Page 127
C
Appendix
RIO Configuration Worksheet
This appendix provides a worksheet to help you configure your RIO devices.
Directions
We recommend that you use a photocopy of the worksheet so you retain a blank worksheet for future applications.
SLC Processor Output Image
SLC Processor Input Image High Byte
Bit Number
Logical Rack 0
Logical Rack 1
Logical Rack 2
Logical Rack 3
- Decimal Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7
15
High Byte
Low Byte 8 7
Bit Number
0 I:e.0 I:e.1 I:e.2 I:e.3 I:e.4 I:e.5 I:e.6 I:e.7 I:e.8 I:e.9 I:e.10 I:e.11 I:e.12 I:e.13 I:e.14 I:e.15 I:e.16 I:e.17 I:e.18 I:e.19 I:e.20 I:e.21 I:e.22 I:e.23 I:e.24 I:e.25 I:e.26 I:e.27 I:e.28 I:e.29 I:e.30 I:e.31
Logical Rack 0
Logical Rack 1
Logical Rack 2
Logical Rack 3
- Decimal Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7
15
Low Byte 8 7
0 O:e.0 O:e.1 O:e.2 O:e.3 O:e.4 O:e.5 O:e.6 O:e.7 O:e.8 O:e.9 O:e.10 O:e.11 O:e.12 O:e.13 O:e.14 O:e.15 O:e.16 O:e.17 O:e.18 O:e.19 O:e.20 O:e.21 O:e.22 O:e.23 O:e.24 O:e.25 O:e.26 O:e.27 O:e.28 O:e.29 O:e.30 O:e.31 e = 1747-SN Slot Number
1
Publication 1747-UM013B-EN-P - January 2005
Page 128
C-2
RIO Configuration Worksheet
SLC Processor Output Image
SLC Processor Input Image High Byte
Bit Number
Logical Rack 0
Logical Rack 1
Logical Rack 2
Logical Rack 3
- Decimal
15
High Byte
Low Byte 8 7
Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7
Bit Number
0 I:e.0 I:e.1 I:e.2 I:e.3 I:e.4 I:e.5 I:e.6 I:e.7 I:e.8 I:e.9 I:e.10 I:e.11 I:e.12 I:e.13 I:e.14 I:e.15 I:e.16 I:e.17 I:e.18 I:e.19 I:e.20 I:e.21 I:e.22 I:e.23 I:e.24 I:e.25 I:e.26 I:e.27 I:e.28 I:e.29 I:e.30 I:e.31
Logical Rack 0
Logical Rack 1
Logical Rack 2
Logical Rack 3 e = 1747-SN Slot Number
Publication 1747-UM013B-EN-P - January 2005
- Decimal Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7 Group 0 Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 Group 7
15
Low Byte 8 7
0 O:e.0 O:e.1 O:e.2 O:e.3 O:e.4 O:e.5 O:e.6 O:e.7 O:e.8 O:e.9 O:e.10 O:e.11 O:e.12 O:e.13 O:e.14 O:e.15 O:e.16 O:e.17 O:e.18 O:e.19 O:e.20 O:e.21 O:e.22 O:e.23 O:e.24 O:e.25 O:e.26 O:e.27 O:e.28 O:e.29 O:e.30 O:e.31
Page 129
Appendix
D
Block Transfer Examples for Earlier Processors
BTR and BTW Control Logic Examples
These BTR and BTW instructions are for SLC 5/03, SLC 5/04 and SLC 5/05 or earlier processors with OS302, OS401, OS501 series B or earlier operating systems.
