For the Allen-Bradley 1747-SN
Page 95
Chapter
6
Troubleshooting This chapter provides information for troubleshooting the RIO scanner.
Troubleshooting
The FAULT LED is off whenever the scanner is operating properly. The COMM LED state is valid only when the FAULT LED is off. When the scanner’s LEDs change state, use the following table to isolate the cause.
FAULT LED (Red)
COMM LED (Red/Green)
LED Condition
Problem
Solution
Error Code(1)
FAULT LED flashing red
G file is missing.
Enter configuration information in G file.
62H
Invalid G file configuration.
Check configuration for proper 63H G file size and settings.
Duplicate node detected.
Disconnect the RIO link from 64H the scanner and either cycle the scanner’s power, or re-enter the Run mode. Look for another scanner on the same network. If the condition persists, replace the scanner.
FAULT LED red
Hardware error on scanner.
Replace scanner.
68H - 6FH
COMM LED off
SLC Processor powered up in Program mode.
Return to Run mode.
(2)
COMM LED flashing green
A device is not properly configured, connected, powered, or is faulted.
Check the RIO link connections, power and switch settings. (A device may be too large or too small).
(2)
COMM LED flashing red
Scanner is incorrectly connected, or all devices are incorrectly configured, have no power, or are faulted.
CHeck the RIO link wiring at the scanner. CHeck device configurations, power status, and network baud rate.
(2)
COMM LED red
Hardware error on scanner.
Replace scanner.
(2)
SCANNER
(1) Word 6 of the SLC processor status file contains this code. Refer to your programming device’s user manual. (2) These conditions do not generate error indications to the SLC processor.
1
Publication 1747-UM013B-EN-P - January 2005
Page 96
6-2
Troubleshooting
Error Codes
The SLC processor reports error codes in word 6 of the SLC processor status file. Below are the format of the status word and applicable error codes.
Slot Number 01H to 1EH
Error Code 62H - G File is missing 63H - Invalid user configuration 64H - Duplicate node fault 68H to 6FH - Scanner hardware problem
For a complete description of the error codes, refer to the user manual provided with your programming device.
Retry Counters
Electrically noisy environments can cause RIO communication problems. You can use the retry counters to determine if your scanner is having problems communicating with configured devices. To access retry counter information, you must view status file words M1:e.16 through M1:e.31 (and M1:e.32 through M1:e.47 if complementary I/O is used). These counters display the number of communication retries the scanner has made. See the section on retry counters in Chapter 4, Configuration and Programming for more detailed information.
Block Transfers
If you are having problems with Block Transfers, see Chapter 5, RIO Block Transfer, for information on error codes.
Publication 1747-UM013B-EN-P - January 2005
Page 97
Appendix
A
Specifications
This appendix provides scanner and system specifications, as well as throughput information. Topics include: • scanner operating specifications • network specifications • throughput introduction • calculating throughput
Scanner Operating Specifications
Backplane Current Consumption
600 mA @ 5V dc
Operating Temperature
+32°F to 140°F (0°C to +60°C)
Storage Temperature
-40°F to 185°F (-40°C to +85°C)
Humidity
5 to 95% without condensation
Noise Immunity
NEMA Standard ICS 2-230
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Network Specifications
Table A.1 Baud Rate Determination of Maximum Cable Length and Terminating Resistor Size
Using Extended Node Capability
Not Using Extended Node Capability
1
Baud Rate
Maximum Cable Distance (Belden 9463)
Resistor Size
57.6K baud
3048 meters (10,000 feet)
115.2K baud
1524 meters (5000 feet)
82 ohm 1/2 Watt Brown - Green Brown - Gold
230.4K baud
762 meters (2500 feet)
57.6K baud
3048 meters (10,000 feet)
115.2K baud
1524 meters (5000 feet)
230.4K baud
762 meters (2500 feet)
150 ohm 1/2 Watt Brown - Green Brown - Gold 82 ohm 1/2 Watt Gray - Red - Black - Gold
Publication 1747-UM013B-EN-P - January 2005
