Page 19

Overview

ATTENTION

1-11

If the logical rack numbers are not properly assigned, unpredictable operation of both ASB modules results. No ASB module errors occur. Refer to your ASB module user manual for specific information on setting the address of the complementary chassis. (For example, in the 1771-ASB manual the addresses for the complementary chassis are referred to as complementary chassis 0-3.)

Guidelines for Configuring Complementary I/O When you configure your remote system for complementary I/O, follow these guidelines: • You can place an output module in the primary chassis opposite another output module in the complementary chassis; they use the same bits in the output image table. However, we do not recommend this placement of modules for redundant I/O. • You cannot use complementary I/O with a chassis that uses 32-point I/O modules and 1-slot addressing or 16-point I/O modules with 2-slot addressing. • Do not place an input module in the primary chassis opposite an input module in the complementary chassis; they will use the same bits in the input image table.

Publication 1747-UM013B-EN-P - January 2005

Page 20

1-12

Overview

Complementary I/O: Placing Modules with 2-Slot Addressing The following figures illustrate a possible module placement to configure complementary I/O using 2-slot addressing.

Example 1

I

I 8

8

O 8

O 8

I

O 16

16

O 8

O 8 1

0

O 8

1

O 8

I

2

I 8

8

E M P T Y

BT

8 O 8

O 8

1 3

E M P T Y

I

BT

O 8

4

E M P T Y

O 8 1

1

16

O 16

5

E M P T Y

O 8 2

2

16

O I 16 16

E M P T Y 2

2

Example 2

I

O 16

16

0

I

O I 16 16

16

1

O 16

2

I

3

I

4

O 16

5

Outputs in the complementary chassis would use the same bits in the output image table as the outputs in the primary chassis. You cannot place inputs in the complementary chassis.

1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is a block transfer module. Important: With 2-slot addressing, if an input module resides in either slot associated with a logical group of the primary chassis, an input module cannot reside in that logical group' s complementary chassis.

Publication 1747-UM013B-EN-P - January 2005

Page 21

Overview

1-13

Complementary I/O: Placing Modules with 1-Slot Addressing The figure below illustrates a possible module placement to configure complementary I/O using 1-slot addressing.

Example 1

I 16

I 16

O 16

O 16

I 16

O 16

O 16

BT

I 16

O 16

O 16

I 16

7

0

1

2

3

O 16

I 16

I 16

O 16

1 0

O 16

1

O 16

2

I 16

3

I 16

4

O 16

5

I 16

6

O 16

E M P T Y

1

2

Example 2

I 16

I 16

I 16

I 16

I 16

I 16

I 16

I 16

I 16

I 16

I 16

I 16

0

1

2

3

4

5

6

7

0

1

2

3

O 16

O 16

O 16

O 16

O 16

O 16

O 16

O 16

O 16

O 16

O 16

O 16

I = Input Module (8- or 16-point) O = Output Module (8- or 16-point) BT = Block Transfer Module 1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is block transfer. .

Publication 1747-UM013B-EN-P - January 2005

Page 22

1-14

Overview

Complementary I/O: Placing Modules with 1/2-Slot Addressing The figure below illustrates a possible module placement to configure complementary I/O using 1-slot addressing.

Example 1

I

I

O

O

I

O

O

BT

O

I

45

67

01

23

O

E M P T Y

I

O

1 01

O

23

O

45

I

67

I

01

O

23

I

2

1 Example 2

I

I

I

I

I

I

I

I

I

I

01

23

45

67

01

23

45

67

01

23

O

O

O

O

O

O

O

O

O

O

I = Input Module (8-, 16-, or 32-point) O = Output Module (8-, 16-, or 32-point) BT = Block Transfer Module 1 = Output modules use the same output image table bits. This is not recommended. 2 = Must be empty if corresponding primary slot is block transfer .

Publication 1747-UM013B-EN-P - January 2005

Page 23

Overview

1-15

Summary for Placing Modules Used In Complementary I/O Discrete Modules

Addressing Method

Types of Modules used

Placement

2-slot

8-point

Install input modules opposite output modules, and output modules opposite input modules.(1)

1-slot

8-point, 16-point

1/2-slot

8-point, 16-point, 32-point

(1) If an input module resides in either slot associated with a logical group of the primary chassis, an input module cannot reside in that logical group’s complementary chassis.

Block Transfer Modules

Addressing Method

Placement

2-slot

The right slot of the primary I/O group can be another block transfer module, or an 8-point input or output module. The left slot of the complementary I/O group must be empty. In the right slot of the complementary I/O group, you can place an 8-point output module; this slot must be empty if the corresponding slot in the primary I/O group is a block transfer module.

