Manual · Allen-Bradley
SERCOS and Analog Motion Configuration and Startup User Manual
Manual297 pagesPDF 13 MB
User manual for configuring and starting up SERCOS and analog motion with Logix controllers and modules such as the 1756-M08SE.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation's configuration and startup manual for SERCOS and analog motion control in Logix Designer. It covers the 1756-HYD02, 1756-M02AE, 1756-M02AS, 1756-M03SE, 1756-M08SE, 1756-M16SE and 1768-M04SE motion modules and Kinetix 6200 control modules. Readers learn to add motion modules, drives, motion groups and axes, commission and tune axes, handle motion faults, use Motion Direct Commands, program motion, and home an axis, with reference appendices on axis properties and attributes.
Its parts
- Preface
- Configure SERCOS motion
- Configure analog motion
- Commission and tune
- Program
- Home an axis
From the manual
Key facts from this manual
Each line names its page in the PDF.
Configuration and startup user manual (publication MOTION-UM001H-EN-P, November 2018) for Logix SERCOS and analog motion control. It covers the 1756-HYD02, 1756-M02AE, 1756-M02AS, 1756-M03SE, 1756-M08SE, 1756-M16SE and 1768-M04SE motion modules and the 2094-SE02F-M00-S0 and 2094-SE02F-M00-S1 Kinetix 6200 control modules. It walks through setting up a motion project in Studio 5000 Logix Designer, adding modules and axes, testing wiring, tuning and homing.
- What it is
- 1756-M03SE, 1756-M08SE, 1756-M16SE, 1768-M04SE: SERCOS interface modules connecting the controller to SERCOS interface drives p. 12
- Protocol
- SERCOS (IEC 61491) over a fiber optic network p. 12
- SERCOS system needs
- Logix L6x, L7x or L8x controller; SERCOS interface drive (6000, 6200, 2000, Ultra3000); SERCOS interface module; Logix Designer application p. 11
- Ring cycle times
- 4 Mbps: 0.5 ms up to 2 drives, 1 ms up to 4, 2 ms up to 8, 9 to 16 not supported; 8 Mbps: 0.5 ms up to 4, 1 ms up to 8, 2 ms up to 16 p. 26, 27
- Axis data type
- AXIS_SERVO_DRIVE for the 1756-M03SE, 1756-M08SE, 1756-M16SE and 1768-M04SE p. 35
- Electronic keying
- Compatible Keying or Exact Match; never Disable Keying with motion modules p. 24
- Module firmware
- Use the firmware revision that goes with the controller's firmware revision p. 23
- Software
- Studio 5000 Logix Designer; screens updated for versions 31 and later p. 3
- 1756-M02AE
- 1756-M02AE: two-axis servo module for ±10V velocity or torque reference drives with quadrature encoder feedback p. 12
- 1756-M02AE inputs
- 1756-M02AE: home limit switch and drive fault inputs, drive enable outputs, 5V or 24V registration inputs, 250 µs loop updates p. 12
- 1756-HYD02
- 1756-HYD02: two-axis servo module for hydraulic actuators, ±10V velocity reference, LDT feedback p. 13
- 1756-M02AS
- 1756-M02AS: two-axis servo module with Serial Synchronous Input (SSI) position feedback p. 13
- Kinetix 6200 control modules
- 2094-SE02F-M00-S0, 2094-SE02F-M00-S1: SERCOS to the controller, EtherNet/IP for the safety configuration tool p. 12
What this manual walks you through
- Creating a controller project p. 19
- Setting time synchronization (CIP Sync) p. 22
- Adding a SERCOS motion module and choosing electronic keying p. 23, 24
- Setting the SERCOS data rate and cycle time p. 26, 27
- Adding and configuring an axis p. 35, 36, 37
- Testing axis wiring and direction p. 63, 64
- Tuning a SERCOS axis p. 64
- Homing an axis: active, passive and absolute homing p. 111
Good to know
- Never use Disable Keying with motion modules. p. 24
- Keep Major Fault on Controller If Connection Fails clear until the program runs the first time, or the controller faults when the ring first phases up. p. 26
- The hookup tests and tuning move the axis even with the controller in remote program mode. p. 64
- The Ultra 3000 needs a 1 or 2 ms SERCOS cycle time. p. 27
- Changing electronic keying online interrupts connections to the device and devices connected through it. p. 25
Questions this manual answers
What axis data type do I use with a 1756-M08SE?
AXIS_SERVO_DRIVE, the type for the 1756-M03SE, 1756-M08SE, 1756-M16SE and 1768-M04SE SERCOS modules. p. 35
What SERCOS cycle time can I use with 8 drives on the ring?
Which controllers work for SERCOS motion?
A Logix L6x, L7x or L8x controller, with a SERCOS interface module and drive. p. 11
Which electronic keying should I choose for a SERCOS module?
Compatible Keying or Exact Match. Disable Keying should never be used with motion modules. p. 24
Can an Ultra3000 run a 0.5 ms SERCOS cycle time?
No. The Ultra 3000 must use a 1 or 2 ms cycle time because its minimum position loop update time is 1 ms. p. 27
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 30 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 150141-150
- Pages 151 to 160151-160
- Pages 161 to 170161-170
- Pages 171 to 180171-180
- Pages 181 to 190181-190
- Pages 191 to 200191-200
- Pages 201 to 210201-210
- Pages 211 to 220211-220
- Pages 221 to 230221-230
- Pages 231 to 240231-240
- Pages 241 to 250241-250
- Pages 251 to 260251-260
- Pages 261 to 270261-270
- Pages 271 to 280271-280
- Pages 281 to 290281-290
- Pages 291 to 297291-297