The text of a manual · part 10 of 18
ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual: 5 - Rack Optimized I/O, pages 56 to 64
Pages 56 to 64 of 122, from ControlLogix Ethernet Communication Interface Module 1756-ENET/B User Manual
The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-ENET
Page 56
5-10
Rack Optimized I/O
TIP
If you want to alter the default parameters, click on the Next button. Refer to the ControlLogix Digital I/O User Manual, publication 1756-6.5.8, for details.
5. Click on the Finish button to save the configuration. The digital input module will appear in the I/O configuration indented under the remote 1756-ENET/B module.
Add the Remote Digital Output Module
6. Right click on the remote 1756-ENET/B module and again select New Module.
Publication 1756-UM051B-EN-P - November 2000
Page 57
Rack Optimized I/O
5-11
The Select Module Type window will open.
7. Select the 1756-OB16I digital output module from the list. The Module Properties window will open.
8. Enter the following parameters (the values we used are listed in the table): Name
Remote_Digital_Output
Slot
2
Comm Format
Rack Optimization
Electronic Keying(1)
Compatible Module
(1)
See Appendix F for important information about Electronic Keying.
Publication 1756-UM051B-EN-P - November 2000
Page 58
5-12
Rack Optimized I/O
TIP
If you want to alter the default parameters, click on the Next button. Refer to the ControlLogix Digital I/O User Manual, publication 1756-6.5.8, for details.
9. Click on the Finish button to accept the configuration. The I/O Configuration in the Project window should look similar to the one shown below.
Edit the Controller Tags When you add modules to the I/O configuration the system creates tags for those modules to use in the application program. For our example application we need to add another Controller Tag.
1. Double-click on the Controller Tags folder in the project window. The Controller Tags window will open. You will see the tags created for the 1756-ENET/B and digital I/O modules.
Tags created by the system
Enter the new tag here
Publication 1756-UM051B-EN-P - November 2000
Page 59
Rack Optimized I/O
5-13
2. Select the Edit Tags tab at the bottom of the Controller Tags window. 3. Create the following tag: Tag Parts_Count
Type Counter
4. Close the Controller Tags window.
Publication 1756-UM051B-EN-P - November 2000
Page 60
5-14
Rack Optimized I/O
Create the Ladder Program
1. Double-click on Main Routine under the Main Program folder, and enter the following ladder program, using the tags previously created.
2. Save the program.
Publication 1756-UM051B-EN-P - November 2000
Page 61
Rack Optimized I/O
5-15
Download the Program to the Controller 1. Click on the Communications menu and select Who Active. The Who Active window will open (Your window will show the drivers and devices you have installed).
2. Select your Ethernet driver (e.g., AB_ETH-1) and expand the tree through the backplane of the local ControlLogix chassis. 3. Highlight the Logix 5550 controller and click on the Download button. You will see a message similar to the following:
4. Click on the Download button. 5. Minimize RSLogix5000.
Publication 1756-UM051B-EN-P - November 2000
Page 62
5-16
Rack Optimized I/O
Test the Example Application
You will test the example application by using a momentary switch to simulate a parts sensor. 1. Wire the 1756-IB16I digital input module as shown in the following figure: 1756-IB16I 1
2 4
GND-0
IN-0
GND-1
IN-1
Count 3
Reset
24V +
–
2. Restore the RSLogix5000 software and place the controller in Run mode. 3. Repeatedly press and release the momentary switch at IN-0 (Count) on the 1756-IB16I digital input module. Each time you press the switch you should see the Parts_Count accumulated value increment on the screen and the LED display of the OB16I output module increment in binary.
Accumulated Value will increment and be moved to Output module.
LED display will increment in binary count
4. Press and release the momentary switch at IN-1 (Reset) on the 1756-IB16 digital input module. You should see the accumulated value of the Parts_Count reset to zero and all of the LEDs on the 1756-OB16I output module turn off.
Publication 1756-UM051B-EN-P - November 2000
Page 63
Rack Optimized I/O
TIP
5-17
Refer to the ControlLogix Digital I/O Modules User Manual, publication 1756-6.5.8, for assistance in wiring and debugging the I/O modules.
This completes the Rack Optimized I/O example.
What’s Next?
The following chapter describes an example application in which you add an analog output module to the I/O configuration using a direct connection.
Publication 1756-UM051B-EN-P - November 2000
Page 64
5-18
Rack Optimized I/O
Publication 1756-UM051B-EN-P - November 2000