Page 9

Chapter

1

Overview

This chapter contains the following information: • system overview • how the scanner interacts with the SLC processor • how the scanner interacts with adapter modules • scanner I/O image concepts • extended node capability • complementary I/O • scanner features • compatible network devices

System Overview

The Remote I/O (RIO) Scanner, Catalog Number 1747-SN, is the remote I/O scanner for the SLC 500. It enables communication between an SLC processor (SLC 5/02 or later) and remotely located (3,048 meters [10,000 feet] maximum) 1746 I/O chassis and other RIO compatible Allen-Bradley operator interface and control devices. The 1747-SN Scanner communicates with remotely located devices using the Allen-Bradley Remote I/O link. The RIO link consists of a single master (scanner) and multiple slaves (adapters). Communication between devices occurs over twisted pair cable with the devices daisy-chained together. The scanner can reside in any slot of the local SLC chassis except for slot 0. The Remote I/O (RIO) Scanner, Catalog Number 1747-SN, is the remote I/O scanner for the SLC 500. It enables communication between an SLC processor (SLC 5/02 or later) and remotely located (3,048 meters [10,000 feet] maximum) 1746 I/O chassis and other RIO compatible Allen-Bradley operator interface and control devices. The 1747-SN Scanner communicates with remotely located devices using the Allen-Bradley Remote I/O link. The RIO link consists of a single master (scanner) and multiple slaves (adapters). Communication between devices occurs over twisted pair cable with the devices daisy-chained together. The scanner can reside in any slot of the local SLC chassis except for slot 0.

1

Publication 1747-UM013B-EN-P - January 2005

Page 10

1-2

Overview

RIO Scanner (Master of the RIO Link)

SLC 5/02 or Later Processor

The scanner transfers input and output data between itself and all configured network devices over twisted pair cable. Note that the end-to-end length of the cable can be a maximum of 3,048 meters (10,000 feet).

Local SLC Chassis

1747-ASB Module (Adapter/Slave)

Remote Chassis Remote Expansion Chassis

Dataliner Message Display (Adapter/Slave)

PanelView Operator Terminal (Adapter/Slave)

RediPANEL (Adapter/Slave)

The scanner can be configured for and transfer a maximum of 4 logical racks of discrete data on the RIO link. The scanner provides discrete I/O and block (Series B or later) transfers. Configurations allowed are any combination of quarter, half, three-quarter, or full logical rack devices.

SLC 5/02 or Later Processor

RIO Scanner The scanner transfers discrete input and output data between itself, remote adapters, and the SLC processor. . Remote adapters consist of 1746 chassis and other Allen-Bradley operator interface and control devices.

Adapter 1

Adapter 2

Adapter 3

Adapter 4

Adapter 5

Adapter 6

Half Logical Rack Device

Quarter Logical Rack Device

Half Logical Rack Device

Three-Quarter Logical Rack Device

Full Logical Rack Device

Full Logical Rack Device

The SLC processor transfers the scanner’s 4 logical racks (32 input image and 32 output image words) of discrete remote I/O image data into the SLC input and output image files. You can adjust the size of the scanner input and output image file during configuration of your SLC system so that the scanner only transfers the discrete I/O data Publication 1747-UM013B-EN-P - January 2005

Page 11

Overview

1-3 your application program requires. Configuration is done through the confiGuration file (G file). Refer to Chapter 4, Configuration and Programming, for more information.

IMPORTANT

The SLC 500 processor (SLC 5/02 or later) supports multiple scanners in its local I/O chassis. The maximum number is dependent on the following: • backplane power requirements (power supply dependent) • SLC 500 processor I/O data table limit (4,096 I/O) • processor memory to support the application (SLC 500 processor dependent)

Scanner I/O Image Division The scanner allows each adapter to use a fixed amount (user defined) of the scanner’s input and output image. Part of the SLC processor’s image is used by local I/O, the other portion is used by the scanner for remote I/O. The scanner remote I/O image is divided into logical racks and further divided into logical groups. A full logical rack consists of eight input and eight output image words. A logical group consists of one input and one output word in a logical rack. Each logical group is assigned a number from 0 to 7.