Page 98
A-2
Specifications
Table A.2 DIP Switch Position for Baud Rate Selection Baud Rate
Throughput Introduction
DIP Switch Position Switch 1
Switch 2
57.6K baud on on
115.2K baud on off
230.4K baud off on
230.4K baud off off
RIO throughput is defined as the time between when an input event occurs at an I/O module in an RIO chassis to when an output event occurs at an I/O module within the same RIO chassis. There are three types of throughput concerning the 1747-SN Series B Scanner and its RIO network: • discrete throughput (time from discretely mapped input to discretely mapped output) without block transfers (BTs) present • discrete throughput (time from discretely mapped input to discretely mapped output) with BTs present • BT throughput (time from when a BT is enabled to when the BT successfully completes)
RIO Network Throughput Components The following components affect RIO network throughput: • the total SLC processor scan time • the total RIO link scan time • adapter(s) backplane scan time(s) • the scanner’s output delay time • the scanner’s input delay time • input module delay times • output module delay times
Publication 1747-UM013B-EN-P - January 2005
Page 99
Specifications
A-3
Processor Scan Scanner Scan ASB Backplane Scan
Scanner Processor
ASB Module
I/O Module
I/O Module
RIO Scan SLC Local Chassis Outputs to Modules Remote Chassis Inputs from Modules Inputs to Modules
RemoteExpansion Chassis Outputs from Modules
Output Device Input Device
When the SLC control program detects that the remote input has been turned on (via the scanner output image), it activates the remote output device (via the scanner output image). Throughput is then defined as the time between when the remote input device is activated to when the remote output turns on.
Calculating Throughput
The 1747-SN Series B Scanner’s throughput is determined by using the formulas provided in this section.
Discrete I/O Throughput without Block Transfers (Tdm-nbt) Present The information in this section is used to calculate the discrete throughput of the 1747-SN Scanner if there are no BTs occurring on the RIO link to any chassis. If BTs are present on the RIO link you must use the Discrete I/O Throughput with Block Transfers (Tdm-bt) Present section to determine your throughput. See page B-6. The formula to calculate the maximum scanner discrete I/O throughput without BTs present is: T dm – nbt = 2T ps + 2T RIO + T adp + T SNo + T SNi + T id + T od Tdm-nbt = The maximum discrete throughput without BTs in milliseconds (ms)
Publication 1747-UM013B-EN-P - January 2005
Page 100
A-4
Specifications
To calculate Tdm-nbt throughput, substitute values for the variables in the formula above. Locate these values in the following documents:
Variable
Variable Description
Location of Variable
Tps
The total processor scan time (ms)
Measured or estimated
TRIO
The total RIO scan time (ms) see the section RIO Scan Time Calculation (TRIO) on page A-4
Tadp
The adapter throughput delay. For a 1747-ASB, this is two ASB backplane scan times.
adapter user manual
TSNo
The scanner module output delay time (ms)
see the section RIO Scanner Output Delay Time (TSNo) on page A-13
TSNi
The scanner module input delay time (ms)
5 ms (constant value for all formulas in this appendix)
Tid
The input module delay time I/O product data and I/O (ms) instruction sheets
Tod
The output module delay time (ms)
I/O product data and I/O instruction sheets
RIO Scan Time Calculation (TRIO) The RIO scan time is calculated by identifying the baud rate and image size of each logical device on the RIO link. Locate the corresponding time value in the following table. If you are using multiple logical devices, add the time values together to determine the total RIO scan time (TRIO). T RIO = T adapter1 + T adapter2 + T adapter3
RIO Scan TImes for Adapters Adapter Size
Publication 1747-UM013B-EN-P - January 2005
Baud Rate 57.6K
115.2K
230.4K
1/4 logical rack
6.0 ms
3.5 ms
2.5 ms
1/2 logical rack
6.5 ms
4.0 ms
2.75 ms
3/4 logical rack
7.5 ms
4.5 ms
3.0 ms
Full logical rack
9.5 ms
5.5 ms
3.5 ms
Page 101
Specifications
A-5
