Page 41
Configure SERCOS motion
Chapter 1
To set the homing sequence: 1. Select the Homing tab, and in Mode, choose the homing mode.
2. In Position, type the position units. 3. In Sequence, choose the sequence type. 4. For all sequence types except Intermediate, in Description, choose the active home sequence direction, and then in Speed and Return Speed, set the homing speeds. 5. Select OK to apply the changes. See also Home an axis on page 111
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
41
Page 42
Page 43
Chapter 2
Configure analog motion
Introduction for Configure Analog Motion
Use this chapter for step-by-step procedures on how to configure analog motion control.
Create a controller project for Configure Analog Motion
Use these instructions to create a controller project. To create a controller project for Configure SERCOS Motion: 1. Open the Studio 5000 software.
2. In the Studio 5000 launcher, under Create, select New Project.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
43
Page 44
Chapter 2
Configure analog motion
3. On the New Project dialog box, choose a controller.
4. In the Name box, type a name for the controller project, and select Next.
5. In the Revision list, select the revision number for the controller. 6. In the Chassis list, select the type of chassis that holds the controller. 7. In the Slot list, select the physical slot where the controller is located. 44
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 45
Configure analog motion
Chapter 2
8. In the Security Authority list, select a security option: •
No Protection - All users can view and edit the project.
•
FactoryTalk Security - Only users authenticated through FactoryTalk Security can view and edit the project
9. (optional) Select Use only the selected Security Authority for authentication and authorization to associate this project with a specific Security Authority. When this check box is selected, users interacting with this project must be authenticated and authorized by the same Security Authority that was used to secure the project. Otherwise, unauthenticated users must rely on Guest User permissions. Tip:
Guest User permissions are cached within the project. The Logix Designer application uses Guest User permissions when the project is opened but not connected to the FactoryTalk Security Authority that secures the project. By default, all Guest User permissions are denied. Guest User permissions are configured in the FactoryTalk Administration Console.
10. Select Logical Name <Controller Name> or Permission Set to apply specific permissions to the controller. Select Logical Name <Controller Name> to apply a Logical Name in FactoryTalk Services Platform that has the same name as the controller. If there is no existing Logical Name that matches the controller name, a new Logical Name is created with the controller's name. The new Logical Name inherits permissions from its parent resource. See FactoryTalk Help for more information on how networks and devices inherit security permissions. Select Permission Set to apply a specific set of permissions to the controller. The permission sets in the list are maintained in FactoryTalk Services Platform and identify a set of actions that are allowed or denied for a particular user and computer combination. 11. (optional) In the Description box, type a description for the controller. Tip:
The description is limited to 128 bytes. Standard ASCII characters consume 1 byte per character, allowing for 128 characters. Characters in some languages require up to three bytes per character, resulting in less than 128 characters.
12. (optional) Select Enable redundancy if this project supports an automatic transfer of project control to a redundant controller in case of primary controller failure. 13. Select Finish.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
45
Page 46
Chapter 2
Configure analog motion
See also Add a SERCOS motion module on page 23 Add a SERCOS interface drive module on page 27 Add a motion group for Configure SERCOS motion on page 32 1. Add an axis on page 34
Set time synchronization for Configure Analog Motion
Time Synchronization in ControlLogix is called CIP Sync. CIP Sync is a layer of functionality that Rockwell Automation has developed on top of the IEEE 1588 PTP protocol. CIP Sync maintains accurate time synchronization of automation solutions. This setting establishes the module to participate in time synchronization. In systems with multiple processors, all controllers must have time synchronization enabled if they use CSmainT/PTP time. The 1756-ENxT communication modules win the arbitration over any processor. To set time synchronization for Configure Analog Motion: 1. In the Controller Organizer, double-click the controller. 2. On the Controller Properties dialog box, select the Date/Time tab.
3. Select Enable Time Synchronization. 46
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 47
Configure analog motion
Chapter 2
4. Select OK. Without intervention, the Grandmaster is PTP and CST master. Use the settings on the Advanced dialog box to let this module win the arbitration over other processors and communication modules in the chassis. See also Integrated Architecture and CIP Sync Configuration Application Technique, publication IA-AT003
Add an analog module
Use these instructions to add an analog module to the system. Important:
For all modules, use the firmware revision that goes with the firmware revision of the controller. See the release notes for the controller’s firmware.
To add an analog module: 1. In the Controller Organizer, right-click the backplane and select New Module.
2. On the Select Module Type dialog box, choose the module to add to the project.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
47
Page 48
Chapter 2
Configure analog motion
3. Select Close on Create, and select Create. 4. On the New Module dialog box, in Name, type a name for the module.
5. In Slot, choose the number that corresponds to the physical slot that contains the module. 6. (optional) In Description, type a description. 7. In Electronic Keying, choose a keying option of either Compatible Keying or Exact Match. WARNING: Disable Keying should never be used with motion modules.
8. Select Open Module Properties, and select OK. Continue with the procedure to modify the properties for the module. See also Electronic Keying on page 24
Modify properties for an analog module
Use the Module Properties dialog box to modify properties and associate axes with the module. To modify the properties for an analog module: 1. In the Controller Organizer, double-click the module.
48
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 49
Configure analog motion
Chapter 2
2. On the Module Properties Report dialog box, select the Associated Axes tab.
3. Select New Axis to create an axis to associate with this module. 4. On the New Tag dialog box, type a name for the Axis and select Create.
5. On the Module Properties Report dialog box, in Channel 0, choose the new axis to assign it to the module. 6. Select Browse to open the Axis Properties dialog box for the associated axis. Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
49
Page 50
Chapter 2
Configure analog motion
7. On the Axis Properties dialog box, in Module on the General tab, choose the module to associate with the axis.
8. Select the Servo tab. 9. In External Drive Configuration, choose the drive configuration.
Tip:
If configuring a torque drive, the drive must be able to be configured for torque. Hydraulic can only be selected for a hydraulic module.
10. Select OK.
50
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018