Local I/O

Logical Rack 0

Logical Rack 1 Remote I/O (Scanner Image)

Logical Group 0 Logical Rack 2 Logical Group 7

Processor I/O Image

Scanner I/O Image

Adapter Image

Publication 1747-UM013B-EN-P - January 2005

Page 12

1-4

Overview

The scanner image contains the image of each adapter on the RIO link. The adapter is assigned a portion of the scanner image, which is referred to as the adapter image.

How the Scanner Scans Remote I/O

The scanner communicates with each logical device in a sequential fashion. First, the scanner initiates communication with a device by sending output data to the device. The device then responds by sending its input data back to the scanner, as illustrated below. You refer to this exchange as a discrete I/O transfer. After the scanner completes its discrete I/O transfer with the last configured network device, it begins another discrete I/O transfer with the first device. It is important to understand that the scanner transfers RIO data on a logical device basis not on an adapter basis. A logical device is a full logical rack or portion of a logical rack assigned to an adapter.

RIO Scanner Scan The scanner updates its input image file each time it scans a logical device.

Scanner Input Image File

Output Device 3

Input Device 3

Output Device 2

Input Device 1

Output Device 1 Input Device 2

Scanner Output Image File

SLC and Scanner Asynchronous Operation The SLC processor scan and RIO scanner scan are independent (asynchronous) of each other. The SLC processor reads the scanner input image file during its input scan and writes the output image file to the scanner during its output scan. The RIO scanner continues reading inputs and writing outputs to the scanner I/O image file, independent of the SLC processor scan cycle. Depending on your SLC processor, RIO link configuration, and application program size, the scanner may complete multiple scans before the SLC processor reads the scanner’s input image file. The RIO scanner updates its I/O files on a per logical rack basis. Publication 1747-UM013B-EN-P - January 2005

Page 13

Overview

1-5

The figure below illustrates the asynchronous operation of the SLC processor and RIO scanner.

SLC Processor Scan Cycle

RIO Scanner Scan Cycle

SLC Input Image File The SLC processor reads the scanner input image file into the SLC input image file, processes it, and creates an SLC output image file. The SLC processor transfers its output file to the scanner..

Scanner Input Image File

Output Image Device 3

Input Image Device 3

Program

Output Image Device 2

SLC Processor

SLC Output Image File

Input Image Device 1 The scanner updates its input image file each time Output it scans a logical device. Image The scanner may scan all Device 1 of its configured logical devices several times before the SLC processor Input reads the scanner's input Image image file. Device 2

Scanner Output Image File

Important: The outputs of the RIO are updated after the end of the first SLC processor scan.

How the Scanner Interacts with Adapters

The scanner’s function is to continuously scan the adapters on the RIO link in a consecutive manner. This scan consists of one or more RIO discrete transfers to each adapter on the RIO link. RIO discrete transfers consist of the scanner sending output image data and communication commands to the adapter that instruct the adapter on how to control its output. (These include run, adapter reset, and reset decide commands.) The adapter responds by sending input data to the scanner. The scanner performs as many RIO discrete transfers as necessary to update the entire adapter image. If RIO discrete transfers do not occur, data is not exchanged between the scanner and adapter. RIO discrete transfers are asynchronous to the processor scan.

Publication 1747-UM013B-EN-P - January 2005

Page 14

1-6

Overview

Processor

Scanner

RIO Discrete Transfers with Adapter 1 SLC Local Chassis RIO Discrete Transfers with Adapter 2 PanelView Operator Terminal RIO Discrete Transfers with Adapter 3

RIO Discrete Transfers with Adapter 4

Scanner I/O Image Concepts

RediPANEL

The scanner’s I/O image consists of RIO logical racks and I/O groups. A full RIO logical rack consists of eight input image and eight output image words. (A word consists of 16 bits of data.) Each word within an RIO logical rack is assigned an I/O group number from 0 to 7. You assign devices on the RIO link a portion of the scanner’s image. Devices can occupy a quarter logical rack (2 input and output words), half logical rack (4 I/O words), three-quarter logical rack (6 I/O words), or full logical rack. You may configure devices to start at any even I/O group number within an RIO logical rack. More than one physical device’s (adapter) I/O information can reside in a single logical rack. Also, by crossing logical rack boundaries, a device can consist of more than one logical rack.

