100Base-T port) require a cross-over pin-out (1-3, 2-6, 3-1, 6-2).

Cables Shielded and non-shielded twisted-pair 10/100Base-T cables with RJ45 connectors are supported. The maximum cable length between an SLC 5/05 Ethernet port and a 10/100Base-T port on an Ethernet hub (without repeaters or fiber) is 100 m (323 ft). However, in an industrial application, cable length should be kept to a minimum.

Ethernet Connections

TCP/IP is the mechanism used to transport Ethernet messages. On top of TCP, the Client/Server Protocol is required to establish sessions and to send the MSG commands. Connections can be initiated by either a client program (INTERCHANGE or RSLinx application) or a processor. The client program or processor must first establish a connection to the SLC 5/05 processor to enable the SLC 5/05 processor to receive solicited messages from a client program or another processor.

Publication 1747-UM011G-EN-P - June 2008