What is in it
User manual for the Allen-Bradley 1747-SN Remote I/O Scanner, the SLC module that exchanges discrete and block transfer data between an SLC processor and remote adapters on the RIO link. It explains how the scanner works, gives a quick start, covers installation, baud rate selection and RIO link wiring, configuration with G and M files in RSLogix 500, block transfer (BTR and BTW) programming, troubleshooting and error codes, and specifications with throughput calculations.
Its parts
- Overview
- Quick Start for Experienced Users
- Installation and Wiring
- Scanner Configuration and Programming
- RIO Block Transfer
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley user manual for the 1747-SN Remote I/O Scanner, the module that links an SLC 500 processor to remote chassis and devices over the Remote I/O link. It covers baud rate setup, installing the module, wiring the link, configuration and block transfers, status lights, error codes and specifications.
- What it is
- Remote I/O scanner for the SLC 500; master of the Remote I/O link p. 9
- Processor
- SLC 5/02 or later p. 9
- Chassis slot
- Any slot of the local SLC chassis except slot 0 p. 9
- Capacity
- Up to 4 logical racks (32 input and 32 output image words) p. 10
- Baud rates
- 57.6, 115.2 or 230.4 Kbaud, set by DIP switch p. 26
- Cable length
- Belden 9463: 3048 m (10,000 ft) at 57.6K, 1524 m (5000 ft) at 115.2K, 762 m (2500 ft) at 230.4K baud p. 97
- Backplane current
- 600 mA at 5V dc p. 97
- Operating temperature
- 0 to 60 C (32 to 140 F) p. 97
- Storage temperature
- -40 to 85 C (-40 to 185 F) p. 97
- Humidity
- 5 to 95% without condensation p. 97
- Link connector
- 3-pin male; repair part number 1746-RT29 p. 27
- Error codes
- 62H G file missing; 63H invalid configuration; 64H duplicate node; 68H to 6FH scanner hardware p. 96
- Status lights
- Red FAULT LED and red/green COMM LED p. 27
- Slot filler
- Card Slot Filler 1746-N2 for unused slots p. 37
What this manual walks you through
- Setting the baud rate DIP switches p. 36
- Inserting and removing the scanner in the SLC chassis p. 37, 38
- Wiring the RIO link and terminating resistors p. 39
- Grounding the cable shield, new installs and Series A retrofits p. 40, 41
- Starting up the RIO system p. 41, 42
- Reading the FAULT and COMM status LEDs p. 43
- Troubleshooting by LED state and error code p. 95, 96
- Checking retry counters in noisy environments p. 96
- RIO network throughput p. 98
Good to know
- All devices on the RIO link must use the same baud rate. p. 26
- Extended node works only if every device on the link supports it. p. 39
- Ground the RIO cable shield at the scanner end only. p. 41
- Disconnect system power before installing, removing or wiring the scanner. p. 37
- Block transfers may not work on adapters set to Hold Last State. p. 43
Questions this manual answers
What does error code 62H mean on a 1747-SN?
The G file is missing; enter the configuration information in the G file. p. 95
How much backplane current does the 1747-SN draw?
600 mA at 5V dc, so check that the SLC power supply has enough reserve. p. 37
How long can the 1747-SN remote I/O cable be?
Up to 3,048 meters (10,000 feet) end to end at 57.6K baud; shorter at higher baud rates. p. 10, 97
What part number is the 1747-SN RIO connector?
The 3-pin male RIO link connector has repair part number 1746-RT29. p. 27
Contents
Chapters and sections
Each line opens the PDF at its page.
- Important User Information2
- Summary of Changes3
- Overview9
- Quick Start for Experienced Users29
- Installation and Wiring35
- Scanner Configuration and Programming45
- Understanding Remote Input and Output Image Files45
- RIO Configuration Using G Files48
- Considerations When Configuring Remote I/O56
- Understanding M Files58
- Device Reset and Remote Output Reset Considerations65
- M1 Status File Description67
- RIO Communication Retry Counter (M1:e.16 -47)74
- Understanding Slot Addressing76
- SLC/Scanner Configuration77
- RIO Block Transfer79
- Troubleshooting95
- Specifications97
13 more lines, from page 97 on
The whole text · 21 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Table of Contents5-8
- Overview, pages 9 to 189-18
- Overview, pages 19 to 2819-28
- Quick Start for Experienced Users29-34
- Installation and Wiring35-44
- Scanner Configuration and Programming, pages 45 to 5345-53
- Scanner Configuration and Programming, pages 54 to 6254-62
- Scanner Configuration and Programming, pages 63 to 7163-71
- Scanner Configuration and Programming, pages 72 to 7872-78
- RIO Block Transfer, pages 79 to 8679-86
- RIO Block Transfer, pages 87 to 9487-94
- Pages 95 to 10395-103
- Pages 104 to 112104-112
- M0 - M1 Files and G Files113-126
- Pages 127 to 135127-135
- Pages 136 to 144136-144
- Pages 145 to 153145-153
- Pages 154 to 160154-160
- Glossary161-164