1-slot

Leave the corresponding I/O group in the complementary chassis empty.

1/2-slot

Leave the corresponding I/O group in the complementary chassis empty.

The following example illustrates how I/O modules requiring two words of the input or output image can leave unused image space.

Publication 1747-UM013B-EN-P - January 2005

Page 24

1-16

Overview

O I O I

I

O I

O

O I

O I O I

O I

1

3

7

I = Input Module O = Output Module

Slot

0

Slot Pair

1

2

1

3

4

2

5

6

7

3

8

Slot 0

4

Slot Pair

Primary Chassis Configured As: Logical Rack Number 0 Logical Group Number 0 Image Size (logical groups) 16 Addressing Mode 1/2-slot Primary/Complementary Primary

InputImage from Primary Chassis Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

5

6

3

8

4

Complementary Chassis Configured As: Logical Rack Number 8 (decimal) Logical Group Number 0 Image Size (logical groups) 16 Addressing Mode 1/2-slot Primary/Complementary Complementary

Primary Chassis I/O Image 10 8

4

2

Complementary Chassis

Primary Chassis

17 15

2

1

7 7

0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

Octal Decimal

1

2 Slot Pair

3

4

Complementary Chassis I/O Image

Output Image from Primary Chassis 17 15

10 8

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

7 7

0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

InputImage Output Image from Complementary Chassis from Complementary Chassis 17 15

Octal Decimal

10 8

7 7

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

1

2 Slot Pair

3

4

0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

Octal Decimal

1

2 Slot Pair

3

4

= unused image space

Input Image

Scanner's I/O Image Both images are overlapped in the scanner. The overlapped image appears where the primary chassis image is configured to reside. In this case, the primary chassis image is configured as starting logical rack 0 and starting logical group 0.

17 15

Logical Rack 0

Logical Rack 1

Publication 1747-UM013B-EN-P - January 2005

Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7

10 8

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

7 7

Output Image 0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

Octal Decimal

1

2 Slot Pair

3

4

17 15

10 8

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

7 7

0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

Octal Decimal

1

2 Slot Pair

3

4

17 15

10 8

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

7 7

0 0

Slot 1 Slot 1 Slot 2 Slot 2 Slot 3 Slot 3 Slot 4 Slot 4 Slot 5 Slot 5 Slot 6 Slot 6 Slot 7 Slot 7 Slot 8 Slot 8

Octal Decimal

1

2 Slot Pair

3

4

Page 25

Overview

1-17

Complementary I/O Application Considerations If you configure a complementary device to use more I/O image space than an associated primary device, then block transfers can only be performed to locations in the complementary device that have associated I/O image space in the primary device. For example, if a primary device is 1/2 logical rack and a complementary device is a full logical rack, block transfers can be performed only in the first 1/2 logical rack of the complementary device. Attempting block transfers in the last half of the complementary device will result in a BT error (error - 11 - device not configured).

Logical Rack 0

Word 0 Word 1 Word 2 Word 3 Word 4 Word 5 Word 6 Word 7

1/2 logical rack configured and usable

Logical Rack 8 1/2 logical rack not configured

1/2 1/2logical logicalrack rack usa configured configured andand usable

Word 0 Word 1 Word 2 Word 3 Word 4 Word 5 Word 6 Word 7

1/2 logical rack 1/2 logical rackbut not configured, usable forbut BTnot since configured, Wordsfor4-7 usable BT are sincenot configured for the Words 4 todevice. 7 are not primary configured for the primary device.

Complementary 1771 I/O Module Details Use the following modules in either primary or complementary I/O chassis opposite any type of module: • Communication Adapter Module (1771-KA2) • Communication Controller Module (1771-KE) • PLC-2 Family/RS-232-C Interface Module (1771-KG) • Fiber Optics Converter Module (1771-AF) • DH/DH+ Communication Adapter Module (1785-KA) • DH+/RS-232C Communications Interface Module (1785-KE) Use the following modules in either primary or complementary I/O chassis opposite any type of module. However, these modules do not work as stand-alone modules; each one has an associated master module. Use care when placing the master modules in the I/O chassis: • Analog Input Expander Module (1771-E1, -E2, -E3) • Analog Output Expander Module (1771-E4) • Servo (Encoder Feedback) Expander Module (1771-ES) • Pulse Output Expander Module (1771-OJ) Publication 1747-UM013B-EN-P - January 2005

Page 26

1-18

Overview

Hardware Features

Below are the scanner’s features. You can find LED information in Chapter 6, Troubleshooting.

SCANNER CAT SER

FAC

)

SLC 500 Remote I/O Scanner

SERIAL NO.