Example Discrete I/O Throughput without Block Transfers Present An SLC 5/03 is controlling an RIO link running at 115.2K baud that has the following adapters: • One 1747-ASB module is configured as a 1/2 logical rack starting at logical rack 0. I/O chassis slot 1 contains 1746-IB16, 16 point input module I/O chassis slot 2 contains 1746-OB16, 16 point output module • Two adapters are each configured as full logical racks (logical racks 1 and 2). • Three adapters are each configured as 1/4 logical racks (logical rack 3). You need to calculate your Tdm-nbt: the RIO throughput time from when the input closes on the 1746-IN16 until the output on the 1746-OB16 is on. 1. Use the throughput formula to calculate the maximum throughput. T dm – nbt = 2T ps + 2T RIO + T ADP + T SNo + T SNi + T id + T od
Tps = 25.0 ms TRIO = The total RIO scan time (ms) TSNo = See value in the table on page A-14, TSNo without M0 File Writes (Normal Mode). TSNi = 5.0 ms Tid = 10.0 ms, which is from I/O module instruction sheets Tod = 1.0 ms, which is from I/O module instruction sheets Tdm-nbt = 2(25.0) + 2TRIO + 8.0 + TSNo + 5.0 + 10.0 + 1.0 2. Calculate the total RIO scan time (TRIO). Locate the baud rate (115.2K) and adapter size, which is found in the table on page A-4. Multiply the RIO scan times listed under the 115.2K heading by the number of each different type of rack that you have. Add those numbers together: T RIO = T adapter1 + T adapter2 + T adapter3
Publication 1747-UM013B-EN-P - January 2005
Page 102
A-6
Specifications
TRIO = 1(4.0 ms) + 2(5.5 ms) + 3(3.5 ms) TRIO = 25.5 ms 3. Find TSNo on page A-14 in the table TSNo without M0 File Writes (Normal Mode). For this example Tupd > Thold, and there are 4 logical racks configured. Therefore: TSNo = 7.0 ms 4. Substitute all the values for variables in the throughput formula and solve for throughput: T dm – nbt = 2T ps + 2T RIO + 2T bp + T SNo + T SNi + T id + T od
Tdm-nbt = 2(25.0)+ 2(25.5) + 8.0 + 7.0 + 5.0 + 10.0 + 1.0 Tdm-nbt = 132.0 ms = maximum throughput
Discrete I/O Throughput with Block Transfers (Tdm-bt) Present The information in this section is used to calculate the discrete throughput of the 1747-SN Scanner if there are BTs occurring on the RIO link to any chassis. If BTs are not present on the RIO link, you must use the Discrete I/O Throughput without Block Transfers (Tdm-nbt) Present section to determine your throughput. See page A-3. The formula to calculate discrete I/O throughput with BTs present is: T dm – bt = 2T ps + 2T RIO + 2T btx + T adp + T SNo – bt + T SNi + T id + T od
Tdm-bt = The maximum discrete throughput with BTs in milliseconds (ms) To calculate Tdm-bt throughput, substitute values for the variables in the formula above. Locate these values in the following documents:
Publication 1747-UM013B-EN-P - January 2005
Page 103
Specifications
A-7
Variable
Variable Description
Location of Variable
Tps
The total processor scan time (ms)
Measured or estimated
TRIO
The total RIO scan time (ms) see the section RIO Scan Time Calculation (TRIO) on page A-4
Tbtx
Additional time due to sending any BT data on the RIO link.
see the section Determining Tbtx on page A-8
Tadp
The adapter throughput delay. For a 1747-ASB, this is two ASB backplane scan times.
adapter user manual
TSNo-bt
Scanner output delay time with BTs present see the section Determining TSNo-bt on page A-7
TSNi
The scanner module input delay time (ms)
5 ms (constant value for all formulas in this appendix)
Tid
The input module delay time I/O product data and I/O (ms) instruction sheets
Tod
The output module delay time (ms)
I/O product data and I/O instruction sheets
Determining TSNo-bt Use the following table to find TSNo-bt for your particular configuration.
IMPORTANT
The times shown are, to the best of our knowledge, the maximum delay times of the scanner. However, in instances that throughput is an important consideration, test the application thoroughly first to ensure proper operation. Note that in most situations the average throughput is much better than the calculated maximum throughput.
Publication 1747-UM013B-EN-P - January 2005