The text of a manual · part 3 of 19
ControlLogix Sequence of Events Module 1756-IB16ISOE (24/48V dc), 1756-IH16ISOE (125V dc) User Manual: 1 - What is the ControlLogix Sequence of Events Module?
Pages 11 to 16 of 160, from ControlLogix Sequence of Events Module 1756-IB16ISOE (24/48V dc), 1756-IH16ISOE (125V dc) User Manual
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1756-IB16
Page 11
Chapter
1
What is the ControlLogix Sequence of Events Module?
What This Chapter Contains This chapter describes the ControlLogix Sequence of Events module. Table 1.1 For information on:
What does Sequence of Events Module Do?
See page:
What does Sequence of Events Module Do?
1-1
What Else Does the Sequence of Event Module Do?
1-3
Understanding the Module’s Physical Features
1-4
Using Module Identification and Status Information
1-5
The ControlLogix Sequence of Events module is a DC input module that offers sub-millisecond timestamping on a per point basis in addition to providing the basic ON/OFF detection as found on other ControlLogix input modules. Timestamping is a ControlLogix feature that registers a time reference to a change in input data. In ControlLogix, the time mechanism used for timestamping is the Coordinated System Time (CST).
Timestamping Using the Coordinated System Time (CST) The Coordinated System Time (CST) is a 64-bit, free-running timer with microsecond (µs) granularity on a ControlLogix backplane. A time master (either a ControlLogix controller or 1756-SYNCH module) generates the timer and sets it on the backplane. All other modules in the chassis have access to the CST and adjust their time reference based on the backplane time reference.
1
Publication 1756-UM528A-EN-P - April 2004
Page 12
1-2
What is the ControlLogix Sequence of Events Module?
CST cannot easily translate to real-time but serves as a relative time reference. Each module in a chassis has access to this reference. The Sequence of Events module grabs the current CST value at the time of the input state change to timestamp the input data. You can propagate the same CST value across multiple chassis, effectively making sure that modules in separate chassis use the same time reference in all their operations, if necessary. You can extend a single CST value across multiple chassis that are physically connected via 1756-SYNCH modules. Additionally, multiple ControlLogix systems–even those that are geographically separated– can use the 1756HP-GPS module to share a common real-time reference. For more information on extending a single CST value across multiple chassis, see Appendix C.
On-Board Data Storage Once a CST timestamp is captured for an input transition, the module’s operational mode impacts how the module functions with respect to: • what data is stored on-board • how much data is stored for each input point • how the data is sent to the controller The next section briefly describes the two modes of operation available with the Sequence of Events module and how they impact the module’s behavior.
Publication 1756-UM528A-EN-P - April 2004
Page 13
What is the ControlLogix Sequence of Events Module?
1-3
Two Modes of Operation The Sequence of Events module can operate in either of the modes described in Table 1.2: Table 1.2 Operational mode:
Description:
CST Per Point Mode
The module timestamps up to 2 input transitions per input, one for OFF to ON transitions and another for ON to OFF transitions.
First In First Out (FIFO) Mode
The module timestamps an unlimited number of input transitions, regardless of direction (i.e., either OFF to ON or ON to OFF) or input (i.e., the same input can transition many times and the module will timestamp every transition) and stores them in an on-board buffer. The module is capable of storing the data for up to 160 input transitions in its on-board buffers at a single time. However, if you retrieve data from the buffers effectively, the module will never miss an input transition, regardless of how many occur.
You set the module’s operational mode when you choose a communication format during initial module configuration. Depending on operational mode, RSLogix 5000 creates different tags for the Sequence of Events when it is added to a project. For more information on each mode, see Chapter 6, Using The Sequence of Events Module in CST Per Point Mode and Chapter 7, Using The Sequence of Events Module in FIFO Mode.
What Else Does the Sequence of Event Module Do?
The Sequence of Events module offers additional features that are common to ControlLogix digital input modules, such as: • Full software configuration via RSLogix 5000 • Removal and insertion under power • Full Class I Division Compliance • Agency Certifications (e.g. UL and CSA) To see a full description of all the features available on your Sequence of Events module, see Chapter 5, Using the Sequence of Events Module Features.
Publication 1756-UM528A-EN-P - April 2004
Page 14
1-4
What is the ControlLogix Sequence of Events Module?
Understanding the Module’s Physical Features
ControlLogix modules mount in a ControlLogix chassis and use a Removable Terminal Block (RTB), or a Bulletin 1492 Interface Module cable that connects to an IFM, to connect all field-side wiring. Before you use your module, you should have already: • installed and grounded a 1756 chassis and power supply. To install these products, refer to the publications listed in Table Preface.3 on page Preface-2. • ordered and received an RTB or IFM and its components for your application; neither RTBs nor IFMs are included with your module purchase. Figure 1.1 Indicators
Locking tab O K
Top and bottom guides ControlLogix backplane
Connector pins
Removable terminal block
Jumper bar
Slots for keying the RTB
41623
Table 1.3 Physical Features on the ControlLogix Sequence of Events Module Physical Feature:
Description:
Backplane connector
The backplane connector interface for the ControlLogix system connects the module to the ControlLogix backplane.
Connector pins
Input/output, power and grounding connections are made to the module through these pins with the use of an RTB or IFM.
Locking tab
The locking tab anchors the RTB or IFM cable on the module, maintaining wiring connections.
Slots for keying
Mechanically keys the RTB to prevent inadvertently making the wrong wire connections to your module.
Status indicators
Indicators display the status of communication, module health and input/output devices. Use these indicators to help in troubleshooting.
Top and bottom guides
Guides provide assistance in seating the RTB or IFM cable onto the module.
Jumper bar
Device you can use to connect multiple points in non-isolated wiring application, as shown on page 3-6.
Publication 1756-UM528A-EN-P - April 2004
Page 15
What is the ControlLogix Sequence of Events Module?
Using Module Identification and Status Information
1-5
Each Sequence of Events module maintains specific identification information that separates it from all other modules. This information assists you in tracking all the components of your system. For example, you can track module identification information to be aware of exactly what modules are located in any ControlLogix chassis at any time. While retrieving module identity, you can also retrieve the module’s status. Each module maintains the information listed in Table 1.4: Table 1.4 Module Identification and Status Information Module Identification:
Description:
Product Type
Module’s product type
Product Code
Module’s catalog number
Major Revision
Module’s major revision number
Minor Revision
Module’s minor revision number
Status
Module’s status. Returns the following information: • Controller ownership (if any) • Whether module has been configured • Device Specific Status, such as: • Self-Test • Flash update in progress • Communications fault • Not owned • Internal fault (need flash update) • Run mode • Minor recoverable fault • Minor unrecoverable fault • Major recoverable fault • Major unrecoverable fault
Vendor ID
Module manufacturer vendor, for example Allen-Bradley
Serial Number
Module serial number
Length of ASCII Text String
Number of characters in module’s text string
ASCII Text String
Module’s ASCII text string description
IMPORTANT
You must perform a WHO service to retrieve this information.
Publication 1756-UM528A-EN-P - April 2004
Page 16
1-6
What is the ControlLogix Sequence of Events Module?
Chapter Summary and What’s Next
Publication 1756-UM528A-EN-P - April 2004
In this chapter you read about what the ControlLogix Sequence of Events module is. Chapter 2 explains How Does the Sequence of Events Module Operate in a ControlLogix System?