Page 19
Overview
ATTENTION
1-11
If the logical rack numbers are not properly assigned, unpredictable operation of both ASB modules results. No ASB module errors occur. Refer to your ASB module user manual for specific information on setting the address of the complementary chassis. (For example, in the 1771-ASB manual the addresses for the complementary chassis are referred to as complementary chassis 0-3.)
Guidelines for Configuring Complementary I/O When you configure your remote system for complementary I/O, follow these guidelines: • You can place an output module in the primary chassis opposite another output module in the complementary chassis; they use the same bits in the output image table. However, we do not recommend this placement of modules for redundant I/O. • You cannot use complementary I/O with a chassis that uses 32-point I/O modules and 1-slot addressing or 16-point I/O modules with 2-slot addressing. • Do not place an input module in the primary chassis opposite an input module in the complementary chassis; they will use the same bits in the input image table.
Publication 1747-UM013B-EN-P - January 2005
Page 20
1-12
Overview
Complementary I/O: Placing Modules with 2-Slot Addressing The following figures illustrate a possible module placement to configure complementary I/O using 2-slot addressing.
Example 1
I
I 8
8
O 8
O 8
I
O 16
16
O 8
O 8 1
0
O 8
1
O 8
I
2
I 8
8
E M P T Y
BT
8 O 8
O 8
1 3
E M P T Y
I
BT
O 8
4
E M P T Y
O 8 1
1
16
O 16
5
E M P T Y
O 8 2
2
16
O I 16 16
E M P T Y 2
2
Example 2
I
O 16
16
0
I
O I 16 16
16
1
O 16
2
I
3
I
4
O 16
5
Outputs in the complementary chassis would use the same bits in the output image table as the outputs in the primary chassis. You cannot place inputs in the complementary chassis.
1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is a block transfer module. Important: With 2-slot addressing, if an input module resides in either slot associated with a logical group of the primary chassis, an input module cannot reside in that logical group' s complementary chassis.
Publication 1747-UM013B-EN-P - January 2005
Page 21
Overview
1-13
Complementary I/O: Placing Modules with 1-Slot Addressing The figure below illustrates a possible module placement to configure complementary I/O using 1-slot addressing.
Example 1
I 16
I 16
O 16
O 16
I 16
O 16
O 16
BT
I 16
O 16
O 16
I 16
7
0
1
2
3
O 16
I 16
I 16
O 16
1 0
O 16
1
O 16
2
I 16
3
I 16
4
O 16
5
I 16
6
O 16
E M P T Y
1
2
Example 2
I 16
I 16
I 16
I 16
I 16
I 16
I 16
I 16
I 16
I 16
I 16
I 16
0
1
2
3
4
5
6
7
0
1
2
3
O 16
O 16
O 16
O 16
O 16
O 16
O 16
O 16
O 16
O 16
O 16
O 16
I = Input Module (8- or 16-point) O = Output Module (8- or 16-point) BT = Block Transfer Module 1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is block transfer. .
Publication 1747-UM013B-EN-P - January 2005
Page 22
1-14
Overview
Complementary I/O: Placing Modules with 1/2-Slot Addressing The figure below illustrates a possible module placement to configure complementary I/O using 1-slot addressing.
Example 1
I
I
O
O
I
O
O
BT
O
I
45
67
01
23
O
E M P T Y
I
O
1 01
O
23
O
45
I
67
I
01
O
23
I
2
1 Example 2
I
I
I
I
I
I
I
I
I
I
01
23
45
67
01
23
45
67
01
23
O
O
O
O
O
O
O
O
O
O
I = Input Module (8-, 16-, or 32-point) O = Output Module (8-, 16-, or 32-point) BT = Block Transfer Module 1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is block transfer .
Publication 1747-UM013B-EN-P - January 2005
Page 23
Overview
1-15
Summary for Placing Modules Used In Complementary I/O Discrete Modules
Addressing Method
Types of Modules used
Placement
2-slot
8-point
Install input modules opposite output modules, and output modules opposite input modules.(1)
1-slot
8-point, 16-point
1/2-slot
8-point, 16-point, 32-point
(1) If an input module resides in either slot associated with a logical group of the primary chassis, an input module cannot reside in that logical group’s complementary chassis.
Block Transfer Modules
Addressing Method
Placement
2-slot
The right slot of the primary I/O group can be another block transfer module, or an 8-point input or output module. The left slot of the complementary I/O group must be empty. In the right slot of the complementary I/O group, you can place an 8-point output module; this slot must be empty if the corresponding slot in the primary I/O group is a block transfer module.
