Installation instructions for the Allen-Bradley ControlLogix Sercos interface modules (1756-M03SE, 1756-M08SE, 1756-M016SE, 1756-M08SEG and their K versions), which link a ControlLogix controller to Sercos interface drives over fiber-optic cables. They cover installation requirements, installing and removing the module, connecting the fiber-optic cables, reading the status indicators, and technical and environmental specifications, with a list of additional resources.

Its parts

  1. Installation Requirements
  2. Install the Module
  3. Connect the Fiber-optic Cables
  4. Check Status Indicators
  5. Remove the Module from the Chassis
  6. Specifications
  7. Additional Resources

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1756-IN572H-EN-P, August 2017) for the ControlLogix Sercos interface modules 1756-M03SE, 1756-M03SEK, 1756-M08SE, 1756-M08SEK, 1756-M016SE, 1756-M016SEK, 1756-M08SEG and 1756-M03SEGK. These modules link a ControlLogix controller to Sercos interface drives over fiber-optic cable. The sheet covers installing and removing the module, connecting the fiber-optic ring, reading the status lights, and the technical and environmental specifications.

What it is
ControlLogix module linking a ControlLogix controller to Sercos interface drives p. 1
Drives, max
3, 8 or 16, depending on the catalog number p. 7
Sercos data rate
4 Mbps or 8 Mbps p. 7
Sercos cycle time
At 4 Mbps: 0.5 ms up to two drives, 1 ms up to four, 2 ms up to eight; at 8 Mbps: 0.5 ms up to four, 1 ms up to eight, 2 ms up to 16 p. 7
Field connections
Fiber-optic receiver and transmitter ports, cables screwed on finger tight p. 1, 5
Fiber-optic cables
Plastic: 2090-SCEPxx-0, 2090-SCVPxx-0, 2090-SCNPxx-0; glass: 2090-SCVGxx-0 p. 7
Drive control modes
Position, velocity and torque p. 7
Backplane power
760 mA at 5.1V DC and 2.5 mA at 24V DC; 5.0 W dissipation p. 7
Slot
One slot wide; any slot of the chassis p. 7
Chassis
1756-A4, 1756-A4K, 1756-A7, 1756-A7K, 1756-A10, 1756-A10K, 1756-A13, 1756-A13K, 1756-A17, 1756-A17K p. 7
Power supplies
1756-PA72/C, 1756-PA72K/C, 1756-PA75/B, 1756-PA75K/B, 1756-PB72/C, 1756-PB72K/C, 1756-PB75/B, 1756-PB75K/B, 1756-PC75/B, 1756-PH75/B p. 7
Redundant power supplies
1756-PA75R, 1756-PA75RK, 1756-PB75R, 1756-PB75RK, 1756-PSCA2, 1756-PSCA2K p. 7
Operating temperature
0 to 60 °C (32 to 140 °F) p. 8
Storage temperature
-40 to 85 °C (-40 to 185 °F) p. 8

What this manual walks you through

  • Preparing the ControlLogix chassis and power supply p. 4
  • Installing the module in the chassis p. 4
  • Connecting the fiber-optic cables p. 5
  • Reading the CP, Sercos ring and OK status lights p. 5, 6
  • Removing the module from the chassis p. 7
  • Technical and environmental specifications p. 7, 8

Good to know

  • Each drive on the Sercos ring needs a unique address; two drives with the same address both respond to commanded motion. p. 5
  • Any break in the fiber-optic ring disables the Sercos network. p. 5
  • Inserting or removing the module with backplane power on can cause an arc; remove power or make sure the area is nonhazardous first. p. 4
  • The 0.5 ms cycle time is for Kinetix 6000 drives. p. 7
  • Do not try to repair or dismantle a faulty module; return it to the manufacturer. p. 4

Questions this manual answers

What data rates does the 1756-M08SE Sercos module support?

4 Mbps or 8 Mbps. p. 7

What does a solid red OK light on a ControlLogix Sercos module mean?

A potential nonrecoverable fault. Restart the module, and replace it if the solid red stays. p. 6

What does a flashing red CP light mean on a 1756-M08SE?

The module is in Sercos communication phase 1, looking for active nodes. p. 6

Which fiber-optic cables work with the 1756-M08SE?

Plastic 2090-SCEPxx-0, 2090-SCVPxx-0 or 2090-SCNPxx-0 cables, or glass 2090-SCVGxx-0 cable. p. 7

Can the 1756-M08SE be installed with the power on?

Yes, with chassis and field-side power on, but an arc can occur, so remove power or make sure the area is nonhazardous first. p. 4

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. ControlLogix Sercos Interface Module Installation Instructions1
    1. Installation Requirements4
    2. Install the Module4
    3. Connect the Fiber-optic Cables5
    4. Check Status Indicators5
    5. Remove the Module from the Chassis7
    6. Specifications7
    7. Additional Resources10
  2. Back Cover10

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10

The file

Revision and size

RevisionPublication 1756-IN572H-EN-P, August 2017
PublisherRockwell Automation
Pages10
PDF752 KB
TextText from the PDF itself.

The first pages · 3 of 10

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 10
Page 2
Page 2of 10
Page 3
Page 3of 10

More documents · 1

For the same models