Page 147

Appendix

E

Using Sample RSLogix 5000 Projects with the Sequence of Events Module

Overview

Rockwell Automation offers several sample RSLogix 5000 projects to use with your Sequence of Events module. The module timestamps input transitions and provides that data to its owner-controller. However, you must use the data to perform such tasks as: • detect relative first faults • determine absolute first faults • associate real-time with CST-formatted timestamps Table E.1 describes the sample projects Rockwell Automation offers:

Table E.1 Project:

Description:

GPS_withSOE.ACD

This project uses multiple user-defined data types (UDTs) and one subroutine. The project provides samples on how to manage and buffer information from a 1756HP-GPS module. Many of these messages are optional and dependent on how you implement your specific system. The last rung of this routine provides the interface for communications between the ControlLogix Sequence of Events module and 1756HP-GPS module so the Sequence of Events module will return UTC time instead of CST.

SOE_Module_FifoExtract.ACD

This project uses multiple user-defined data types (UDTs) and subroutines. The project is an example of extracting data from an Sequence of Events module system (multiple modules), with the following constraints: • The modules operate in FIFO mode. • The controller uses Standard Retrieval to retrieve timestamp data from multiple Sequence of Events modules. • Sample of sorting multiple timestamps

ST_BubbleSort.ACD

This project uses two Structured Text subtroutines. The project is an example of easily sorting data.

IMPORTANT

Table E.1 only briefly describes the sample projects. The projects have rung-by-rung descriptions to explain why the projects were written as they were. We recommend you open the projects to see exactly how they were written and how to use them.

To access the sample projects, see page E-2.

1

Publication 1756-UM528A-EN-P - April 2004

Page 148

E-2

Using Sample RSLogix 5000 Projects with the Sequence of Events Module

Accessing the Sample Projects

The sample projects are available at the following locations: • RSLogix 5000 CD that shipped with v13 • RSLogix 5000 software via the Vendor Sample Project PDF accessible through online help • Rockwell Automation Technical Support Knowledgebase, available at: – http://support.rockwellautomation.com/ – Click on the Knowledgebase link.

Publication 1756-UM528A-EN-P - April 2004

Page 149

Glossary Absolute time Time represented in an easily understood format (i.e., Gregorian format). You must use the 1756HP-GPS module to convert timestamps to absolute time. In this format, time is represented in year, month, day, hour, minute, second and microsecond. Communications format Format that defines the operational mode used on the Sequence of Events and, consequently, the type of information transferred between the module and its owner-controller. This format also defines the tags created for each the module. Compatible match An electronic keying protection mode that requires that the physical module and the module configured in the software to match according to vendor and catalog number. In this case, the minor revision of the module must greater than or equal to that of the configured slot. Connection The communication mechanism from the controller to another module in the control system. ControlLogix backplane The backplane used by the 1756 chassis. Coordinated system time (CST) Timer value which is kept synchronized for all modules within a single ControlBus chassis CST Per Point Operating mode on the Sequence of Events module in which the module timestamps up to 2 input transitions per input, one for OFF to ON transitions and another for ON to OFF transitions. Current event Event for which the Sequence of Events module is currently producing data

1

Publication 1756-UM528A-EN-P - April 2004

Page 150

Glossary

2

Direct connection A connection where the controller establishes an individual connection with the Sequence of Events module. Disable keying An electronic keying protection mode that requires no attributes of the physical module and the module configured in the software to match Download The process of transferring the contents of a project on the workstation into the controller Electronic keying A feature where modules can be requested to perform an electronic check to make sure that the physical module is consistent with what was configured by the software Exact match An electronic keying protection mode that requires the physical module and the module configured in the software to match according to vendor, catalog number, major revision and minor revision First In First Out (FIFO) Operating mode on the Sequence of Events module in which the module timestamps an unlimited number of input transitions, regardless of direction (i.e., either OFF to ON or ON to OFF) or input (i.e., the same input can transition many times and the module will timestamp every transition) and stores them in an on-board buffer. Global positioning system (GPS) A constellation of 24 radio navigation satellites that transmit signals used, by GPS receivers, to determine precise location (position, velocity, and time) solutions. Inhibit A ControlLogix process that allows you to configure a Sequence of Events module but prevent it from communicating with the owner-controller. In this case, the controller behaves as if the I/O module does not exist at all.

Publication 1756-UM528A-EN-P - April 2004

Page 151

Glossary

3

Interface module (IFM) A module that uses prewired cable to connect wiring to an I/O module Major revision A module revision that is updated any time there is a functional change to the module Minor revision A module revision that is updated any time there is a change to the module that does not affect its function or interface Owner-controller The controller that creates and stores the primary configuration and communication connection to a module Program mode In this mode the following events occur: • Controller program is not executing. • Inputs are still actively producing data. Pulse per second Process by which the 1756HP-GPS receives the UCT time reference from the navigation sattelites that are part of the GPS system. Relative time Time format used when sorting timestamps in CST format. In this case, you cannot easily determine what the 64-bit timestamps represent, but you can determine an order for the timestamps that will provide a relative reference for when a timestamped transition occurred. Remote connection A connection where the controller establishes an individual connection with Sequence of Events modules in a remote chassis Removal and insertion under power (RIUP) ControlLogix feature that allows a user to install or remove a module or RTB while power is applied

Publication 1756-UM528A-EN-P - April 2004

Page 152

Glossary

4

Removable terminal block (RTB) Field wiring connector for Sequence of Events modules Requested packet interval (RPI) The maximum amount of time between broadcasts of I/O data Run mode In this mode, the following events occur: • Controller program is executing • Inputs are actively producing data Service A system feature that is performed on user demand, such as fuse reset or diagnostic latch reset System side Backplane side of the interface to the Sequence of Events module Tag A named area of the controller’s memory where data is stored Time master Device, either ControlLogix controller or 1756-SYNCH module, that sets the CST time for a ControlLogix chassis and/or SynchLink system. Timestamping ControlLogix process that stamps a change in input data with a relative time reference of when that change occurred Universal Coordinated Time (UCT) World standard time format maintained by atomic clocks operated by government organizations around the world. The 1756HP-GPS module reports UTC as a 64-bit unsigned long integer representing the number of elapsed microseconds since 1 January 1972. Wall clock time (WCT) Gregorian time format. In this format, time is represented in year, month, day, hour, minute, second and microsecond.

Publication 1756-UM528A-EN-P - April 2004