Page 261

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Tune Rise Time

AXIS_SERVO

REAL

GSV

Seconds The Tune Rise Time attribute returns the axis rise time as measured during the tuning procedure. This value is only applicable to axes configured for interface to an external velocity servo drive. In this case, the Tune Rise Time attribute value is used to calculate the Tune Velocity Bandwidth.

Tune Speed Scaling

AXIS_SERVO

REAL

GSV

% / KiloCounts Per Seconds The Tune Speed Scaling attribute returns the axis drive scaling factor measured during the tuning procedure. This value is only applicable to axes configured for interface to an external velocity servo drive. In this case, the Tune Speed Scaling attribute value is directly applied to the Velocity Scaling attribute by a subsequent MAAT (Motion Apply Axis Tune) instruction.

Tune Status

AXIS_SERVO AXIS_SERVO_DRIVE

INT

GSV

0 = tune process successful 1 = tune in progress 2 = tune process aborted by user 3 = tune process timed out 4 = AXIS_SERVO, tune process failed due to servo fault = AXIS_SERVO_DRIVE, tune process failed due to drive fault 5 = axis reached Tuning Travel Limit 6 = axis polarity set incorrectly More codes for a AXIS_SERVO_DRIVE 7 = tune measurement fault 8 = tune configuration fault The Tune Status attribute returns status of the last run MRAT (Motion Run Axis Tuning) instruction that initiates a tuning procedure on the targeted axis. Use the attribute to determine when the MRAT initiated operation successfully completed. Conditions may occur, however, that make it impossible for the control to properly perform the operation. When this is the case, the tune process is automatically aborted and a tune fault reported that is stored in the Tune Status output parameter.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

261

Page 262

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Tuning Configuration Bits

AXIS_SERVO AXIS_SERVO_DRIVE

DINT

GSV SSV

Bits 0 = Tuning Direction Reverse 1 = Tune Position Error Integrator 2 = Tune Velocity Error Integrator 3 = Tune Velocity Feedforward 4 = Tune Acceleration Feedforward 5 = Tune Output Low-Pass Filter 6 = bidirectional Tuning 7 = Tune Backlash Compensation 8 = Tune Torque Offset Tuning Direction Reverse The Tune Direction Reverse bit determines the direction of the tuning procedure. If this bit is set (true), motion is initiated in the reverse (or negative) direction. Tune Position Error Integrator If this bit is: • ON, The tuning procedure calculates the Position Integral Gain. • OFF, The tuning procedure sets the Position Integral Gain to 0. Tune Velocity Error Integrator If this bit is: • ON, The tuning procedure calculates the Velocity Integral Gain. • OFF, The tuning procedure sets the Velocity Integral Gain to 0. Tune Velocity Feedforward If this bit is: • ON, The tuning procedure calculates the Velocity Feedforward Gain. • OFF, The tuning procedure sets the Velocity Feedforward Gain to 0. Tune Acceleration Feedforward If this bit is: • ON, The tuning procedure calculates the Acceleration Feedforward Gain. • OFF, The tuning procedure sets the Acceleration Feedforward Gain to 0. Tune Output Low-Pass Filter If this bit is: • ON, The tuning procedure calculates the Output Filter Bandwidth. • OFF, The tuning procedure sets the Output Filter Bandwidth to 0, which disables the filter.

262

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 263

Motion axis attributes

Attribute

Appendix B

Axis Type

Data Type

Access

Tuning Configuration Bits (continued)

Description Bidirectional Tuning The Bidirectional Tuning bit determines whether the tuning procedure is unidirectional or bidirectional. If this bit is set (true), the tuning motion profile is first initiated in the specified tuning direction and then is repeated in the opposite direction. Information returned by the Bidirectional Tuning profile can be used to tune Backlash Compensation and Torque Offset. When configured for a hydraulics External Drive Type, the bidirectional tuning algorithm also computes the Directional Scaling Ratio. Tune Backlash Compensation This tuning configuration is only valid if configured for bidirectional tuning. If this bit is: • ON, The tuning procedure calculates the Backlash Compensation Gain. • OFF, The Backlash Compensation Gain is not affected. Tune Torque Offset This tuning configuration is only valid if configured for bidirectional tuning. If this bit is: • ON, The tuning procedure calculates the Torque Offset. • OFF, The Torque Offset is not affected.