Block Transfer Read Control Logic Example Rung 2:0 CONFIGURE THE BTR OPERATION TYPE, LENGTH AND RIO ADDRESS AT POWER-UP. BIT B3:100/7 MUST BE SET PRIOR TO GOING TO RUN TO INDICATE A BTR OPERATION. | | | | | | | POWER-UP BTR | | BIT CONTROL | | S:1 +COP---------------+ | |----] [--------------------------------------------------+COPY FILE +-| | 15 |Source #B3:100| | | |Dest #M0:1.100| | | |Length 3| | | +------------------+ | Rung 2:1 COPY THE BTR STATUS AREA TO A BINARY FILE WHICH WILL BE USED THROUGHOUT THE PROGRAM. THIS AVOIDS ADDRESSING THE M1 FILE MULTIPLE TIMES DURING EACH PROGRAM SCAN. EACH TIME AN INSTRUCTION CONTAINING AN M1 FILE BIT, WORD OR FILE IS SCANNED BY THE PROCESSOR, AN IMMEDIATE DATA TRANSFER TO THE MODULE OCCURS AND THEREFORE WILL IMPACT THE OVERALL PROCESSOR SCAN TIME. | SERVICE | | THE BTR | | STATUS/ | | BTR | | PENDING BTR STATUS | | B3:5 +COP---------------+ | |-+----] [-----+------------------------------------------+COPY FILE +-| | | 0 | |Source #M1:1.100| | | | | |Dest #B3:0| | | | | |Length 4| | | | | +------------------+ | | | CHECK BTR | | | | STATUS | | | | UNTIL DN | | | | OR ER BIT | | | | IS OFF | | | | B3:5 | | | +----] [-----+ | | 1 | Rung 2:2 UNLATCH THE BIT THAT CONTINUES TO CHECK THE BTR STATUS. WHEN A BTR IS COMPLETE, THE DONE BIT IS SET. THE LADDER PROGRAM MUST THEN UNLATCH THE ENABLE BIT, THEN WAIT FOR THE SN MODULE TO TURN OFF THE DONE BIT BEFORE ANOTHER BTR TO THE SAME M-FILE LOCATION CAN BE INITIATED. THIS IS ONE COMPLETE BTR CYCLE. | | CHECK BTR | | | STATUS | | VIRTUAL | UNTIL DN | | BTR DONE | OR ER BIT | | BIT | IS OFF | | B3:0 B3:5 | |-+----]/[-----+-------------------------------------------------------(U)-----| | | 13 | 1 | | | | | | | VIRTUAL | | | | BTR ERROR | | | | BIT | | | | B3:0 | | | +----]/[-----+ | | 12 |
1
Publication 1747-UM013B-EN-P - January 2005
Page 130
D-2
Block Transfer Examples for Earlier Processors
Rung 2:3 WHEN A BTR SUCCESSFULLY COMPLETES, BUFFER THE BT DATA AND UNLATCH THE BT ENABLE BIT. ALSO, UNLATCH THE BTR PENDING BIT AND LATCH THE BIT THAT CONTINUES CHECKING THE BTR STATUS UNTIL THE SN MODULE TURNS OFF THE DONE BIT. | | | | | VIRTUAL | | BTR DONE | | BIT BTR DATA | | B3:0 +COP---------------+ | |----] [----------------------------------------------+-+COPY FILE +-+-| | 13 | |Source #M1:1.110| | | | | |Dest #N7:10| | | | | |Length 64| | | | | +------------------+ | | | | SERVICE | | | | THE BTR | | | | STATUS/ | | | | BTR | | | | PENDING | | | | B3:5 | | | +----(U)---------------+ | | | 0 | | | | | | | | | | | | VIRTUAL | | | | BT ENABLE | | | | BIT | | | | B3:100 | | | +----(U)---------------+ | | | 15 | | | | CHECK BTR | | | | STATUS | | | | UNTIL DN | | | | OR ER BIT | | | | IS OFF | | | | B3:5 | | | +----(L)---------------+ | | 1 | Rung 2:4 IF A BTR ERROR OCCURS, UNLATCH THE ENABLE BIT AND BUFFER THE BT ERROR CODE. ALSO, UNLATCH THE BTR PENDING BIT AND LATCH THE BIT THAT CONTINUES CHECKING THE BTR STATUS UNTIL THE SN MODULE TURNS OFF THE ERROR BIT. | | | | | VIRTUAL | | BTR ERROR BTR ERROR | | BIT CODE | | B3:0 +MOV---------------+ | |----] [----------------------------------------------+-+MOVE +-+-| | 12 | |Source B3:3| | | | | | 0000000000000000| | | | | |Dest B3:4| | | | | | 0000000000000000| | | | | +------------------+ | | | | | | | | SERVICE | | | | THE BTR | | | | STATUS/ | | | | BTR | | | | PENDING | | | | B3:5 | | | +----(U)---------------+ | | | 0 | | | | | | | | | | | | VIRTUAL | | | | BT ENABLE | | | | BIT | | | | B3:100 | | | +----(U)---------------+ | | | 15 | | | | CHECK BTR | | | | STATUS | | | | UNTIL DN | | | | OR ER BIT | | | | IS OFF | | | | B3:5 | | | +----(L)---------------+ | | 1 |
Publication 1747-UM013B-EN-P - January 2005
Page 131
Block Transfer Examples for Earlier Processors
D-3
Rung 2:5 WHEN USER LOGIC INITIATES A NEW BTR, LATCH THE ENABLE BIT , AS LONG AS A BTR IS NOT IN PROGRESS. ALSO, LATCH THE BTR PENDING BIT , SO THE BTR STATUS FILE WILL BE READ BY THE LADDER PROGRAM. | | | | SERVICE | | USER LOGIC| | | THE BTR | | TO |VIRTUAL |VIRTUAL |VIRTUAL STATUS/ | | INITIATE A|BT ENABLE |BTR DONE |BTR ERROR BTR | | BTR |BIT |BIT |BIT PENDING | | I:2.0 B3:100 B3:0 B3:0 B3:5 | |----] [--------]/[--------]/[--------]/[-----------------------+----(L)-----+-| | 0 15 13 12 | 0 | | | | | | | | | | | | VIRTUAL | | | | BT ENABLE | | | | BIT | | | | B3:100 | | | +----(L)-----+ | | 15 | Rung 2:6 MOVE THE VIRTUAL CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHENEVER A TRANSITION OF THE BTR ENABLE BIT OCCURS. | | | | | VIRTUAL | | BT ENABLE | | BIT | | B3:100 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source B3:100| | | | | | 0000000000000000| | | | | |Dest M0:1.100| | | | | | *| | | | | +------------------+ | | | | | | | | | | | VIRTUAL | | | | BTR DONE | | | | BIT | | | | B3:0 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | VIRTUAL | | | | BTR ERROR | | | | BIT | | | | B3:0 | | | +----] [-----+ | | 12 | Rung 2:7 | | |-------------------------------------+END+------------------------------------| | |
Publication 1747-UM013B-EN-P - January 2005
Page 132
D-4
Block Transfer Examples for Earlier Processors
Block Transfer Write Control Logic Example
Rung 2:0 CONFIGURE THE BTW LENGTH AND RIO ADDRESS AT POWER-UP. ALSO, BE SURE THE BLOCK TRANSFER OPERATION BIT IS A ”0” INDICATING A BTW. ALL THESE PARAMETERS MUST BE ENTERED PRIOR TO PLACING THE PROCESSOR IN THE RUN MODE. | | | | | | | POWER-UP | | BIT | | S:1 +COP---------------+ | |----] [--------------------------------------------------+COPY FILE +-| | 15 |Source #B3:100| | | |Dest #M0:1.100| | | |Length 3| | | +------------------+ | Rung 2:1 COPY THE BTW STATUS AREA TO A BINARY FILE WHICH WILL BE USED THROUGHOUT THE PROGRAM, ONLY WHEN A BTW IS PENDING. THIS AVOIDS ACCESSING THE M1 FILE MULTIPLE TIMES DURING EACH PROGRAM SCAN. EACH TIME AN INSTRUCTION CONTAINING AN M1 FILE BIT, WORD OR FILE IS SCANNED BY THE PROCESSOR,AN IMMEDIATE DATA TRANSFER TO THE MODULE OCCURS AND THEREFORE WILL IMPACT THE PROCESSOR SCAN TIME. | SERVICE | | THE BTW | | STATUS/ | | BTW | | PENDING BTW STATUS | | B3:5 +COP---------------+ | |-+----] [-----+------------------------------------------+COPY FILE +-| | | 0 | |Source #M1:1.100| | | | | |Dest #B3:0| | | | | |Length 4| | | | | +------------------+ | | | | | | | CHECK BTW | | | | STATUS | | | | UNTIL DONE | | | | BIT IS OFF | | | | B3:5 | | | +----] [-----+ | | 1 | Rung 2:2 UNLATCH THE BIT THAT CONTINUES TO CHECK THE BTW STATUS. WHEN A BTW IS COMPLETE, THE DONE BIT IS SET. THE LADDER PROGRAM MUST THEN UNLATCH THE ENABLE BIT, THEN WAIT FOR THE SN MODULE TO TURN OFF THE DONE BIT BEFORE ANOTHER BTW TO THE SAME M-FILE LOCATION CAN BE INITIALIZED. THIS IS ONE COMPLETE BTW CYCLE. | | | | | CHECK BTW | | VIRTUAL | STATUS | | BTW DONE | UNTIL DONE | | BIT | BIT IS OFF | | B3:0 B3:5 | |-+----]/[-----+-------------------------------------------------------(U)-----| | | 13 | 1 | | | | | | | VIRTUAL | | | | BTW ERROR | | | | BIT | | | | B3:0 | | | +----]/[-----+ | | 12 | Rung 2:3 WHEN A BTW SUCCESSFULLY COMPLETES, UNLATCH THE BTW ENABLE BIT. ALSO, UNLATCH THE BTW PENDING BIT AND LATCH THE BIT THAT CONTINUES CHECKING THE BTW STATUS UNTIL THE SN MODULE TURNS OFF THE DONE BIT. | SERVICE | | THE BTW | | VIRTUAL STATUS/ | | BTW DONE BTW | | BIT PENDING | | B3:0 B3:5 | |----] [--------------------------------------------------------+----(U)-----+-| | 13 | 0 | | | | | | | | | | | | VIRTUAL | | | | BTW ENABLE | | | | BIT | | | | B3:100 | | | +----(U)-----+ | | | 15 | | | | | | | | CHECK BTW | | | | STATUS | | | | UNTIL DONE | | | | BIT IS OFF | | | | B3:5 | | | +----(L)-----+ | | 1 |
Publication 1747-UM013B-EN-P - January 2005
Page 133
Block Transfer Examples for Earlier Processors
D-5
Rung 2:4 IF A BTW ERRORS, UNLATCH THE ENABLE BIT, THE BTW PENDING BIT AND BUFFER THE BTW ERROR CODE. ALSO, LATCH THE BIT THAT CONTINUES CHECKING THE BTW STATUS UNTIL THE SN MODULE TURNS OFF THE ERROR BIT. | | | | | VIRTUAL | | BTW ERROR BUFFER BTW | | BIT ERROR CODE | | B3:0 +MOV---------------+ | |----] [----------------------------------------------+-+MOVE +-+-| | 12 | |Source B3:3| | | | | | 0000000000000000| | | | | |Dest B3:4| | | | | | 0000000000000000| | | | | +------------------+ | | | | SERVICE | | | | THE BTW | | | | STATUS/ | | | | BTW | | | | PENDING | | | | B3:5 | | | +----(U)---------------+ | | | 0 | | | | | | | | VIRTUAL | | | | BTW ENABLE | | | | BIT | | | | B3:100 | | | +----(U)---------------+ | | | 15 | | | | | | | | CHECK BTW | | | | STATUS | | | | UNTIL DONE | | | | BIT IS OFF | | | | B3:5 | | | +----(L)---------------+ | | 1 | Rung 2:5 WHEN USER LOGIC INITIATES A NEW BTW, COPY THE DATA TO THE M0 FILE DATA AREA AND LATCH THE VIRTUAL BTW ENABLE BIT, PROVIDED THAT A BTW IS NOT IN PROGRESS. ALSO, LATCH THE BTW PENDING BIT, SO THE BT STATUS FILE WILL BE READ BY THE LADDER PROGRAM. | | | | | | USER LOGIC| | | | | TO |VIRTUAL |VIRTUAL |VIRTUAL | | INITIATE A|BTW ENABLE|BTW DONE |BTW ERROR | | BTW |BIT |BIT |BIT BTW DATA | | I:2.0 B3:100 B3:0 B3:0 +COP---------------+ | |----] [--------]/[--------]/[--------]/[-------------+-+COPY FILE +-+-| | 0 15 13 12 | |Source #N7:110| | | | | |Dest #M0:1.110| | | | | |Length 64| | | | | +------------------+ | | | | SERVICE | | | | THE BTW | | | | STATUS/ | | | | BTW | | | | PENDING | | | | B3:5 | | | +----(L)---------------+ | | | 0 | | | | | | | | | | | | VIRTUAL | | | | BTW ENABLE | | | | BIT | | | | B3:100 | | | +----(L)---------------+ | | 15 |