1-slot
Leave the corresponding I/O group in the complementary chassis empty.
1/2-slot
Leave the corresponding I/O group in the complementary chassis empty.
The following example illustrates how I/O modules requiring two words of the input or output image can leave unused image space.
Publication 1747-UM013B-EN-P - January 2005
Page 24
1-16
Overview
O I O I
I
O I
O
O I
O I O I
O I
1
3
7
I = Input Module O = Output Module
Slot
0
Slot Pair
1
2
1
3
4
2
5
6
7
3
8
Slot 0
4
Slot Pair
Primary Chassis Configured As: Logical Rack Number 0 Logical Group Number 0 Image Size (logical groups) 16 Addressing Mode 1/2-slot Primary/Complementary Primary
InputImage from Primary Chassis Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
5
6
3
8
4
Complementary Chassis Configured As: Logical Rack Number 8 (decimal) Logical Group Number 0 Image Size (logical groups) 16 Addressing Mode 1/2-slot Primary/Complementary Complementary
Primary Chassis I/O Image 10 8
4
2
Complementary Chassis
Primary Chassis
17 15
2
1
7 7
0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
Octal Decimal
1
2 Slot Pair
3
4
Complementary Chassis I/O Image
Output Image from Primary Chassis 17 15
10 8
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
7 7
0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
InputImage Output Image from Complementary Chassis from Complementary Chassis 17 15
Octal Decimal
10 8
7 7
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
1
2 Slot Pair
3
4
0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
Octal Decimal
1
2 Slot Pair
3
4
= unused image space
Input Image
Scanner's I/O Image Both images are overlapped in the scanner. The overlapped image appears where the primary chassis image is configured to reside. In this case, the primary chassis image is configured as starting logical rack 0 and starting logical group 0.
17 15
Logical Rack 0
Logical Rack 1
Publication 1747-UM013B-EN-P - January 2005
Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7
10 8
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
7 7
Output Image 0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
Octal Decimal
1
2 Slot Pair
3
4
17 15
10 8
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
7 7
0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
Octal Decimal
1
2 Slot Pair
3
4
17 15
10 8
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
7 7
0 0
Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8
Octal Decimal
1
2 Slot Pair
3
4
Page 25
Overview
1-17
Complementary I/O Application Considerations If you configure a complementary device to use more I/O image space than an associated primary device, then block transfers can only be performed to locations in the complementary device that have associated I/O image space in the primary device. For example, if a primary device is 1/2 logical rack and a complementary device is a full logical rack, block transfers can be performed only in the first 1/2 logical rack of the complementary device. Attempting block transfers in the last half of the complementary device will result in a BT error (error - 11 - device not configured).
Logical Rack 0
Word 0 Word 1 Word 2 Word 3 Word 4 Word 5 Word 6 Word 7
1/2 logical rack configured and usable
Logical Rack 8 1/2 logical rack not configured
1/2 1/2logical logicalrack rack usa configured configured andand usable
Word 0 Word 1 Word 2 Word 3 Word 4 Word 5 Word 6 Word 7
1/2 logical rack 1/2 logical rackbut not configured, usable forbut BTnot since configured, Wordsfor4-7 usable BT are sincenot configured for the Words 4 todevice. 7 are not primary configured for the primary device.
Complementary 1771 I/O Module Details Use the following modules in either primary or complementary I/O chassis opposite any type of module: • Communication Adapter Module (1771-KA2) • Communication Controller Module (1771-KE) • PLC-2 Family/RS-232-C Interface Module (1771-KG) • Fiber Optics Converter Module (1771-AF) • DH/DH+ Communication Adapter Module (1785-KA) • DH+/RS-232C Communications Interface Module (1785-KE) Use the following modules in either primary or complementary I/O chassis opposite any type of module. However, these modules do not work as stand-alone modules; each one has an associated master module. Use care when placing the master modules in the I/O chassis: • Analog Input Expander Module (1771-E1, -E2, -E3) • Analog Output Expander Module (1771-E4) • Servo (Encoder Feedback) Expander Module (1771-ES) • Pulse Output Expander Module (1771-OJ) Publication 1747-UM013B-EN-P - January 2005
Page 26
1-18
Overview
Hardware Features
Below are the scanner’s features. You can find LED information in Chapter 6, Troubleshooting.
SCANNER CAT SER
FAC
)
SLC 500 Remote I/O Scanner
SERIAL NO.