COMM FAULT

SW1 O 1 2 N

UL LISTED IND. CONT. EQ. SA )

/

FOR HAZ. LOC. A196

2 HOST FRN.:

1

2

ON

ON

KBAUD 57.6

ON

OFF

115.2

OFF ON

230.4

OFF OFF

230.4

CONNECT ONE END OF CABLE SHIELD TO CHASSIS MOUNTING BOLT. REFER T O USER'S MANUAL.

MAKE IN U.S.A.

PLUG FRN.: CURRENT REQUIREMENT: 600 mA @5VDC

OPERATING TEMPERATURE CODE T3C

CLASS I, GROUPS A, B, C AND D, DIV.2 B

1

LINE 1 SHIELD LINE 2

1747±SN

3

O N

7

12

4

6

5

1. Status Led

Displays normal communication and fault status

2. Front Label

Allows user to record configured baud rate

3. RIO Link Connector

Allows for connections to RIO link devices

4. Cable Tie Slots

Secures communication wiring from module

5. Self-Locking Tabs

Secures module in chassis slot

6. Side Label (Nameplate)

Provides module information

7. Baud Rate DIP Switch

Allows user to set baud rate

Baud Rate DIP Switch The Baud Rate DIP switch selects the RIO link baud rate. The baud rates are: • 57.6 Kbaud • 115.2 Kbaud • 230.4 Kbaud

IMPORTANT

Publication 1747-UM013B-EN-P - January 2005

For proper system operation, the baud rate of all devices on the RIO link must be the same.

Page 27

Overview

1-19

LEDs Two LEDs allow you to monitor scanner and communication status. FAULT LED - allows you to monitor scanner status. This LED is red. The FAULT LED’s normal state is off; therefore, it is off whenever the scanner is operating properly. COMM LED - allows you to monitor communication with all configured devices. This LED is green and its normal state is on once the processor has entered Run mode. The LED is red if there is a communication problem. The COMM LED status information is valid only when the FAULT LED is off.

RIO Link Connector This 3-pin male connector connects the scanner to the RIO link. The Allen-Bradley repair part number is 1746-RT29.

Compatible Devices

Catalog Number

Device

Comments

1785-LT/x(1) (2)

PLC- 5/15 (in adapter mode)

-

1785-LT2(1)(2)

PLC- 5/25 (in adapter mode)

-

1785-LT3(1)(2)

PLC- 5/12 (in adapter mode)

-

1785-L30x(1)(2)

PLC- 5/30 (in adapter mode)

-

1785-L40x(1)(2)

PLC- 5/40 (in adapter mode)

-

1785-L60x(1)(2)

PLC- 5/60 (in adapter mode)

-

1771-ASC

Remote I/O Adapter Module

-

1771-ASB(3) (4)

Remote I/O Adapter Module

-

1771-AM1(1)

1-Slot I/O Chassis W/Integral Power Supply and Adapter

-

1771-AM2(1)

2-Slot I/O Chassis W/Integral Power Supply and Adapter

-

1784-F30D(1)

Plant Floor Terminal Remote I/O Expansion Module

-

1771-RIO

Remote I/O Interface Module

-

Publication 1747-UM013B-EN-P - January 2005

Page 28

1-20

Overview

Catalog Number 1771-JAB

(1)

Device

Comments

Single Point I/O Adapter Module Single Point I/O Adapter Module

1771-DCM

Direct Communication Module

-

1778-ASB(1)

Remote I/O Adapter Module

-

1747-DCM(1)

Direct Communication Module

-

2706-xxxx(1)(5)

DL40 Dataliner

-

2705-xxx(1)

RediPANEL

Requires half logical rack configuration if you want to use stored messages.Requires half logical rack configuration if you want to use stored messages.

2711-xx(1)

PanelView Terminal

You can address PanelView Terminals as up to four full logical racks of discrete I/O. You can also assign partial logical racks.You can address PanelView Terminals as up to four full logical racks of discrete I/O. You can also assign partial logical racks.

1336-G2(1)

Remote I/O Adapter for 1336 AC Industrial Drives

-

1395-NA(1)

Remote I/O Adapter for 1395 DC Industrial Drives

-

1791-xxx

Block I/O Products

The adapter is built into the block.

1747-ASB(1)

SLC 500 Remote I/O Adapter Module

-

1794-ASB

Flex I/O 24VDC Remote I/O Adapter

-

(1) Extended node capability (2) In adapter mode (3) Series A, B, and C (4) Extended node capability for Series B and C (5) Must be Catalog Number 2706-ExxxxxB1

Publication 1747-UM013B-EN-P - January 2005