Publication 1747-UM013B-EN-P - January 2005
Page 134
D-6
Block Transfer Examples for Earlier Processors
Rung 2:6 MOVE THE VIRTUAL CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHENEVER A TRANSITION OF THE BTW ENABLE BIT OCCURS. | | | | | VIRTUAL | | BTW ENABLE | | BIT | | B3:100 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source B3:100| | | | | | 0000000000000000| | | | | |Dest M0:1.100| | | | | | *| | | | | +------------------+ | | | | | | | | | | | VIRTUAL | | | | BTW DONE | | | | BIT | | | | B3:0 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | VIRTUAL | | | | BTW ERROR | | | | BIT | | | | B3:0 | | | +----] [-----+ | | 12 | Rung 2:7 | | |-------------------------------------+END+------------------------------------| | |
Directional Continuous Block Transfer Example The following rungs demonstrate a directional continuous block transfer. As long as the BTR precondition bit is true, block transfer reads execute continuously. Use the same method for a BTW.
Publication 1747-UM013B-EN-P - January 2005
Page 135
Block Transfer Examples for Earlier Processors
D-7
Rung 2:0 CONFIGURE THE BTR OPERATION TYPE, LENGTH AND RIO ADDRESS AT POWER-UP. BIT B3:100/7 MUST BE SET PRIOR TO GOING TO RUN TO INDICATE A BTR OPERATION. | | | | | | | POWER-UP BTR | | BIT CONTROL | | S:1 +COP---------------+ | |----] [--------------------------------------------------+COPY FILE +-| | 15 |Source #B3:100| | | |Dest #M0:1.100| | | |Length 3| | | +------------------+ | Rung 2:1 COPY THE BTR STATUS AREA TO A BINARY FILE WHICH WILL BE USED THROUGHOUT THE PROGRAM. THIS AVOIDS ADDRESSING THE M1 FILE MULTIPLE TIMES DURING EACH PROGRAM SCAN. EACH TIME AN INSTRUCTION CONTAINING AN M1 FILE BIT, WORD OR FILE IS SCANNED BY THE PROCESSOR, AN IMMEDIATE DATA TRANSFER TO THE MODULE OCCURS AND THEREFORE WILL IMPACT THE OVERALL PROCESSOR SCAN TIME. | | | | | | | BTR | | PENDING BTR STATUS | | B3 +COP---------------+ | |-+----] [-----+------------------------------------------+COPY FILE +-| | | 80 | |Source #M1:1.100| | | | | |Dest #B3:0| | | | | |Length 4| | | | | +------------------+ | | | | | | | | | | | | | | | CHECK BTR | | | | STATUS | | | | B3 | | | +----] [-----+ | | 81 | Rung 2:2 WHEN THE ERROR OR DONE BIT IS SET INDICATING THAT THE BTR COMPLETED EITHER UNSUCCESSFULLY OR SUCCESSFULLY, THE ENABLE BIT MUST BE UNLATCHED BY THE LADDER PROGRAM. THE 1747-SN SCANNER THEN UNLATCHES THE ERROR/DONE BIT TO COMPLETE THE BLOCK TRANSFER HAND-SHAKE PROCESS. AT THIS TIME THE ”CHECK BTR STATUS” BIT MUST BE UNLATCHED TO AVOID UNNECESSARY M-FILE ACCESSES. | | | | | VIRTUAL | | BTR DONE CHECK BTR | | BIT STATUS | | B3 B3 | |-+----]/[-----+-------------------------------------------------------(U)-----| | | 13 | 81 | | | | | | | | | | | | | | | | | | | VIRTUAL | | | | BT ERROR | | | | BIT | | | | B3 | | | +----]/[-----+ | | 12 |
Publication 1747-UM013B-EN-P - January 2005