Page 63
Using the Sequence of Events Module Features
5-11
In the example, a Sequence of Events module: • is Enable CST Capture-enabled for all of its points • uses a 2ms input filter setting for OFF to ON transitions Three possible scenarios can result after an input transitioning from OFF to ON in the given circumstances. • Scenario #1 (no bounce) – The input turns ON and remains for the full 2ms. In this case, the module considers the transition valid and sends the data recorded at the transition to the controller. Figure 5.1 Input turns ON; timestamp recorded Input remains ON for at least 2ms; transition is considered valid and the timestamp is sent to the controller
0
1
2
3
4
5
6
7
8
43671
Time in milliseconds
• Scenario #2 – The input turns ON but turns OFF before 2ms (length of the input filter setting) elapses. In this case, the Sequence of Events module continues to scan the input every 25µs for 4x the length of the input filter setting (i.e., for 8ms). At some point in those 8ms, the input turns ON again and remains for at least 2ms (i.e., the input filter setting). In this case, the module considers the transition valid and sends the data timestamped at the original transition to the controller. Figure 5.2 Input turns ON; timestamp recorded
Input turns OFF before 2ms have elapsed. Input turns ON and remains ON for at least 2ms in the time period that is 4x the input filter setting (i.e., 8ms). The module sends the timestamp recorded at the original transition point to the controller. 43672
0
1
2
3 4 5 6 Time in milliseconds
7
8
Publication 1756-UM528A-EN-P - April 2004
Page 64
5-12
Using the Sequence of Events Module Features
• Scenario #3 – The input turns ON but turns OFF before 2ms (length of the input filter setting) elapses. In this case, the Sequence of Events module continues to scan the input every 25µs for 4x the length of the input filter setting (i.e., for 8ms). In those 8ms, the input never remains ON for at least 2ms (i.e., the input filter setting). In this case, the module considers the transition invalid and drops the data timestamped at the original transition. Figure 5.3 Input turns OFF before 2ms have elapsed.
In none of these time periods is the input ON for at least 2ms After 8ms (i.e., 4x the input filter setting), the module drops the data recorded at the original transition. If an RPI occurs during this 8ms, the module sends the controller its current valid input data; the data that’s sent does not include data from the transition describes in this graphic because the timestamp has not been validated.
Input turns ON; timestamp #1
43671
0
1
2
3
4
5
6
Time in milliseconds
7
8
The next time the input turns ON, the module records the transition as timestamp #1.
Use the Configuration tab in RSLogix 5000 to configure Input Filters, as shown in the example below.
Type the filter times or use the increase/decrease arrows to configure the Input Filter Time. The Input Filter Time range is 0 to 50ms.
Publication 1756-UM528A-EN-P - April 2004
Page 65
Using the Sequence of Events Module Features
5-13
Electronic Keying Instead of plastic mechanical backplane keys, electronic keying allows the ControlLogix system to control what modules belong in the various slots of a configured system. During module configuration, you must choose one of the following keying options for your Sequence of Events module: • Exact Match • Compatible Module • Disable Keying When the controller attempts to connect to and configure a Sequence of Events module (e.g. after program download), the module compares the following parameters before allowing the connection and configuration to be accepted: • Vendor • Product Type • Product Code • Major Revision - Change that affects the module’s function or RSLogix 5000 interface • Minor Revision - Change that does not affect the module’s intended function or RSLogix 5000 interface The comparison is made between the keying information present in the module and the keying information in the controller’s program, preventing the inadvertent operation of a system with the wrong module in the wrong slot. For example, if you select Exact Match and a module with revision 1.2 is placed in a location configured for a module with revision 1.4, the controller does not make a connection to the new module because of the mismatched revisions.
Publication 1756-UM528A-EN-P - April 2004
Page 66
5-14
Using the Sequence of Events Module Features
Table 5.4 describes the keying options available with your module. Table 5.4 Keying option:
Definition:
Exact Match
All of the parameters listed above must match or the inserted module will reject a connection to the controller.
Compatible Module
The Compatible Match mode allows a Sequence of Events module to determine whether it can emulate the module defined in the configuration sent from the controller. With Sequence of Events modules, the module can emulate older revisions. The module will accept the configuration if the configuration’s major.minor revision is less than or equal to the physical module’s revision. For example, if the configuration contains a major.minor revision of 1.7, the module inserted into the slot must have a firmware revision of 1.7 or higher for a connection to be made. When a module is inserted with a major.minor revision that is less than the revision for which the slot is configured (i.e., the module has a revision of 1.6 and the slot is configured for a module with revision 1.8), no connection is made between the controller and the I/O module.
TIP
We recommend using Compatible Match whenever possible. Remember, though, with major revision changes, the module only works to the level of the configuration. At the time of this printing, the Sequence of Events module uses a major revision of 1.3(1) However, if a new major revision for the module is released, consider this example. If a slot is configured for a module with major.minor revision of 1.7 and you insert a module with a major.minor revision of 2.3, the module works at the 1.7 level, with respect to module functions that are related to RSLogix 5000 such as interface changes. Bug fixes that are affected by the module’s firmware, though, would work at the 2.3 revision level. If possible, we recommend that you make sure configuration is updated to match the revision levels of all I/O modules, including your Sequence of Events module. Failure to do so may not prevent the application from working but may defeat the purpose of upgrading your modules’ revision levels.