Tuning Speed

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / Seconds The Tuning Speed attribute sets the maximum speed of the tuning procedure. This attribute should be set to the desired maximum operating speed of the motor before running the tuning procedure. The tuning procedure measures maximum acceleration and deceleration rates based on ramps to and from the Tuning Speed. Thus, the accuracy of the measured acceleration and deceleration capability is reduced by tuning at a speed other than the desired operating speed of the system.

Tuning Torque

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

% The Tuning Torque attribute determines the maximum torque of the tuning procedure. This attribute should be set to the desired maximum safe torque level before running the tuning procedure. The default value is 100%, which yields the most accurate measure of the acceleration and deceleration capabilities of the system. In some cases, a lower tuning torque limit value may be desirable to limit the stress on the mechanics during the tuning procedure. In this case, the acceleration and deceleration capabilities of the system are extrapolated based on the ratio of the tuning torque to the maximum torque output of the system. Note that the extrapolation error increases as the Tuning Torque value decreases.

Tuning Travel Limit

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units The Tuning Travel Limit attribute limits the travel of the axis during the tuning procedure. If the axis cannot complete the tuning procedure before exceeding the Tuning Travel Limit, the motion module stops the tuning procedure and reports that the Tuning Travel Limit was exceeded via the Tune Status attribute. This does not mean that the Tuning Travel Limit was actually exceeded, but that had the tuning procedure gone to completion, the limit would be exceeded.

Velocity Command

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Velocity Command in Position Units / Seconds Velocity Command is the current velocity reference to the velocity servo loop, in the configured axis Position Units per Second, for the specified axis. The Velocity Command value, hence, represents the output of the outer position control loop. Velocity Command is not to be confused with Command Velocity, which represents the rate of change of Command Position input to the position servo loop.

Velocity Data Scaling

AXIS_SERVO_DRIVE

INT

GSV

This attribute is derived from the Drive Units attribute. See IDN 44 in IEC 1491.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

263

Page 264

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Velocity Data Scaling Exp

AXIS_SERVO_DRIVE

INT

GSV

This attribute is derived from the Drive Units attribute. See IDN 46 in IEC 1491.

Velocity Data Scaling Factor

AXIS_SERVO_DRIVE

DINT

GSV

This attribute is derived from the Drive Units attribute. See IDN 45 in IEC 1491.

Velocity Droop

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Error

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Velocity Error in Position Units / Seconds Velocity Error is the difference, in configured axis Position Units per Second, between the commanded and actual velocity of an axis. For an axis with an active velocity servo loop, velocity error is used, along with other error terms, to drive the motor to the condition where the velocity feedback is equal to the velocity command..

Velocity Feedback

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Velocity Feedback in Position Units / Seconds Velocity Feedback is the actual velocity of the axis as estimated by the motion module, in the configured axis Position Units per second. The estimated velocity is computed by applying a 1 KHz low-pass filter to the change in actual position over the servo update interval. Velocity Feedback is a signed value - the sign (+ or -) depends on which direction the axis is currently moving.