IMPORTANT

Publication 1747-UM013B-EN-P - January 2005

The following illustration shows only the input image configuration of the scanner’s I/O image. The output image configuration is the same.

Page 15

Overview

1-7

Input Image Half of a Scanner 's I/O Image Bit Number (decimal)

RIO Logical Rack 0

RIO Logical Rack 1

RIO Logical Rack 2

RIO Logical Rack 3

Rack 0 Group 0

Word 0

Rack 0 Group 1

Word 1 Word 2

Rack 0 Group 2 Rack 0 Group 3

Word 3

Rack 0 Group 4

Word 4

Rack 0 Group 5 Rack 0 Group 6

Word 5 Word 6

Rack 0 Group 7

Word 7

Rack 1 Group 0

Word 8

Rack 1 Group 1

Word 9

Rack 1 Group 2

Word 10

Rack 1 Group 3

Word 11

Rack 1 Group 4

Word 12

Rack 1 Group 5

Word 13

Rack 1 Group 6 Rack 1 Group 7 Rack 2 Group 0

Word 14 Word 15 Word 16

Rack 2 Group 1

Word 17

Rack 2 Group 2

Word 18

Rack 2 Group 3

Word 19

Rack 2 Group 4 Rack 2 Group 5

Word 20 Word 21

Rack 2 Group 6

Word 22

Rack 2 Group 7

Word 23

Rack 3 Group 0

Word 24

Rack 3 Group 1

Word 25

Rack 3 Group 2

Word 26

Rack 3 Group 3

Word 27

Rack 3 Group 4

Word 28

Rack 3 Group 5 Rack 3 Group 6

Word 29 Word 30

Rack 3 Group 7

Word 31

Bit Number (octal)

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Quarter Logical Rack Not Used In This Example

Half Logical Rack Not Used In This Example

Three-Quarter Logical Rack

Not Used In This Example

Full Logical Rack

17 8

16 8

15 8

14 8

13 8

12 8

11 8

10 8

78

68

58

48

38

28

18

08

Example Scanner I/O Image The illustrations below show a scanner’s input image of 4 RIO link devices.

Publication 1747-UM013B-EN-P - January 2005

Page 16

1-8

Overview

SLC 5/02 or Later Processor RIO Scanner

Device 2

Device 1

Three-Quarter Logical Rack Device Begins at Logical Rack 1, Group 0.

Full Logical Rack Device Begins at Logical Rack 0, Group 0.

Device 3

Device 4

Half Logical Rack Device Begins at Logical Rack 2, Group 0.

Quarter Logical Rack Device Begins at Logical Rack 2, Group 4.

Important: The illustration below shows only the scanner's input image. The output image looks the same. Bit Number Rack 0 Group 0

Word 1

Rack 0 Group 2

Word 2

13

12

11

10

9

8

7

6

5

4

3

2

1

0

17 8

16 8

15 8

14 8

13 8

12 8

11 8

10 8

78

68

58

48

38

28

18

08

Word 3 Word 4 Word 5 Word 6

Rack 0 Group 7

Word 7

Rack 1 Group 0

Word 8

Rack 1 Group 1

Word 9

1 Group 2 RIO Rack Rack 1 Group 3 Logical Rack 1 Group 4 Rack 1 Rack 1 Group 5

Word 10

Rack 1 Group 6 Rack 1 Group 7 Rack 2 Group 0

Word 14 Word 15 Word 16

Word 11 Word 12 Word 13

Rack 2 Group 1

Word 17

RIO Rack 2 Group 2 Rack 2 Group 3 Logical Rack 2 Group 4 Rack 2 Rack 2 Group 5

Word 18

Rack 2 Group 6

Word 22

Rack 2 Group 7

Word 23

Word 19 Word 20 Word 21

Rack 3 Group 0

Word 24

Rack 3 Group 1

Word 25

RIO Rack 3 Group 2 Rack 3 Group 3 Logical Rack 3 Group 4 Rack 3 Rack 3 Group 5

14

Word 0

Rack 0 Group 1

RIO Rack 0 Group 3 Rack 0 Group 4 Logical Rack 0 Group 5 Rack 0 Rack 0 Group 6

15

Word 26 Word 27 Word 28

Rack 3 Group 6

Word 29 Word 30

Rack 3 Group 7

Word 31

Bit Number (octal)