Disable Keying
The inserted module attempts to accept a connection to the controller regardless of its type. ATTENTION
Be extremely cautious when using the disable keying option; if used incorrectly, this option can lead to personal injury or death, property damage or economic loss.
If keying is disabled, a controller makes a connection with most modules of the same type as that used in the slot configuration. For the ControlLogix Sequence of Events module, if keying is disabled, the controller will only make a connection to another Sequence of Events module. A controller will NOT establish a connection if any of the following conditions exist, even if keying is disabled: • The slot is configured for one module type (e.g. input module) and a module of another type (e.g. output module) is inserted in the slot. • The module inserted into the slot cannot accept some portion of the configuration. For example, if a Sequence of Events module is inserted into a slot configured for a diagnostic input module, the controller cannot make a connection because the module will not accept/process the diagnostic configuration. (1)
Minor revisions are incremented by single counts such that minor level 10 (i.e., major.minor revision level = 1.10) follows minor revision level 9 (i.e., 1.9).
Publication 1756-UM528A-EN-P - April 2004
Page 67
Using the Sequence of Events Module Features
5-15
Module Inhibiting With module inhibiting, you can indefinitely suspend a connection between an owner-controller and a Sequence of Events module. This process can occur in the following way: • You write configuration for a Sequence of Events module but inhibit the module to prevent it from communicating with the owner-controller. In this case, the owner-controller does not establish a connection and configuration is not sent to the module until the connection is uninhibited. The following examples are instances where you may need to use module inhibiting: • You want to FLASH upgrade your module. We recommend you: a. Inhibit the module. b. Perform the upgrade. c. Uninhibit the module. • You are using a program that includes a module that you do not physically possess yet, but you do not want the controller to continually look for a module that does not exist yet. In this case, you can inhibit the module in your program until it physically resides in the proper slot. You can inhibit your Sequence of Events module on the Connection tab in RSLogix 5000, as shown in the example below.
Click on this box to inhibit or uninhibit the module
Publication 1756-UM528A-EN-P - April 2004
Page 68
5-16
Using the Sequence of Events Module Features
Other Inherent Module Features
Table 5.5 lists features on the Sequence of Events module that cannot be configured. Table 5.5 This feature:
is described on:
Removal and Insertion Under Power (RIUP)
5-16
Module Fault Reporting
5-16
Fully Software Configurable
5-17
Producer/Consumer Model
5-17
Status Indicator Information
5-18
Full Class I Division 2 Compliance
5-19
Agency Certifications
5-19
Removal and Insertion Under Power (RIUP) The Sequence of Events module is designed to be installed or removed while chassis power is applied.
WARNING
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
Module Fault Reporting Your Sequence of Events module provides both a hardware and software indication when a module fault occurs. The module’s status indicator and RSLogix 5000 graphically display each fault and include a fault message describing the nature of the fault. This feature allows you to determine how the fault affects your module and what action you should take to resume normal operation. For more information on how to use hardware and software indicators when a module fault occurs, see Chapter 8, Troubleshooting the Sequence of Events Module.
Publication 1756-UM528A-EN-P - April 2004
Page 69
Using the Sequence of Events Module Features
5-17
Fully Software Configurable RSLogix 5000 uses a custom, easily understood interface to write configuration. All module features are enabled or disabled through the I/O configuration portion of the software. You can also use the software to interrogate your Sequence of Events module to retrieve: • serial number • revision information • product code • vendor identification • error/fault information • diagnostic counters. By eliminating such tasks as setting hardware switches and jumpers, the software makes module configuration easier and more reliable.
Producer/Consumer Model By using the Producer/Consumer model, Sequence of Events modules can produce data without having been polled by a controller first. The module produces the data and the owner-controller device consumes it.
Publication 1756-UM528A-EN-P - April 2004
Page 70
5-18
Using the Sequence of Events Module Features
Status Indicator Information Each Sequence of Events module has LED status indicators on the front of the module that allows you to check the module health and operational status. Table 5.6 describes the module’s LED status indicators: Table 5.6 Status:
Description:
I/O status
This yellow display indicates the ON/OFF state of the field device.
(ST LEDs) Module status
This red/green display indicates the module’s communication/module health status.
(OK LED)
The LED status indicators used on the Sequence of Events module are shown in Figure 5.4. Figure 5.4
20945
For more information on how to use the Sequence of Events module’s LED status indicators, and RSLogix 5000, when troubleshooting your application, see Chapter 8, Troubleshooting the Sequence of Events Module.
Publication 1756-UM528A-EN-P - April 2004
Page 71
Using the Sequence of Events Module Features
5-19
Full Class I Division 2 Compliance The Sequence of Events module maintains CSA Class I Division 2 system certification. This allows the ControlLogix system to be placed in an environment other than only a 100% hazard free. IMPORTANT
Modules should not be pulled under power, nor should a powered RTB be removed, in a Class I Division 2 environment.
Agency Certifications The Sequence of Events module is marked for any agency certifications (e.g. UL, CSA, CE, FM and C-Tick) it has obtained. See the module’s label for all agency certifications.
Chapter Summary and What’s Next
In this chapter, you read about using the Sequence of Events module’s features. Chapter 6 describes the Using The Sequence of Events Module in CST Per Point Mode.
Publication 1756-UM528A-EN-P - April 2004
Page 72
5-20
Using the Sequence of Events Module Features
Notes: