Page 231

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Motion Status Bits

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV

Allows access to all motion status bits in one 32-bit word. This attribute is the same as the Motion Status tag.

Motor Capacity

AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. The present utilization of motor capacity as a percent of rated capacity.

Motor Data

AXIS_SERVO_DRIVE

Struct { INT; SINT [256]}

MSG

Struct {length; data[ ]} The Motor Data attribute is a structure with a length element and an array of bytes that contains important motor configuration information needed by an A-B SERCOS drive to operate the motor. The length element represents the number of data elements in the data array. The meaning of data within the data array is understood only by the drive. The block of data stored in the Motor Data attribute is derived at configuration time from a Logix Designer software motion database file.

Motor Electrical Angle

AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Degrees The present electrical angle of the motor shaft.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

231

Page 232

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Motor Feedback Configuration

AXIS_SERVO_DRIVE

INT

GSV

The controller and drive use this for scaling the feedback device counts. These attributes are derived from the corresponding Motor and Auxiliary Feedback Unit attributes. Bit 0 = Feedback type 0, rotary (default) 1, linear 1 = (reserved) 2 = Linear feedback unit 0, metric 1, english 3 = Feedback Polarity (Aux Only) 0, not inverted 1, inverted

Feedback Polarity The Feedback Polarity bit attribute can be used to change the sense of direction of the feedback device. This bit is only valid for auxiliary feedback devices. When performing motor/feedback hookup diagnostics on an auxiliary feedback device using the MRHD and MAHD instructions, the Feedback Polarity bit is configured for the auxiliary feedback device to insure negative feedback into the servo loop. Motor feedback devices must be wired properly for negative feedback since the Feedback Polarity bit is forced to 0, or noninverted. Motor Feedback Interpolation Factor

AXIS_SERVO_DRIVE

DINT

GSV

Feedback Counts per Cycle The Feedback Interpolation attributes establish how many Feedback Counts there are in one Feedback Cycle. The Feedback Interpolation Factor depends on the feedback device and the drive feedback circuitry. Quadrature encoder feedback devices and the associated drive feedback interface typically support 4x interpolation, so the Interpolation Factor for these devices would be set to 4 Feedback Counts per Cycle (Cycles are sometimes called Lines). High Resolution Sin/Cosine feedback device types can have interpolation factors as high as 2048 Counts per Cycle. The product to the Feedback Resolution and the corresponding Feedback Interpolation Factor is the overall resolution of the feedback channel in Feedback Counts per Feedback Unit. In our example, a Quadrature encoder with a 2000 line/rev resolution and 4x interpolation factor would have an overall resolution of 8000 counts/rev.

Motor Feedback Resolution

AXIS_SERVO_DRIVE

DINT

GSV

Cycles per Motor Feedback Unit The Motor and Aux Feedback Resolution attributes are used to provide the A-B drive with the resolution of the associated feedback device in cycles per feedback unit. These parameters provide the SERCOS drive with critical information needed to compute scaling factors used to convert Drive Counts to Feedback counts.

232

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 233

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Motor Feedback Type

AXIS_SERVO_DRIVE

INT

GSV

The Motor and Aux Feedback Type attributes are used to identify the motor mounted or auxiliary feedback device connected to the drive.

Motor Feedback Units

AXIS_SERVO_DRIVE

INT

GSV

The Motor Feedback Units attribute establishes the unit of measure that is applied to the Motor Feedback Resolution attribute value. The Aux Feedback Units attribute establishes the unit of measure that is applied to the Aux Feedback Resolution attribute value. Units appearing in the enumerated list cover linear or rotary, english or metric feedback devices. 0 = revs 1 = inches 2 = mm

Motor ID

AXIS_SERVO_DRIVE

INT

GSV

The Motor ID attribute contains the enumeration of the A-B motor catalog number associated with the axis. If the Motor ID does not match that of the actual motor, an error is generated during the drive configuration process.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

233

Page 234

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Motor Inertia

AXIS_SERVO_DRIVE

REAL

GSV SSV

%Rated / Pos Units per Sec2 The Motor Inertia value represents the inertia of the motor without any load attached to the motor shaft in Torque Scaling units of %Rated / Pos Units per Sec2. The Load Inertia Ratio attribute’s value represents the ratio of the load inertia to the motor inertia. Auto-tuning uses the Motor Inertia value to calculate the Load Inertia Ratio based on this equation. Load Inertia Ratio = (Total Inertia - Motor Inertia) / Motor Inertia. Total Inertia is directly measured by the auto-tuning algorithm and applied to the Torque Scaling attribute in units of %Rated / Pos Units per Sec2. If the Load Inertia Ratio value is known, the Motor Inertia value can also be used to calculate a suitable Torque Scaling value for the fully loaded motor without performing an auto-tune. The equation used by RSLogix5000 and the Logix Designer application to calculate the Torque Scaling value is: Torque Scaling = (1 + Load Inertia Ratio) * Motor Inertia. The value for Load Inertia may be automatically calculated using Rockwell’s MotionBook program while the value for Motor Inertia is derived from the Motion database file based on the motor selection.

Motor Overtemp Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the motor’s temperature exceeds the motor shutdown temperature.

Motor Rated Continuous Current

AXIS_SERVO_DRIVE

REAL

GSV

The Motor Rated Continuous Current attribute is a float that specifies the nameplate AC continuous current rating of the motor. This represents the current applied to the motor under full load conditions at rated speed and voltage. Any positive number. This is a database number and should not be changed.

Motor Rated Peak Current

AXIS_SERVO_DRIVE

REAL

GSV

The Motor Rated Peak Current attribute is a float that specifies the peak or intermittent current rating of the motor. The peak current rating of the motor is often determined by the thermal constraints of the stator winding or the saturation limits of PM motor magnetic material. Any positive number. This is a database number and should not be changed.

Motor Thermal Fault Action

AXIS_SERVO_DRIVE

SINT

GSV SSV

Move Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Move motion profile is currently in progress. Cleared when the Move is complete or is superseded by some other motion operation.

Neg Dynamic Torque Limit

AXIS_SERVO_DRIVE

REAL

Tag

The currently operative negative positive torque/current limit magnitude. It should be the lowest value of all torque/current limits in the drive at a given time, including: amplifier peak limit, motor peak limit, user current limit, amplifier thermal limit, and motor thermal limit.

234

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 235

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Neg Hard Overtravel Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set if the axis moves beyond the negative direction position limits as established by hardware overtravel limit switches mounted on the equipment. This fault can only occur when the drive is in the enabled state and the Hard Overtravel Checking bit is set in the Fault Configuration Bits attribute. If the Hard Overtravel Fault Action is set for Stop Command, the faulted axis can be moved or jogged back inside the soft overtravel limits. Any attempt, however, to move the axis further beyond the hard overtravel limit switch using a motion instruction results in an instruction error. To recover from this fault, the axis must be moved back within normal operation limits of the equipment and the limit switch closed. This fault condition is latched and requires execution of a Motion Axis Fault Reset (MAFR) or Motion Axis Shutdown Reset (MASR) instruction to clear. Any attempt to clear the fault while the overtravel limit switch is still open and the drive is enabled is unsuccessful.

Neg Overtravel Input Status

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is: • ON, The Negative Overtravel input is active. • OFF, The Negative Overtravel input is inactive.

Neg Soft Overtravel Fault

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is: • ON, The axis moved or tried to move past the Maximum Negative travel limit. • OFF, The axis moved back within the Maximum Negative travel limit This fault can only happen when the drive is enabled and the axis is configured for Soft Travel Limits. If the Soft Overtravel Fault Action is set for Stop Command, the faulted axis can be moved or jogged back inside the soft overtravel limits. Any attempt, however, to move the axis further beyond the soft overtravel limit using a motion instruction results in an instruction error. As soon as the axis is moved back within the specified soft overtravel limits, the corresponding soft overtravel fault bit is automatically cleared. However, the soft overtravel fault stays through any attempt to clear it while the axis position is still beyond the specified travel limits while the axis is enabled.

Negative Dynamic Torque Limit

AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. %Rated The currently operative maximum negative torque/current limit magnitude. The value should be the lowest value of all torque/current limits in the drive at a given time. This limit includes the amplifier peak limit, motor peak limit, user current limit, amplifier thermal limit, and the motor thermal limit.

Output Cam Execution Targets

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV

Represents the number of Output Cam nodes attached to this axis. Valid range = 0-8 with default of 0. The Output Cam Execution Targets attribute is used to specify the number of Output Cam nodes attached to the axis. This attribute can only be set as part of an axis create service and dictates how many Output Cam Nodes are created and associated to that axis. Each Output Cam Execution Target requires approximately 5.4k bytes of data table memory to store persistent data. With four Output Cam Execution Targets per axis, an additional 21.6k bytes of memory is required for each axis. The ability to configure the number of Output Cam Execution Targets for an axis reduces the memory required per axis if the Output Cam functionality is not needed, or only 1 or 2 Output Cam Execution Targets are needed for an axis. Each axis can be configured differently.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

235

Page 236

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Output Cam Lock Status AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV Tag

Set of Output Cam Lock Status bits The Output Cam Lock Status bit is set when an Output Cam is armed. This is initiated by executing an MAOC instruction with Immediate execution selected, when a pending output cam changes to armed, or when the axis approaches or passes through the specified axis arm position. As soon as this output cam current position moves beyond the cam start or cam stop position, the Output Cam Lock bit is cleared. This bit is also cleared if the Output Cam is terminated by a MDOC instruction.

Output Cam Lock Status AXIS_CONSUMED AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

Tag

A set of bits that are set when an Output Cam is locked to the Master Axis. The bit number corresponds with the execution target number. One bit per execution target.

Output Cam Pending Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV Tag

A set of bits that are set when an Output Cam is waiting for an armed Output Cam to move beyond its cam start/cam end position. The bit number corresponds with the execution target number. One bit per execution target. The Output Cam Pending Status bit is set if an Output Cam is currently pending the completion of another Output Cam. This would be initiated by executing an MAOC instruction with Pending execution selected. As soon as this output cam is armed, being triggered when the currently executing Output Cam completes, the Output Cam Pending bit is cleared. This bit is also cleared if the Output Cam is terminated by an MDOC instruction.

Output Cam Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV Tag

A set of bits that are set when the Output Cam is initiated. The bit number corresponds with the execution target number. One bit per execution target. The Output Cam Status bit is set when an Output Cam is initiated. The Output Cam Status bit is reset when the cam position moves beyond the cam start or cam end position in ‘Once’ execution mode with no Output Cam pending or when the Output Cam is terminated by an MDOC instruction.

Output Cam Transition Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV Tag

A set of bits that are set when the transition from the current armed Output Cam to the pending Output Cam is in process. The bit number corresponds with the execution target number. One bit per execution target. The Output Cam Transition Status bit is set when a transition between the currently armed and the pending Output Cam is in process. Therefore, each Output Cam controls a subset of Output Bits. The Output Cam Transition Status bit is reset when the transition to the pending Output Cam is complete or when the Output Cam is terminated by an MDOC instruction.

236

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 237

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Output Limit

AXIS_SERVO

REAL

GSV SSV

0.0…10.0V This controller attribute is replicated in the motion module. The Output Limit attribute provides a method of limiting the maximum servo output voltage of a physical axis to a specified level. The servo output for the axis as a function of position servo error, with and without servo output limiting, is shown below.

The servo output limit may be used as a software current or torque limit if using a servo drive in torque (current) loop mode. The percentage of the drive’s maximum current that the servo controller commands is equal to the specified servo output limit. For example, if the drive is capable of 30 Amps of current for a 10 Volt input, setting the servo output limit to 5V limits the maximum drive current to 15 Amps. The servo output limit may also be used if the drive cannot accept the full ±10 Volt range of the servo output. In this case, the servo output limit value effectively limits the maximum command sent to the amplifier. For example, if the drive can only accept command signals up to ±7.5 Volts, set the servo output limit value to 7.5 volts. Output Limit Status

AXIS_SERVO

BOOL

Tag

If this bit is: • ON, The servo output is at or past the Output Limit value. • OFF, The servo output is within the Output Limit value

Output LP Filter Bandwidth

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Hertz The Output LP (Low Pass) Filter Bandwidth controls the bandwidth of the drive’s low-pass digital output filter. The programmable low-pass output filter is bypassed if the configured Output LP Filter Bandwidth for this filter is set to zero (the default). This output filter can be used to filter out, or reduce, high frequency variation of the drive output to the motor. The lower the Output LP Filter Bandwidth, the greater the attenuation of these high frequency components of the output signal. Unfortunately, since the low-pass filter adds lag to the servo loop, which pushes the system towards instability, decreasing the Output LP Filter Bandwidth usually requires lowering the Position or Velocity Proportional Gain of the system to maintain stability. The output filter is particularly useful in high inertia applications where resonance behavior can severely restrict the maximum bandwidth capability of the servo loop. This controller attribute is replicated in the motion module.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

237

Page 238

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Output Notch Filter Frequency

AXIS_SERVO_DRIVE

REAL

GSV SSV

Hertz The Output Notch Filter Frequency attribute controls the center frequency of the drive’s digital notch filter. Currently implemented as a 2nd order digital filter with a fixed Q, the Notch Filter provides approximately 40DB of output attenuation at the Notch Filter Frequency. The programmable notch filter is bypassed if the configured Output Notch Filter Frequency for this filter is set to zero (the default). This output notch filter is particularly useful in attenuating mechanical resonance phenomena. The output filter is particularly useful in high inertia applications where mechanical resonance behavior can severely restrict the maximum bandwidth capability of the servo loop.

Output Offset

AXIS_SERVO

REAL

GSV SSV

+/-10V Another common situation when interfacing an external Servo Drive, particularly for velocity servo drives, is the effect of drive offset. Cumulative offsets of the servo module’s DAC output and the Servo Drive Input result in a situation where a zero commanded Servo Output value causes the axis to ‘drift’. If the drift is excessive, it can play havoc on the Hookup Diagnostic and Tuning procedures and result in a steady-state non-zero position error when the servo loop is closed. Output offset compensation can be used to correct this problem by adding a fixed value, called Output Offset, to the Servo Output. This value is chosen to achieve near zero drive velocity when the uncompensated Servo Output value is zero. This controller attribute is replicated in the motion module.

Overload Fault

AXIS_SERVO_DRIVE

BOOL

Tag

When the load limit of the motor/drive is first exceeded, the Overload warning bit is set. If the condition persists, the Overload fault is set. Often this bit is tied into the IT limit of the drive.

Overspeed Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set when the speed of the axis, as determined from the feedback, exceeds the overspeed limit, which is typically set to 150% of configured velocity limit for the motor.

Physical Axis Fault

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

If this bit is set, there are one or more faults on the physical axis. The faults can then be determined through access to the fault attributes of the associated physical axis. Should this fault give the controller a major fault? • YES, Set the General Fault Type of the motion group = Major Fault.

Pos Dynamic Torque Limit

AXIS_SERVO_DRIVE

REAL

Tag

The currently operative maximum positive torque/current limit magnitude. It should be the lowest value of all torque/current limits in the drive at a given time, including: amplifier peak limit, motor peak limit, user current limit, amplifier thermal limit, and motor thermal limit.

Pos Hard Overtravel Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set if the axis moves beyond the current position limits as established by hardware overtravel limit switches mounted on the equipment. This fault can only occur when the drive is in the enabled state and the Hard Overtravel Checking bit is set in the Fault Configuration Bits attribute. If the Hard Overtravel Fault Action is set for Stop Command, the faulted axis can be moved or jogged back inside the soft overtravel limits. Any attempt, however, to move the axis further beyond the hard overtravel limit switch using a motion instruction results in an instruction error. To recover from this fault, the axis must be moved back within normal operation limits of the equipment and the limit switch closed. This fault condition is latched and requires execution of an Motion Axis Fault Reset (MAFR) or Motion Axis Shutdown Reset (MASR) instruction to clear. Any attempt to clear the fault while the overtravel limit switch is still open and the drive is enabled is unsuccessful.

Pos Lock Status

AXIS_SERVO AXIS_SERVO_DRIVE

DINT

Tag

Set when the magnitude of the axis position error is less than or equal to the configured Position Lock Tolerance value for the associated physical axis.

238

• NO, Write code to handle these faults.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 239

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Pos Overtravel Input Status

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is: • ON, The Positive Overtravel input is active. • OFF, The Positive Overtravel input is inactive.

Pos Soft Overtravel Fault

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is: • ON, The axis moved or tried to move past the Maximum Positive travel limit. • OFF, The axis moved back within the Maximum Positive travel limit This fault can only happen when the drive is enabled and the axis is configured for Soft Travel Limits. If the Soft Overtravel Fault Action is set for Stop Command, the faulted axis can be moved or jogged back inside the soft overtravel limits. Any attempt, however, to move the axis further beyond the soft overtravel limit using a motion instruction results in an instruction error. As soon as the axis is moved back within the specified soft overtravel limits, the corresponding soft overtravel fault bit is automatically cleared. However, the soft overtravel fault stays through any attempt to clear it while the axis position is still beyond the specified travel limits while the axis is enabled.

Position Cam Lock Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set whenever the master axis satisfies the starting condition of a currently active Position Cam motion profile. The starting condition is established by the Start Control and Start Position parameters of the MAPC instruction. This bit is cleared when the current position cam profile completes, or is superseded by some other motion operation. In unidirectional master direction mode, the Position Cam Lock Status bit is cleared when moving in the ‘wrong’ direction and sets when moving in the ‘correct’ direction.

Position Cam Pending Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Position Cam motion profile is currently pending the completion of a currently executing cam profile. This would be initiated by executing an MAPC instruction with Pending execution selected. This bit is cleared when the current position cam profile completes, initiating the start of the pending cam profile. This bit is also cleared if the position cam profile completes, or is superseded by some other motion operation.

Position Cam Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Position Cam motion profile is currently in progress. Cleared when the Position Cam is complete or is superseded by some other motion operation.

Position Command

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Position Command in Position Units Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Position Command is the current value of the Fine Command Position into the position loop summing junction, in configured axis Position Units. Within the active servo loop, the Position Command value is used to control the position of the axis.

Position Data Scaling

AXIS_SERVO_DRIVE

INT

GSV

This attribute is derived from the Drive Units attribute. See IDN 76 in IEC 1491.

Position Data Scaling Exp

AXIS_SERVO_DRIVE

INT

GSV

This attribute is derived from the Drive Units attribute. See IDN 78 in IEC 1491.

Position Data Scaling Factor

AXIS_SERVO_DRIVE

DINT

GSV

This attribute is derived from the Drive Units attribute. See IDN 77 in IEC 1491.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

239

Page 240

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Position Differential Gain

AXIS_SERVO

REAL

GSV SSV

In some External Velocity Servo Drive applications where the level of damping provided by the external drive is insufficient for good position servo loop performance, additional damping may be achieved via the Position Loop Differential Gain. Assuming a non-zero Position Loop Differential Gain value, the difference between the current Position Error value and the last Position Error value is computed. This value is then multiplied by the Position Loop Differential Gain to produce a component to the Servo Output or Velocity Command that attempts to correct for the change in position error, creating a ‘damping’ effect. Increasing this gain value results in greater ‘damping’ of the axis.

Position Error

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Position Error in Position Units Position Error is the difference, in configured axis Position Units, between the command and actual positions of an axis. For an axis with an active servo loop, position error is used, along with other error terms, to drive the motor to the condition where the actual position is equal to the command position.

Position Error Fault

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

Set when the axis position error exceeds the Position Error Tolerance. This fault can only occur when the drive is in the enabled state. The controller latches this fault. Use a Motion Axis Fault Reset (MAFR) or Motion Axis Shutdown Reset (MASR) instruction to clear the fault.

Position Error Fault Action

AXIS_SERVO AXIS_SERVO_DRIVE

SINT

GSV SSV

This controller attribute is replicated in the motion module. Position Error Tolerance AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units The Position Error Tolerance parameter specifies how much position error the servo or drive tolerates before issuing a Position Error Fault. Like the position lock tolerance, the position error tolerance is interpreted as a ± quantity. For example, specifying a position error tolerance of 0.75 Position Units means that a Position Error Fault is generated whenever the position error of the axis is greater than 0.75 or less than -0.75 Position Units, as shown.

The self tuning routine sets the position error tolerance to twice this error at maximum speed based on the measured response of the axis. In most applications, this value provides reasonable protection in case of an axis fault or stall condition without nuisance faults during normal operation. If the calculated position error tolerance value needs to change, the recommended setting is 150% to 200% of the position error while the axis is running at its maximum speed. This controller attribute is replicated in the motion module.

240

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018