264

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 265

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Velocity Feedforward Gain

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

% This controller attribute is replicated in the motion module. Servo Drives require non-zero command input to generate steady-state axis acceleration or velocity. To provide the non-zero output from the Servo Module, a non-zero position or velocity error needs to be present. This is called dynamic error while moving ‘following error’. This non-zero following error condition is a situation to try to avoid. Ideally zero should follow the error. This could be achieved through use of the position integral gain controls as described above, but typically the response time of the integrator action is too slow to be effective. An alternative approach with superior dynamic response is to use Velocity and Acceleration Feedforward. The Velocity Feedforward Gain attribute is used to provide the Velocity Command output necessary to generate the commanded velocity. It does this by scaling the current Command Velocity by the Velocity Feedforward Gain and adding it as an offset to the Velocity Command generated by the position loop control elements. With this done, the position loop control elements do not need to generate much of a contribution to the Velocity Command, hence, the Position Error value is significantly reduced. Hence, the Velocity Feedforward Gain allows the error of the servo system that follows to be reduced to nearly zero when running at a constant speed. This is important in applications such as electronic gearing and synchronization applications where it is necessary that the actual axis position not significantly lag behind the commanded position at any time. The optimal value for Velocity Feedforward Gain is 100% theoretically. In reality, however, the value may need to be tweaked to accommodate velocity loops with non-infinite loop gain and other application considerations. One thing that may force a smaller Velocity Feedforward value is that increasing amounts of feedforward tends to exacerbate axis overshoot. If necessary, the Velocity Feedforward Gain may be ‘tweaked’ from the 100% value by running a simple user program that jogs the axis in the positive direction and monitor the Position Error of the axis during the jog. Increase the Velocity Feedforward Gain until the Position Error at constant speed is as small as possible, but still positive. If the Position Error at constant speed is negative, the actual position of the axis is ahead of the command position. If this occurs, decrease the Velocity Feedforward Gain such that the Position Error is again positive. Note that reasonable maximum velocity, acceleration, and deceleration values must be entered to jog the axis.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

265

Page 266

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Velocity Integral Gain

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

1/mSeconds-Seconds This controller attribute is replicated in the motion module. When configured for a torque (current) loop servo drive, every servo update, the current Velocity Error is also accumulated in a variable called the Velocity Integral Error. This value is multiplied by the Velocity Integral Gain to produce a component to the Servo Output or Torque Command that attempts to correct for the velocity error. The characteristic of Vel I Gain correction, however, is that any non-zero Velocity Error accumulates in time to generate enough force to make the correction. This attribute of Vel I Gain makes it invaluable in applications where velocity accuracy is critical. The higher the Vel I Gain value the faster the axis is driven to the zero Velocity Error condition. Unfortunately, I Gain control is intrinsically unstable. Too much I Gain results in axis oscillation and servo instability. In certain cases, Vel I Gain control is disabled. One such case is when the servo output to the axis’ drive is saturated. Continuing integral control behavior in this case would only exacerbate the situation. Another common case is when performing certain motion. When the Integrator Hold Enable attribute is set, the servo loop automatically disables the integrator during commanded motion. Due to the destabilizing nature of Integral Gain, it is recommended that Position Integral Gain and Velocity Integral Gain be considered mutually exclusive. If Integral Gain is needed for the application, use one or the other. In general, where static positioning accuracy is required, Velocity Integral Gain is the better choice. The typical value for the Velocity Integral Gain is ~15 mSec-1-Sec-1. If you have an AXIS_SERVO_DRIVE data type… While the Vel I Gain, if employed, is typically established by the automatic servo tuning procedure, the Pos I Gain value may also be set manually. Before doing this, it must be stressed that the Torque Scaling factor for the axis must be established for the drive system. See Torque Scaling attribute description for an explanation of how the Torque Scaling factor can be calculated. Once this is done, the Vel I Gain can be computed based on the current or computed value for the Vel P Gain using this formula: Vel I Gain = 0.25 * 0.001 Sec/mSec * (Vel P Gain)2 Assuming a Vel P Gain value of 0.25 Sec-1, this results in a Vel I Gain value of ~15.6 mSec-1Sec-1-

Velocity Integrator Error

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Velocity Integrator Error in Position Units – mSec / Sec Velocity Integrator Error is the running sum of the Velocity Error, in the configured axis Position Units per Second, for the specified axis. For an axis with an active velocity servo loop, the velocity integrator error is used, along with other error terms, to drive the motor to the condition where the velocity feedback is equal to the velocity command.

Velocity Limit Bipolar

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Limit Negative AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Limit Positive

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Limit Status

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the magnitude of the commanded velocity to the velocity servo loop input is greater than the configured Velocity Limit.

266

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 267

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Velocity Lock Status

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the magnitude of the physical axis Velocity Feedback is within the configured Velocity Window of the current velocity command.

Velocity Offset

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV Tag

Velocity Offset in Position Units / Sec Velocity Offset compensation can be used to give a dynamic velocity correction to the output of the position servo loop. Since this value is updated synchronously every Base Update Period, the Velocity Offset can be tied into custom outer control loop algorithms using Function Block programming.

