ControlLogix Sequence of Events Module 1756-IB16ISOE (24/48V dc), 1756-IH16ISOE (125V dc) User Manual: C - Synchronizing CSTs Across Multiple Chassis

Pages 129 to 134 of 160, from ControlLogix Sequence of Events Module 1756-IB16ISOE (24/48V dc), 1756-IH16ISOE (125V dc) User Manual

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1756-IB16

Page 129

Appendix

C

Synchronizing CSTs Across Multiple Chassis

Overview

While each ControlLogix chassis uses the CST on its backplane to serve as the single time reference for all modules in the chassis, the CSTs between separate chassis are different from each other by default. You can synchronize CSTs between chassis; synchronization is especially useful when Sequence of Events modules reside in a remote chassis (with respect to the location of the controller). Some applications must be designed in such a way that a Sequence of Events module cannot reside in the controller’s local chassis. Yet, the controller still needs the timestamp from when transitions occur on the remote module in terms it understands. For the timestamp with the input data to make any sense to the controller, the CSTs in the separate chassis must be synchronized. In other words, in this case, any chassis that contain Sequence of Events module must synchronized via SynchLink.

Using a Time Master Each ControlLogix chassis can house a time master (ControlLogix controller or 1756-SYNCH module), a device that establishes the CST for a ControlLogix chassis. In a single chassis scenario, the ControlLogix controller typically serves as the time master. When you require CST synchronization across multiple chassis, you need a time master in each chassis and those masters must receive a single CST from a common source. You can use ControlLogix SynchLink modules (1756-SYNCH) to synchronize CSTs between ControlLogix chassis. In the most basic terms, the following occurs to synchronize time between chassis: • You must use RSLogix 5000, v13 or greater. (You can synchronize CSTs between chassis with previous versions of RSLogix 5000 but those versions require a ControlLogix controller be located in each chassis. This section describes synchronizing CSTs with v13 or greater.) • A 1756-SYNCH module is located in each chassis, local and remote.

1

Publication 1756-UM528A-EN-P - April 2004

Page 130

C-2

Synchronizing CSTs Across Multiple Chassis

• The controller in the local chassis typically serves as the time master for its chassis; the 1756-SYNCH module in the local chassis can also serve as the time master. • The 1756-SYNCH module in the local chassis sends a common CST time reference to 1756-SYNCH modules in remote chassis over a fiber optic connection. • The 1756-SYNCH module in remote chassis receive the CSTs from the 1756-SYNCH module in the local chassis and use that time to set the CST on the backplane of the chassis where they reside. • All the other modules in the remote chassis operate with a CST from the backplane that is synchronized with the CST in the controller’s chassis. Figure C.1 Chassis #1

Chassis #2 CST on backplane synchronized with Chassis

CST on

43743

ControlNet CST propagated via Controller - Sets CST for local chassis.

1756-SYNCH - Gets CST from backplane and sends it to the other 1756-SYNCH modules.

1756-SYNCH - Gets CST from 1756-SYNCH in local chassis and sets it on the backplane in Chassis #2

Sequence of events module in remote chassis timestamps input data with the same CST as used by the controller in Chassis #1.

Once the CST is synchronized between chassis, as shown in Figure C.1, the modules in chassis #2 use the same CST as the modules in chassis #1. You can use 1756-SYNCH modules to synchronize CSTs for up to 257 ControlLogix chassis. Synchronization of CSTs between ControlLogix chassis provides a common CST with no more than +/-5µs drift between chassis.

Publication 1756-UM528A-EN-P - April 2004

Page 131

Synchronizing CSTs Across Multiple Chassis

C-3

Configuring 1756-SYNCH Modules in RSLogix 5000 The SynchLink module can be configured for multiple mastership and slave roles with respect to the Coordinated System Time and the SynchLink. The 1756-SYNCH modules used in the example on page C-2 require specific configuration for the system to work. Figure C.2 shows the example again but also show what the configuration for each 1756-SYNCH module needs to be. Figure C.2 Chassis #1

Chassis #2

ControlNet CST propagated via 1756-SYNCHs 43743

1756-SYNCH - Gets CST from backplane and sends it to the other 1756-SYNCH modules. Configure this 1756-SYNCH module as shown below.

This setting is required because the module relays time from its backplane to the SynchLink.

This setting is recommended. In this case, you must make sure the ControlLogix controller is configured as the Chassis CST Master.

1756-SYNCH - Gets CST from 1756-SYNCH in local chassis and sets it on the backplane in Chassis #2. Configure this 1756-SYNCH module as shown below.

This setting is required because the module relays time from its backplane to the SynchLink.

This Dependence on SynchLink setting is optional for the 1756-SYNCH module. We recommend that when you are using the 1756-SYNCH module with the Sequence of Events module, you use the Required option.

For more information on how to configure the 1756-SYNCH module, see ControlLogix SynchLink Module User Manual, publication number 1756-UM521.

Publication 1756-UM528A-EN-P - April 2004

Page 132

C-4

Synchronizing CSTs Across Multiple Chassis

Synchronizing Chassis in ControlLogix Redundancy Systems

When Sequence of Events modules are used in ControlLogix Redundancy systems, the chassis that contain the Sequence of Events modules must be synchronized. Figure C.3 on page C-5 shows an example ControlLogix redundancy system that uses Sequence of Events modules in some of its remote chassis to timestamp input transitions and 1756-SYNCH modules to synchronize CSTs among those remote chassis. When synchronizing time in ControlLogix redundancy systems that also use Sequence of Events modules, remember the following: • A time master (either ControlLogix controller or 1756-SYNCH module) must reside in each synchronized chassis. • All chassis containing Sequence of Events modules must also contain 1756-SYNCH modules that provide a common CST via SynchLink. IMPORTANT

At the time of this printing (April 2004), ControlLogix Redundancy was only available with ControlLogix controllers version 11.71. To synchronize remote Sequence of Events modules, you must either: • Use version 13 redundancy across the system or • Use version 11.71 for the redundancy controllers and include a ControlLogix controller, version 13, in one of the synchronized remote chassis, as shown in the example. In this case, you must use two RSLogix 5000 projects–one for the redundancy controllers (programmed with RSLogix 5000, version 11) and one for the remote chassis controller (programmed with RSLogix 5000, version 13).

Publication 1756-UM528A-EN-P - April 2004

Page 133

Synchronizing CSTs Across Multiple Chassis

C-5

Figure C.3 Each chassis contains: • 1756-L55 controller, version 11.71

Primary chassis

Secondary chassis

• 1757-SRM module • 1756-CNB(R) module (series D, version 5.23 or greater) These chassis are NOT synchronized. ControlNet

43834

SynchLink Chassis contains: • 1756-L55 controller, version 13.x – Required because the redundant controllers use version 11.71. This controller is not required if you use version 13 redundancy.

Each chassis contains: • Sequence of Events module • 1756-SYNCH module • 1756-CNB(R) module (series D, version 5.23 or greater)

Chassis containing 1756-CNB(R) module (series D, version 5.23 or greater) and remote I/O but no Sequence of Events or 1756-SYNCH modules and not synchronized with the other remote chassis.

• Sequence of Events module • 1756-SYNCH module • 1756-CNB(R) module (series D, version 5.23 or greater)

Related SynchLink Documentation

For more information on how to use the 1756-SYNCH module, see: • SynchLink Design Guide, publication number 1756-TD008 • ControlLogix SynchLink Module User Manual, publication number 1756-UM521.

Publication 1756-UM528A-EN-P - April 2004

Page 134

C-6

Synchronizing CSTs Across Multiple Chassis

Notes:

Publication 1756-UM528A-EN-P - April 2004