Page 81

Commission and tune

Chapter 3 the error text field. The message ‘MOTION GROUP SHUTDOWN executed!’ appears to indicate that shutdown is complete. If the command fails, then an error is indicated as per normal operation.

Motion Direct Command error process

When executing a Motion Direct Command, there are two levels of error detections. •

The first level is verification of the command’s operands. If a verification error is detected, a message ‘Failed to Verify’ is posted on the dialog box and a message is posted to the error result window.

•

The second level is the initial motion direct command’s error response return code. If an error code is detected, an ‘Execution Error’ message appears on the dialog box.

Regardless of whether an error is detected, a message appears in the Error result window describing the results of the executed command.

Motion Direct Command verification

When selecting Execute from a Motion Direct Command dialog box, the operands are verified. If any operand fails verification, a ’Failed to Verify’ message appears on the dialog box. A detailed error message appears in the Errors result window describing the fault.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

81

Page 82

Chapter 3

Commission and tune

This allows multiple verification errors to appear and provides navigation to the error source. Double-click the error in the Errors window to open the Motion Direct Command dialog box.

If no errors are detected, the status indicates the executed instruction and states no errors.

Motion Direct Command execution error

82

When selecting Execute from a Motion Direct Command dialog box and the operands are verified as valid, the command is executed. If the command fails immediately, an ‘Execution Error’ message appears on the dialog box. Regardless

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 83

Commission and tune

Chapter 3 of whether an error is detected, a detailed message appears in the Error result window describing the immediate results of the executed command.

The message ‘Execution Error’ clears on subsequent command execution or if selecting a new command. The information provided in the error result window after an execution is not cleared and provides a history of what was executed.

What if the software goes offline or the controller changes modes? Can two workstations give Motion Direct Commands?

When the Logix Designer application transitions to Off-line and Direction Command instructions continue, if the controller Mode is changed, then the configured ‘Programmed Stop Mode’ controls what happens to motion. When Execute is enabled and commands can be executed from a workstation, the group is locked. This means that another workstation cannot execute commands while this lock is in place. The lock is relinquished when all Motion Direct Command dialog boxes for the Motion Group are closed.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

83

Page 84

This page is a scan with no text; see it in the PDF.

Page 85

Chapter 4

Program

Introduction

This chapter describes how to program a velocity profile and jerk rate. Use these motion profiles for various instructions:

Definition of Jerk

•

Trapezoidal profile for linear acceleration and deceleration

•

S-curve profiles for controlled jerk

Jerk is the rate of change of acceleration or deceleration. The jerk parameters only apply to S-curve profile moves using these instructions. • MAJ

• MCS

• MAM

• MCCD

• MAS

• MCCM

• MCD

• MCLM

Example: If acceleration changes from 0 to 40 mm/s2 in 0.2 seconds, the jerk is: (40 mm/s2 - 0 mm/s2) / 0.2 s = 200 mm/s3

Choose a profile

Consider cycle time and smoothness when choosing a profile.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

85

Page 86

Chapter 4

Program

To accomplish

Choose this profile

• Fastest acceleration and deceleration times Trapezoidal • More flexibility in programming subsequent motion

Consideration Jerk does not limit the acceleration and deceleration time: • The Acceleration and Deceleration rates control the maximum change in Velocity. • The equipment and load get more stress than with an S-curve profile. • Jerk is considered infinite and is shown as a vertical line.

Smoother acceleration and deceleration that reduces the stress on the equipment and load

Jerk limits the acceleration and deceleration time. • More time is needed to accelerate and decelerate than a trapezoidal profile.

S-curve

• If the instruction uses an S-curve profile, the controller calculates acceleration, deceleration, and jerk when starting the instruction. • The controller calculates triangular acceleration and deceleration profiles.

Jerk Rate Calculation

If the instruction uses or changes an S-curve profile, the controller calculates acceleration, deceleration, and jerk when starting the instruction. The system has a Jerk priority planner. In other words, Jerk has a higher priority than acceleration and velocity. Therefore, the programmed Jerk is always present. If a move is velocity-limited, the move does not reach the programmed acceleration or velocity.

86

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 87

Program

Chapter 4

Jerk Parameters for MAJ programmed in units of % time are converted to engineering units. If Start Speed < MAJ Programmed Speed

If Start Velocity > MAJ Programmed Speed

Jerks for programmed moves, such as MAM or MCLM instructions, in units of % time are converted to engineering units as follows: If Start Speed < Programmed Speed

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

87

Page 88

Chapter 4

Program

If Start Speed > Programmed Speed

Depending on the instruction’s Speed parameter, the same ‘% of time jerk’ can result in slopes for the acceleration profile that differ from the deceleration profile.

88

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 89

Program

Chapter 4

The motion planner algorithm adjusts the actual jerk rate so that the acceleration profile and the deceleration profile contains at least the '% of time' ramp time. If the Start Speed is close to the programmed Speed parameter, the actual percentage of ramp time may be higher than the programmed value. In most cases the condition is: if: (start Speed is == 0.0) OR (start Speed is > 2 * max Speed) then: get programmed percentage of ramp time else: get higher than programmed percentage of ramp time

Conversion from Engineering Units to To convert Engineering Units to % of Time, use these equations: % of Time For Accel Jerk:

For Decel Jerk:

Use % of Time for the easiest programming of jerk

Use % of Time to specify how much of the acceleration or deceleration time has jerk. Calculating actual jerk values is not necessary.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

89

Page 90

Chapter 4

Program

Example

Profile

100% of Time

At 100% of Time, the acceleration or deceleration changes the entire time that the axis speeds up or slows down.

60% of Time

At 60% of Time, the acceleration or deceleration changes 60% of the time that the axis speeds up or slows down. The acceleration or deceleration is constant for the other 40%.

Velocity Profile Effects

This table summarizes the differences between profiles.

90

Profile

ACC/DEC

Motor

Priority of Control

Type

Time

Stress

Highest to Lowest

Trapezoidal

Fastest

Worst

Acc/Dec

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Velocity

Position