The text of a manual · part 5 of 21
Remote I/O Scanner 1747-SN User Manual: Quick Start for Experienced Users
Pages 29 to 34 of 171, from Remote I/O Scanner 1747-SN User Manual
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-SN
Page 29
Chapter
2
Quick Start for Experienced Users This chapter helps you to get started using the RIO Scanner. We base the procedures here on the assumption that you have a basic understanding of SLC 500 products. You must: • understand electronic process control • be able to interpret the ladder logic instructions for generating the electronic signals that control your application Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more detailed information. It also references other documentation that may be helpful if you are unfamiliar with programming techniques or system installation requirements. If you have any questions, or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information. This chapter: • tells you what tools and equipment you need • lists preliminary considerations • describes when to address, configure and program the module • explains how to install and wire the module • discusses system power-up procedures
Required Tools and Equipment
1
Have the following tools and equipment ready: • medium blade screwdriver • programming equipment • termination kit (package of resistors and ring lug included with the scanner) • approximately 15 inches of #20 AWG for grounding the drain shield to the SLC chassis (for Series A retrofits) • an adequate length of RIO communication cable (Belden 9463) for your specific application Publication 1747-UM013B-EN-P - January 2005
Page 30
2-2
Quick Start for Experienced Users
Procedures
1. Check the contents of the shipping box. Unpack the module making sure that the contents include: • RIO Scanner (Catalog Number 1747 SN) • termination kit If the contents are incomplete, call your local Allen-Bradley representative for assistance. 2. Ensure you chassis supports placement of the 1747-SN module. Review the power requirements of your system to see that your chassis supports placement of the scanner module. The scanner consumes 600 mA @ 5VDC. For modular style systems, calculate the total load on the system power supply using the procedure described in the SLC 500 Modular Hardware Style User Manual, Publication 1747-UM011. See Chapter 3, Installation and Wiring and Appendix A Specifications in this manual. 3. Configure the module using the DIP switches. Set the DIP switches (located on the printed circuit board) to the desired baud rate. Note that all RIO devices must be configured for the same baud rate.
Baud Rate
DIP Switch Position Switch 1
Switch 2
57.6K baud on on
115.2K baud on off
230.4K baud off on
230.4K baud off off
See Chapter 3, Installation and Wiring. 4. Insert the 1747-SN module into the chassis.
Publication 1747-UM013B-EN-P - January 2005
Page 31
Quick Start for Experienced Users
ATTENTION
2-3
Never install, remove, or wire modules with power applied to the chassis or devices wired to the module.
Make sure system power is off; then insert the scanner module into your 1746 chassis. In this example procedure, local slot 1 is selected. See Chapter 3, Installation and Wiring.
Make sure system power is off; then insert the scanner module into your 1746 chassis. In this example procedure, local slot 1 is selected.
Top and Bottom Module Release(s)
Card Guide
5. Connect all RIO link devices. Ensure that you: • Daisy chain each RIO link device. • Ground the shield drain wire to the nearest chassis mounting bolt. • Connect the appropriate termination resistors on each end of the link. 6. Configure the system. Set up your system I/O configuration for the particular slot in which you installed the scanner (slot 1 in this example). If your module is not listed in your software version, select Other and enter the scanner input module ID code (13608) at the prompt on the I/O configuration display. See Chapter 4, Configuration and Programming.
Publication 1747-UM013B-EN-P - January 2005
Page 32
2-4
Quick Start for Experienced Users
7. Enter the number of scanned words. Enter the number of Scanned Input and Output Words using the Specialty I/O and Advanced Setup menus. The default value is 32 I/O words. You can specify less than 32 and reduce the processor scan time by transferring only the part of the input and output image that your application requires. It is important that you do not set either of these values to 0. If you do, the scanner will not work correctly. See Chapter 4, Configuration and Programming. 8. Set the M0 - M1 and G file sizes. Using the Specialty I/O Configuration menu, set the M1 and M0 file sizes to 32 words (48 words if using complementary I/O). (32 words is the minimum required for operation.) If you do not set the M1 and M0 file sizes to at least 32 words, the programming device will not allow you to access the M files in the SLC control program. Set the G file size to 3 (5 if using complementary I/O) using the Specialty I/O Configuration menu. Do the programming necessary to configure the M0 and M1 Block Transfer Buffers. If you are using the block transfer (BT) function, you should set the M1 and M0 file sizes to 3,300. Ensure that you refer to chapter 5 before completing this selection. Write the remainder of the SLC control program that specifies how your scanner will transfer data to/from the SLC processor and RIO devices. Refer to Chapter 4, Configuration and Programming and Chapter 5, RIO Block Transfer. 9. Go through the system start-up procedure. a. Apply power. b. Download your program to the SLC. c. Place the SLC in Run mode. The scanner’s FAULT LED is off and the COMM LED is green, as shown below. (This is the valid LED pattern when in Run mode or after a Run mode to Program mode transition.) See Chapter 3, Installation and Wiring.
Publication 1747-UM013B-EN-P - January 2005
Page 33
Quick Start for Experienced Users
2-5
SCANNER COMM
FAULT
FAULT LED is off. COMM LED is green.
Publication 1747-UM013B-EN-P - January 2005
Page 34
2-6
Quick Start for Experienced Users
Publication 1747-UM013B-EN-P - January 2005