e = slot number of the SLC chassis containing the scanner

Publication 1747-UM013B-EN-P - January 2005

InputFile Address I:e.0 I:e.1 I:e.2 I:e.3 Device1 I:e.4 I:e.5 I:e.6 I:e.7 I:e.8 I:e.9 I:e.10 Device 2 I:e.11 I:e.12 I:e.13 I:e.14 Not Used I:e.15 I:e.16 I:e.17 Device 3 I:e.18 I:e.19 I:e.20 Device 4 I:e.21 I:e.22 I:e.23 I:e.24 I:e.25 I:e.26 I:e.27 Not Used I:e.28 I:e.29 I:e.30 I:e.31

Page 17

Overview

1-9

Transferring Data with RIO Discrete and Block Transfers Input and output image data and command information are quickly exchanged between a scanner and adapter using RIO discrete transfers. RIO discrete transfers are the simplest and fastest way a scanner and adapter communicate with each other. RIO discrete transfers, which are transparent to the user, consist of the scanner sending the output image data to the adapter, and the adapter transmitting input data to the scanner. Each RIO discrete transfer also contains scanner commands for the adapter. Through your control program, you command the SLC processor to initiate RIO block transfers, which directs the scanner to exchange large amounts of data to/from an adapter. Block Transfers (BTs) use the basic RIO discrete transfer mechanism of the RIO link. However, the actual transfer of data occurs asynchronous to the discrete transfers. It is possible for several discrete transfers to occur before the scanner processes a block transfer. Refer to Chapter 5, RIO Block Transfer for more details.

Physical and Logical RIO Link Specifications The maximum number of adapters with which your scanner can communicate is determined by the scanner’s and adapter’s physical and logical specifications, as described below: • Physical Specifications are the maximum number of adapters that can be connected to the scanner. For more information, see Extended Node Capability below. • Logical Specifications for the scanner are the maximum number of logical racks the scanner can address, how the logical racks can be assigned, and whether the scanner can perform BTs.

Extended Node Capability Extended node functionality allows you to connect up to 32 physical devices on an RIO link. You must use 82 Ohm RIO link resistors in an extended node configuration. You can only use extended node if all RIO link devices have extended node capability. (Refer to the Compatible Devices table at the end of this chapter, or to the specifications of your device.) The 1747-SN Series B Scanner has extended node capability. However, the smallest logical rack division is 1/4 logical rack and the scanner image size is 4 logical racks. Therefore, the scanner is limited to 16 devices unless complementary

Publication 1747-UM013B-EN-P - January 2005

Page 18

1-10

Overview

I/O is used. Refer to the following section for more information on complementary I/O.

Complementary I/O Complementary I/O is very useful when portions of your input and output images are unused because it allows the images of two adapters to overlap each other in the scanner’s I/O image. To use complementary I/O, the I/O image from one adapter must be the mirror (complement) of the other. This means that there must be an input module in the primary chassis and an output module in the same slot of the complementary chassis. This enables total use of the scanner’s 32 input and 32 output word image for I/O addressing of up to 1024 discrete points.

ATTENTION

Because the primary and complementary chassis images overlap, input and specialty combination I/O modules must never share the same image location. Inputs received by the scanner may be incorrect and RIO block transfers will not be serviced properly. If an output module shares its output image with another output module, both output modules receive the same output information.

If you want to use complementary I/O, two adapters that support this function are required (e.g., 1747-ASB modules). One adapter is configured (via its DIP switches) as a primary chassis, the other as a complementary chassis. If a primary chassis exists, it is scanned first. Primary and complementary chassis cannot have the same logical rack number. The logical rack numbers must be assigned to the primary and complementary racks as shown below:

Publication 1747-UM013B-EN-P - January 2005

Primary Chassis Logical Rack Number

Complementary Chassis Logical Rack Number Decimal

Octal

0

8

10

1

9

11

2

10

12

3

11

13