Velocity Polarity

AXIS_SERVO_DRIVE

INT

GSV

This attribute is derived from the Drive Polarity attribute. See IDN 42 in IEC 1491.

Velocity Proportional Gain

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

1/Seconds This controller attribute is replicated in the motion module. AXIS_SERVO When configured for a torque (current) loop servo drive, the servo module’s digital velocity loop provides damping without the requirement for an analog tachometer. The Velocity Error is multiplied by the Velocity Proportional Gain to produce a component to the Servo Output or Torque Command that ultimately attempts to correct for the velocity error, creating the damping effect. Thus, increasing the Velocity Proportional Gain results in smoother motion, enhanced acceleration, reduced overshoot, and greater system stability. The velocity loop also allows higher effective position loop gain values to be used, however, too much Velocity Proportional Gain leads to high frequency instability and resonance effects. Note that units for Velocity Proportional Gain are identical to that of the Position Proportional Gain making it easy to perform classic inches/min/mil calculations to determine static stiffness or damping. Maximum Bandwidth There are limitations to the maximum bandwidth that can be achieved for the velocity loop based on the dynamics of the torque loop of the servo drive and the desired damping of the system, Z. These limitations may be expressed as: Bandwidth (Velocity) = 0.25 * 1/Z2 * Bandwidth (Torque)follow For example, if the bandwidth of the drive’s torque loop is 100 Hz and the damping factor, Z, is 0.8, the velocity bandwidth is approximately 40 Hz. Based on this number, the corresponding gains for the loop can be computed. Note that the bandwidth of the torque loop includes feedback sampling delay and filter time constant. The velocity loop in the motion controller is not used when the servo module is configured for a velocity loop servo drive, Thus, establishing the Velocity Proportional Gain is not required in this case. The typical value for the Velocity Proportional Gain is ~250 Sec-1.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

267

Page 268

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Velocity Proportional Gain (continued)

Velocity Scaling

268

Description AXIS_SERVO_DRIVE The standard RA SERCOS drive’s digital velocity loop provides damping without the requirement for an analog tachometer. The Velocity Error is multiplied by the Velocity Proportional Gain to produce a Torque Command that ultimately attempts to correct for the velocity error, creating the damping effect. Thus, increasing the Velocity Proportional Gain results in smoother motion, enhanced acceleration, reduced overshoot, and greater system stability. The velocity loop also allows higher effective position loop gain values to be used, however, too much Velocity Proportional Gain leads to high frequency instability and resonance effects. Note that units for Velocity Proportional Gain are identical to that of the Position Proportional Gain making it easy to perform classic calculations to determine damping and bandwidth. If the desired unity gain bandwidth of the velocity servo in Hertz is known, use this formula to calculate the corresponding P gain. Vel P Gain = Bandwidth (Hertz) / 6.28 In general, modern velocity servo systems typically run with a unity gain bandwidth of ~40 Hertz. The typical value for the Velocity Proportional Gain is ~250 Sec-1. Maximum Bandwidth There are limitations to the maximum bandwidth that can be achieved for the velocity loop based on the dynamics of the inner torque loop of the system and the desired damping of the system, Z. These limitations may be expressed as: Bandwidth (Velocity) = 0.25 * 1/Z2 * Bandwidth (Torque) For example, if the bandwidth of the drive’s torque loop is 100 Hz and the damping factor, Z, is 0.8, the velocity bandwidth is approximately 40 Hz. Based on this number, the corresponding gains for the loop can be computed. Note that the bandwidth of the torque loop includes feedback sampling delay and filter time constant.

AXIS_SERVO

REAL

GSV SSV

% / Position Units Per Second This controller attribute is replicated in the motion module. The Velocity Scaling attribute is used to convert the output of the servo loop into equivalent voltage to an external velocity servo drive. This ‘normalizes’ the units of the servo loop gain parameters so that their values are not affected by variations in feedback resolution, drive scaling, or mechanical gear ratios. The Velocity Scaling value is typically established by servo’s automatic tuning procedure but these values can be calculated, if necessary, using these guidelines. If the axis is using a velocity servo drive, the software velocity loop in the servo module is disabled. In this case, the Velocity Scaling value can be calculated by this formula: Velocity Scaling = 100% / (Speed @ 100%) For example, if this axis is using position units of motor revolutions (revs), and the servo drive is scaled such that with an input of 100% (for example, 10 Volts) the motor goes 5,000 RPM (or 83.3 RPS), the Torque Scaling attribute value would be calculated as shown below. Velocity Scaling = 100% / (83.3 RPS) = 1.2% / Revs Per Second

