Manual · Allen-Bradley
ControlLogix Sercos Interface Module Installation Instructions
Manual10 pagesPDF 752 KB
Installation instructions for the Allen-Bradley ControlLogix Sercos interface modules, including the 1756-M03SE, 1756-M08SE and 1756-M016SE.
Covers · 1 model
The models it covers
Summary
What is in it
Installation instructions for the Allen-Bradley ControlLogix Sercos interface modules (1756-M03SE, 1756-M08SE, 1756-M016SE, 1756-M08SEG and their K versions), which link a ControlLogix controller to Sercos interface drives over fiber-optic cables. They cover installation requirements, installing and removing the module, connecting the fiber-optic cables, reading the status indicators, and technical and environmental specifications, with a list of additional resources.
Its parts
- Installation Requirements
- Install the Module
- Connect the Fiber-optic Cables
- Check Status Indicators
- Remove the Module from the Chassis
- Specifications
- Additional Resources
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (publication 1756-IN572H-EN-P, August 2017) for the ControlLogix Sercos interface modules 1756-M03SE, 1756-M03SEK, 1756-M08SE, 1756-M08SEK, 1756-M016SE, 1756-M016SEK, 1756-M08SEG and 1756-M03SEGK. These modules link a ControlLogix controller to Sercos interface drives over fiber-optic cable. The sheet covers installing and removing the module, connecting the fiber-optic ring, reading the status lights, and the technical and environmental specifications.
- What it is
- ControlLogix module linking a ControlLogix controller to Sercos interface drives p. 1
- Drives, max
- 3, 8 or 16, depending on the catalog number p. 7
- Sercos data rate
- 4 Mbps or 8 Mbps p. 7
- Sercos cycle time
- At 4 Mbps: 0.5 ms up to two drives, 1 ms up to four, 2 ms up to eight; at 8 Mbps: 0.5 ms up to four, 1 ms up to eight, 2 ms up to 16 p. 7
- Field connections
- Fiber-optic receiver and transmitter ports, cables screwed on finger tight p. 1, 5
- Fiber-optic cables
- Plastic: 2090-SCEPxx-0, 2090-SCVPxx-0, 2090-SCNPxx-0; glass: 2090-SCVGxx-0 p. 7
- Drive control modes
- Position, velocity and torque p. 7
- Backplane power
- 760 mA at 5.1V DC and 2.5 mA at 24V DC; 5.0 W dissipation p. 7
- Slot
- One slot wide; any slot of the chassis p. 7
- Chassis
- 1756-A4, 1756-A4K, 1756-A7, 1756-A7K, 1756-A10, 1756-A10K, 1756-A13, 1756-A13K, 1756-A17, 1756-A17K p. 7
- Power supplies
- 1756-PA72/C, 1756-PA72K/C, 1756-PA75/B, 1756-PA75K/B, 1756-PB72/C, 1756-PB72K/C, 1756-PB75/B, 1756-PB75K/B, 1756-PC75/B, 1756-PH75/B p. 7
- Redundant power supplies
- 1756-PA75R, 1756-PA75RK, 1756-PB75R, 1756-PB75RK, 1756-PSCA2, 1756-PSCA2K p. 7
- Operating temperature
- 0 to 60 °C (32 to 140 °F) p. 8
- Storage temperature
- -40 to 85 °C (-40 to 185 °F) p. 8
What this manual walks you through
- Preparing the ControlLogix chassis and power supply p. 4
- Installing the module in the chassis p. 4
- Connecting the fiber-optic cables p. 5
- Reading the CP, Sercos ring and OK status lights p. 5, 6
- Removing the module from the chassis p. 7
- Technical and environmental specifications p. 7, 8
Good to know
- Each drive on the Sercos ring needs a unique address; two drives with the same address both respond to commanded motion. p. 5
- Any break in the fiber-optic ring disables the Sercos network. p. 5
- Inserting or removing the module with backplane power on can cause an arc; remove power or make sure the area is nonhazardous first. p. 4
- The 0.5 ms cycle time is for Kinetix 6000 drives. p. 7
- Do not try to repair or dismantle a faulty module; return it to the manufacturer. p. 4
Questions this manual answers
What data rates does the 1756-M08SE Sercos module support?
4 Mbps or 8 Mbps. p. 7
What does a solid red OK light on a ControlLogix Sercos module mean?
A potential nonrecoverable fault. Restart the module, and replace it if the solid red stays. p. 6
What does a flashing red CP light mean on a 1756-M08SE?
The module is in Sercos communication phase 1, looking for active nodes. p. 6
Which fiber-optic cables work with the 1756-M08SE?
Plastic 2090-SCEPxx-0, 2090-SCVPxx-0 or 2090-SCNPxx-0 cables, or glass 2090-SCVGxx-0 cable. p. 7
Can the 1756-M08SE be installed with the power on?
Yes, with chassis and field-side power on, but an arc can occur, so remove power or make sure the area is nonhazardous first. p. 4
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file