COMM FAULT
SW1 O 1 2 N
UL LISTED IND. CONT. EQ. SA )
/
FOR HAZ. LOC. A196
2 HOST FRN.:
1
2
ON
ON
KBAUD 57.6
ON
OFF
115.2
OFF ON
230.4
OFF OFF
230.4
CONNECT ONE END OF CABLE SHIELD TO CHASSIS MOUNTING BOLT. REFER T O USER'S MANUAL.
MAKE IN U.S.A.
PLUG FRN.: CURRENT REQUIREMENT: 600 mA @5VDC
OPERATING TEMPERATURE CODE T3C
CLASS I, GROUPS A, B, C AND D, DIV.2 B
1
LINE 1 SHIELD LINE 2
1747±SN
3
O N
7
12
4
6
5
1. Status Led
Displays normal communication and fault status
2. Front Label
Allows user to record configured baud rate
3. RIO Link Connector
Allows for connections to RIO link devices
4. Cable Tie Slots
Secures communication wiring from module
5. Self-Locking Tabs
Secures module in chassis slot
6. Side Label (Nameplate)
Provides module information
7. Baud Rate DIP Switch
Allows user to set baud rate
Baud Rate DIP Switch The Baud Rate DIP switch selects the RIO link baud rate. The baud rates are: • 57.6 Kbaud • 115.2 Kbaud • 230.4 Kbaud
IMPORTANT
Publication 1747-UM013B-EN-P - January 2005
For proper system operation, the baud rate of all devices on the RIO link must be the same.
Page 27
Overview
1-19
LEDs Two LEDs allow you to monitor scanner and communication status. FAULT LED - allows you to monitor scanner status. This LED is red. The FAULT LED’s normal state is off; therefore, it is off whenever the scanner is operating properly. COMM LED - allows you to monitor communication with all configured devices. This LED is green and its normal state is on once the processor has entered Run mode. The LED is red if there is a communication problem. The COMM LED status information is valid only when the FAULT LED is off.
RIO Link Connector This 3-pin male connector connects the scanner to the RIO link. The Allen-Bradley repair part number is 1746-RT29.
Compatible Devices
Catalog Number
Device
Comments
1785-LT/x(1) (2)
PLC- 5/15 (in adapter mode)
-
1785-LT2(1)(2)
PLC- 5/25 (in adapter mode)
-
1785-LT3(1)(2)
PLC- 5/12 (in adapter mode)
-
1785-L30x(1)(2)
PLC- 5/30 (in adapter mode)
-
1785-L40x(1)(2)
PLC- 5/40 (in adapter mode)
-
1785-L60x(1)(2)
PLC- 5/60 (in adapter mode)
-
1771-ASC
Remote I/O Adapter Module
-
1771-ASB(3) (4)
Remote I/O Adapter Module
-
1771-AM1(1)
1-Slot I/O Chassis W/Integral Power Supply and Adapter
-
1771-AM2(1)
2-Slot I/O Chassis W/Integral Power Supply and Adapter
-
1784-F30D(1)
Plant Floor Terminal Remote I/O Expansion Module
-
1771-RIO
Remote I/O Interface Module
-
Publication 1747-UM013B-EN-P - January 2005
Page 28
1-20
Overview
Catalog Number 1771-JAB
(1)
Device
Comments
Single Point I/O Adapter Module Single Point I/O Adapter Module
1771-DCM
Direct Communication Module
-
1778-ASB(1)
Remote I/O Adapter Module
-
1747-DCM(1)
Direct Communication Module
-
2706-xxxx(1)(5)
DL40 Dataliner
-
2705-xxx(1)
RediPANEL
Requires half logical rack configuration if you want to use stored messages.Requires half logical rack configuration if you want to use stored messages.
2711-xx(1)
PanelView Terminal
You can address PanelView Terminals as up to four full logical racks of discrete I/O. You can also assign partial logical racks.You can address PanelView Terminals as up to four full logical racks of discrete I/O. You can also assign partial logical racks.
1336-G2(1)
Remote I/O Adapter for 1336 AC Industrial Drives
-
1395-NA(1)
Remote I/O Adapter for 1395 DC Industrial Drives
-
1791-xxx
Block I/O Products
The adapter is built into the block.
1747-ASB(1)
SLC 500 Remote I/O Adapter Module
-
1794-ASB
Flex I/O 24VDC Remote I/O Adapter
-
(1) Extended node capability (2) In adapter mode (3) Series A, B, and C (4) Extended node capability for Series B and C (5) Must be Catalog Number 2706-ExxxxxB1
Publication 1747-UM013B-EN-P - January 2005