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 269

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Velocity Servo Bandwidth

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Hertz The value for the Velocity Servo Bandwidth represents the unity gain bandwidth that is to be used to calculate the gains for a subsequent MAAT (Motion Apply Axis Tune) instruction. The unity gain bandwidth is the frequency beyond which the velocity servo is unable to provide any significant position disturbance correction. In general, within the constraints of a stable servo system, the higher the Velocity Servo Bandwidth is the better the dynamic performance of the system. A maximum value for the Velocity Servo Bandwidth is generated by the MRAT (Motion Run Axis Tune) instruction. Computing gains based on this maximum value via the MAAT instruction results in dynamic response in keeping with the current value of the Damping Factor described above. Alternatively, the responsiveness of the system can be ‘softened’ by reducing the value of the Velocity Servo Bandwidth before executing the MAAT instruction.. There are practical limitations to the maximum Velocity Servo Bandwidth for the velocity servo loop based on the drive system and, in some cases, the desired damping factor of the system, Z. Exceeding these limits could result in an unstable servo operation.

The factor of 0.159 represents the 1/2PI factor required to convert Radians per Second units to Hertz. Velocity Standstill Status

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the magnitude of the physical axis Velocity Feedback is less than the configured Velocity Standstill Window.

Velocity Standstill Window

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Threshold

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Velocity Threshold Status

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the magnitude of the physical axis Velocity Feedback is less than the configured Velocity Threshold.

Velocity Window

AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / sec This attribute maps directly to a SERCOS IDN. See the SERCOS Interface standard for a description. This attribute is automatically set. Usually it does not need to be changed.

Watch Event Armed Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set when a watch event is armed through execution of the MAW (Motion Arm Watch) instruction. Cleared when a watch event occurs or an MDW (Motion Disarm Watch) instruction is executed.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

269

Page 270

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Watch Event Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set when a watch event occurs. Cleared when another MAW (Motion Arm Watch) instruction or an MDW (Motion Disarm Watch) instruction is executed.

Watch Event Task

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

MSG

Shows which task is triggered when the watch event happens. • An instance of 0 means that no event task is configured to be triggered by the watch event. • The triggering of the task occurs simultaneously with the setting of the Process Complete bit for the instruction that armed the watch event. • The controller sets this attribute. Do not set it by an external device.

Watch Position

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

Additional error code information

REAL

GSV Tag

Watch Position in Position Units Watch Position is the current set-point position of an axis, in the configured axis Position Units, as configured in the last, most recently executed, MAW (Motion Arm Watch) instruction for that axis.

See these manuals for more information about error codes displayed on drives and/or multi-axis motion control systems. Publication

Description

Kinetix 2000 Multi-Axis Servo Drive User Provides detailed installation instructions for mounting, Manual, publication 2093-UM001 wiring, and troubleshooting the Kinetix 2000 drive, and system integration for the drive/motor combination with a Logix controller.

270

Kinetix 6000 Multi-Axis Drives User Manual, publication 2094-UM001

Provides detailed installation instructions for mounting, wiring, and troubleshooting the Kinetix 6000 drive, and system integration for the drive/motor combination with a Logix controller.

Kinetix 7000 High Power Servo Drive User Manual, publication 2099-UM001

Provides detailed installation instructions for mounting, wiring, and troubleshooting the Kinetix 7000 drive, and system integration for the drive/motor combination with a Logix controller.

Ultra 3000 Digital Servo Drive Installation Instructions, publication 2098-IN003

Provides the mounting, wiring, and connecting procedures for the Ultra3000 and standard Rockwell Automation/Allen-Bradley motors recommended for use with the Ultra3000.

8720 High Performance Drive Installation Instructions, publication 8720MC-IN001

Provides the mounting, wiring, and connecting procedures for the 8720MC and standard Rockwell Automation/ AllenBradley motors recommended for use with the 8720MC.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018