Page 154

D-26

Block Transfer Examples for Earlier Processors

Rung 2:10 MOVE THE VIRTUAL BTR CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHILE A BTR IS IN PROGRESS, AND CONTINUE DOING SO UNTIL THE ENABLE, DONE AND ERROR BITS ARE ALL TURNED OFF. | | | | | VIRTUAL BTR | | BTR ENABLE CONTROL | | BIT BITS | | N7:50 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source N7:50| | | | | | 0| | | | | |Dest M0:1.100| | | | | | *| | | | | +------------------+ | | | | | | | | | | | VIRTUAL | | | | BTR DONE | | | | BIT | | | | N7:60 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | VIRTUAL | | | | BTR ERROR | | | | BIT | | | | N7:60 | | | +----] [-----+ | | 12 | Rung 2:11 MOVE THE VIRTUAL BTW CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHILE A BTW IS IN PROGRESS, AND CONTINUE DOING SO UNTIL THE ENABLE, DONE AND ERROR BITS ARE ALL TURNED OFF. | | | | | VIRTUAL BTW | | BTW ENABLE CONTROL | | BIT BITS | | N7:53 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source N7:53| | | | | | 0| | | | | |Dest M0:1.200| | | | | | *| | | | | +------------------+ | | | | | | | | | | | VIRTUAL | | | | BTW DONE | | | | BIT | | | | N7:64 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | VIRTUAL | | | | BTW ERROR | | | | BIT | | | | N7:64 | | | +----] [-----+ | | 12 | Rung 2:12 | | |-------------------------------------+END+------------------------------------| | |

Publication 1747-UM013B-EN-P - January 2005

Page 155

Block Transfer Examples for Earlier Processors

D-27

Bidirectional Alternating Repeating Block Transfer The following rungs demonstrate a bidirectional alternating repeating block transfer. Using these rungs ensures the block transfer requests are executed in the order in which they are sent to the queue. This example also ensures that the BTR and BTW repeatedly alternate. The XIO conditions prevent the BTR and BTW from queuing simultaneously. The BT’s continue as long as the ladder rungs are scanned.

Rung 2:0 CONFIGURE THE BT OPERATION TYPE, LENGTH AND RIO ADDRESS (R,G,S IN DECIMAL) AT POWER-UP. BIT N7:50/7 MUST BE SET TO A ”1” TO INDICATE A BTR AND N7:53/7 MUST BE A LOGICAL ”0” TO INDICATE A BTW OPERATION. | | | | | | | POWER-UP BTR | | BIT CONTROL | | S:1 +COP---------------+ | |----] [----------------------------------------------+-+COPY FILE +-+-| | 15 | |Source #N7:50| | | | | |Dest #M0:1.100| | | | | |Length 3| | | | | +------------------+ | | | | | | | | | | | | | | | | BTW | | | | OPERATION | | | | +COP---------------+ | | | +-+COPY FILE +-+ | | |Source #N7:53| | | |Dest #M0:1.200| | | |Length 3| | | +------------------+ | Rung 2:1 COPY THE BTR STATUS AREA TO AN INTEGER FILE ONLY WHEN A BTR IS IN PROGRESS. THIS STATUS DATA WILL THEN BE USED THROUGHOUT THE PROGRAM AND WILL LIMIT THE NUMBER OF M-FILE ACCESSES | | | | | | | BTR | | PENDING BTR STATUS | | B3 +COP---------------+ | |-+----] [-----+------------------------------------------+COPY FILE +-| | | 0 | |Source #M1:1.100| | | | | |Dest #N7:60| | | | | |Length 4| | | | | +------------------+ | | | | | | | | | | | | | | | CHECK BTR | | | | STATUS | | | | B3 | | | +----] [-----+ | | 2 |

Publication 1747-UM013B-EN-P - January 2005

Page 156

D-28

Block Transfer Examples for Earlier Processors

Rung 2:2 UNLATCH THE BIT THAT CONTINUES TO CHECK THE BTR STATUS. WHEN A BTR IS COMPLETE, THE DONE OR ERROR BIT IS SET. THE LADDER PROGRAM MUST THEN UNLATCH THE ENABLE BIT, THEN WAIT FOR THE SN MODULE TO TURN OFF THE DONE/ERROR BIT BEFORE ANOTHER BTR TO THE SAME M-FILE LOCATION CAN BE INITIATED. THIS IS ONE COMPLETE BTR CYCLE. | | | | | VIRTUAL | | BTR DONE CHECK BTR | | BIT STATUS | | N7:60 B3 | |-+----]/[-----+-------------------------------------------------------(U)-----| | | 13 | 2 | | | | | | | | | | | | | | | BTR ERROR | | BIT | | | | N7:60 | | | +----]/[-----+ | | 12 | Rung 2:3 COPY THE BTW STATUS AREA TO AN INTEGER FILE ONLY WHEN A BTW IS IN PROGRESS. THIS STATUS DATA WILL THEN BE USED THROUGHOUT THE PROGRAM AND WILL LIMIT THE NUMBER OF M-FILE ACCESSES. | | | | | | | BTW BTW | | PENDING STATUS | | B3 +COP---------------+ | |-+----] [-----+------------------------------------------+COPY FILE +-| | | 1 | |Source #M1:1.200| | | | | |Dest #N7:64| | | | | |Length 4| | | | | +------------------+ | | | | | | | | | | | | | | | CHECK BTW | | | | STATUS | | | | B3 | | | +----] [-----+ | | 3 | Rung 2:4 UNLATCH THE BIT THAT CONTINUES TO CHECK THE BTW STATUS. WHEN A BTW IS COMPLETE, THE DONE OR ERROR BIT IS SET. THE LADDER PROGRAM MUST THEN UNLATCH THE ENABLE BIT, THEN WAIT FOR THE SN MODULE TO TURN OFF THE THE DONE/ERROR BIT BEFORE ANOTHER BTW TO THE SAME M-FILE LOCATION CAN BE INITIATED. THIS COMPLETES ONE BTW CYCLE. | | | | | VIRTUAL | | BTW DONE CHECK BTW | | BIT STATUS | | N7:64 B3 | |-+----]/[-----+-------------------------------------------------------(U)-----| | | 13 | 3 | | | | | | | | | | | VIRTUAL | | | | BTW ERROR | | | | BIT | | | | N7:64 | | | +----]/[-----+ | | 12 |

Publication 1747-UM013B-EN-P - January 2005

Page 157

Block Transfer Examples for Earlier Processors

D-29

Rung 2:5 WHEN A BTR SUCCESSFULLY COMPLETES, BUFFER THE BTR DATA AND UNLATCH BOTH THE BTR VIRTUAL ENABLE BIT AND THE BTR PENDING BIT. ALSO, LATCH THE BIT THAT CONTINUES CHECKING THE BTR STATUS UNTIL THE SN MODULE TURNS OFF THE DONE BIT. | | | | | VIRTUAL | | BTR DONE | | BIT BTR DATA | | N7:60 +COP---------------+ | |----] [----------------------------------------------+-+COPY FILE +-+-| | 13 | |Source #M1:1.110| | | | | |Dest #N7:0| | | | | |Length 10| | | | | +------------------+ | | | | | | | | | | | | | | | | BTR | | | | PENDING | | | | B3 | | | +----(U)---------------+ | | | 0 | | | | | | | | | | | | VIRTUAL | | | | BTR ENABLE | | | | BIT | | | | N7:50 | | | +----(U)---------------+ | | | 15 | | | | | | | | | | | | | | | | | | | | | | | | CHECK BTR | | | | STATUS | | | | B3 | | | +----(L)---------------+ | | 2 | Rung 2:6 WHEN A BTR UNSUCCESSFULLY COMPLETES, BUFFER THE ERROR CODE AND UNLATCH THE BTR ENABLE BIT AND THE BTR PENDING BIT. ALSO, LATCH THE CHECK BTR STATUS BIT IN ORDER TO CONTINUE READING THE STATUS INFORMATION FROM THE SCANNER UNTIL IT TURNS THE ERROR BIT OFF, COMPLETING THE HAND-SHAKE PROCESS. | | | | | BTR ERROR | | BIT | | N7:60 +MOV---------------+ | |----] [----------------------------------------------+-+MOVE +-+-| | 12 | |Source M1:1.103| | | | | | *| | | | | |Dest N7:21| | | | | | 0| | | | | +------------------+ | | | | | | | | | | | | | | | | BTR | | | | PENDING | | | | B3 | | | +----(U)---------------+ | | | 0 | | | | | | | | | | | | VIRTUAL | | | | BTR ENABLE | | | | BIT | | | | N7:50 | | | +----(U)---------------+ | | | 15 | | | | | | | | | | | | | | | | CHECK BTR | | | | STATUS | | | | B3 | | | +----(L)---------------+ | | 2 |

Publication 1747-UM013B-EN-P - January 2005

Page 158

D-30

Block Transfer Examples for Earlier Processors

Rung 2:7 WHEN A BTW SUCCESSFULLY OR UNSUCCESSFULLY COMPLETES, UNLATCH THE BTW ENABLE BIT AND THE BTW PENDING BIT TO COMPLETE A BTW SEQUENCE. ALSO, LATCH THE BIT THAT CONTINUES CHECKING THE BTW STATUS UNTIL THE SN MODULE TURNS THE DONE/ERROR BIT OFF. IN ADDITION, BUFFER THE BTW ERROR CODE IN CASE AN ERROR OCCURS. | | | | | VIRTUAL | | BTW DONE BTW | | BIT PENDING | | N7:64 B3 | |-+----] [-----+--------------------------------------+----(U)---------------+-| | | 13 | | 1 | | | | | | | | | | | | | | | VIRTUAL | | VIRTUAL | | | | BTW ERROR | | BTW ENABLE | | | | BIT | | BIT | | | | N7:64 | | N7:53 | | | +----] [-----+ +----(U)---------------+ | | 12 | 15 | | | | | | | | | | | | | | | | CHECK BTW | | | | STATUS | | | | B3 | | | +----(L)---------------+ | | | 3 | | | | | | | | | | | | | | | | BTW ERROR | | | | CODE | | | | +MOV---------------+ | | | +-+MOVE +-+ | | |Source M1:1.203| | | | *| | | |Dest N7:22| | | | 0| | | +------------------+ | Rung 2:8 THIS RUNG AND THE NEXT RUNG WILL TOGGLE BETWEEN EXECUTING A BTR AND A BTW. | | | | | | | | | | | VIRTUAL |VIRTUAL |VIRTUAL | | | BTR ENABLE|BTW ENABLE|BTR DONE |BTR ERROR BTR | | BIT |BIT |BIT |BIT PENDING | | N7:50 N7:53 N7:60 N7:60 B3 | |----]/[--------]/[--------]/[--------]/[-----------------------+----(L)-----+-| | 15 15 13 12 | 0 | | | | | | | +++ +++| | +++ +++| | | | | | | | | | | | | | | VIRTUAL | | | | BTR ENABLE | | | | BIT | | | | N7:50 | | | +----(L)-----+ | | 15 |

Publication 1747-UM013B-EN-P - January 2005

Page 159

Block Transfer Examples for Earlier Processors

D-31

Rung 2:9 | | | | | | | | | | | VIRTUAL |VIRTUAL |VIRTUAL |VIRTUAL | | BTR ENABLE|BTW ENABLE|BTW DONE |BTW ERROR | | BIT |BIT |BIT |BIT BTW DATA | | N7:50 N7:53 N7:64 N7:64 +COP---------------+ | |----]/[--------]/[--------]/[--------]/[-------------+-+COPY FILE +-+-| | 15 15 13 12 | |Source #N7:10| | | | | |Dest #M0:1.210| | | | | |Length 11| | | | | +------------------+ | | | | | | | | | | | | VIRTUAL | | | | BTW ENABLE | | | | BIT | | | | N7:53 | | | +----(L)---------------+ | | | 15 | | | | | | | | | | | | | | | | BTW | | | | PENDING | | | | B3 | | | +----(L)---------------+ | | 1 | Rung 2:10 MOVE THE VIRTUAL BTR CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHILE A BTR IS IN PROGRESS, AND CONTINUE DOING SO UNTIL THE ENABLE, DONE AND ERROR BITS ARE ALL TURNED OFF, COMPLETING THE HAND-SHAKE PROCESS. | | | | | VIRTUAL BTR | | BTR ENABLE CONTROL | | BIT WORD | | N7:50 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source N7:50| | | | | | 0| | | | | |Dest M0:1.100| | | | | | *| | | | | +------------------+ | | | | | | | | | | | | | | | | | | | VIRTUAL | | | | BTR DONE | | | | BIT | | | | N7:60 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | | | | | BTR ERROR | | | | BIT | | | | N7:60 | | | +----] [-----+ | | 12 |

Publication 1747-UM013B-EN-P - January 2005

Page 160

D-32

Block Transfer Examples for Earlier Processors

Rung 2:11 MOVE THE VIRTUAL BTW CONTROL WORD TO THE M0 FILE FOR THE SN MODULE WHILE A BTR IS IN PROGRESS, AND CONTINUE DOING SO UNTIL THE ENABLE, DONE AND ERROR BITS ARE ALL TURNED OFF, COMPLETING THE HAND-SHAKE PROCESS. | | | | | VIRTUAL BTW | | BTW ENABLE CONTROL | | BIT WORD | | N7:53 +MOV---------------+ | |-+----] [-----+------------------------------------------+MOVE +-| | | 15 | |Source N7:53| | | | | | 0| | | | | |Dest M0:1.200| | | | | | *| | | | | +------------------+ | | | | | | | | | | | VIRTUAL | | | | BTW DONE | | | | BIT | | | | N7:64 | | | +----] [-----+ | | | 13 | | | | | | | | | | | | VIRTUAL | | | | BTW ERROR | | | | BIT | | | | N7:64 | | | +----] [-----+ | | 12 | Rung 2:12 | | |-------------------------------------+END+------------------------------------| | |

Publication 1747-UM013B-EN-P - January 2005