Page 31
Configure SERCOS motion
Chapter 1
7. On the Module Properties Report dialog box, in Node (Number), choose an AXIS_SERVO_DRIVE tag to associate with the drive’s node. 8. (optional) In the second Node (Number), choose an axis. 9. Select the Power tab.
10. In Bus Regulator Configuration, choose the catalog number that describes the bus regulator device used by the drive module. Depending upon the drive selected, one or more of the bus regulator IDs may be available. Important:
This setting does not apply to the 8720MC drive, the Ultra3000 SERCOS drive, or Kinetix 6200 Integrated Drive Motor (IDM) drive. For those drives, <none> is the only available option.
11. If configuring a Kinetix 2000 230-volt drive, in Input Power, choose Single-Phase or Three-Phase. 12. If configuring an IDM Power Interface Module (IPIM) or IDM module, in Additional Bus Capacitance, choose the additional bus capacitance that is required. This parameter is only valid if an axis is associated with the Kinetix 6000 and Kinetix 6200 IAM module. When an axis is initially associated to the IAM, this parameter shows the default value and is enabled. If a valid value is set in the associated axis, and the axis is not associated to the IAM, this parameter is reset to the default value and cannot change until an axis is associated to the IAM. 13. Select OK. See also Add an axis on page 34
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
31
Page 32
Chapter 1
Configure SERCOS motion
Add a motion group for Configure SERCOS Motion
Use these instructions to add a motion group. Important:
Only one motion group can be created for each project.
To add a motion group for Configure SERCOS Motion: 1. In the Controller Organizer, right-click Motion Groups and select New Motion Group.
2. On the New Tag dialog box, in Name, type a name for the motion group.
3. (optional) In Description, type a description. 4. Select Create.
32
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 33
Configure SERCOS motion
Chapter 1
See also Add an axis on page 34
Set the Base Update Period
The Base Update Period (also known as the Coarse Update Period) is how often the motion planner runs. The motion planner is the part of the controller that handles position and velocity information for the axes. When the motion planner runs, it interrupts most other tasks regardless of their priority. Example: If the Base Update Period is set to 10 ms, then every 10 ms the controller stops scanning the code and performing other system overhead tasks, and runs the motion planner.
Use these guidelines to set the Base Update Period. Guideline
Description
Number of Axes
1756-L6x controller 4 axes/ms 1756-L7x controller8 axes/ms
Save Controller’s Time
Leave at least half the controller’s time for the scan of all the code.
Base Update Period and SERCOS modules
For SERCOS interface motion modules, set the Base Update Period to a multiple of the cycle time of the motion module. Example: If the cycle time is 2 ms, set the Base Update Period to 8 ms, 10 ms, 12ms, and so on.
Base Update Period and Analog modules
For analog motion modules, set the Base Update Period to: • At least 3 times the servo update period of the motion module. • A multiple of the servo update period of the motion module.
To set the Base Update Period: 1. In the Controller Organizer, double-click the motion group.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
33
Page 34
Chapter 1
Configure SERCOS motion
2. Select the Attribute tab.
3. In Base Update Period, choose the update period using the guidelines mentioned earlier. The valid values range from 0.5 to 32, in 0.5 increments. Tip:
The Axis Schedule button opens the Axis Schedule dialog box to schedule the base and alternate update periods and assign axes to them. Since axes used in coordinate system objects cannot be multiplexed, only the Base Update Period is used. Therefore, there is no need to open the Axis Schedule dialog box.
4. In General Fault Type, choose Non Major Fault. 5. Select OK. See also Manage motion faults on page 67
Add an axis
34
Use these instructions to add an axis for each of the drives.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 35
Configure SERCOS motion
Chapter 1
To add an axis for Configure SERCOS Motion: 1. In the Controller Organizer, right-click the motion group and select New Axis.
2.
Choose the data type based on these guidelines. •
If using one of these motion modules, choose AXIS_SERVO_DRIVE. •
1756-M03SE
•
1756-M08SE
•
1756-M16SE
•
1768-M04SE
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
35
Page 36
Chapter 1
Configure SERCOS motion
•
If using a virtual configuration (no hardware), choose AXIS_VIRTUAL.
3. On the New Tag dialog box, in Name, type a name for the axis.
4. (optional) In Description, type a description for the axis. 5. Select Create. See also Configure an axis to Configure SERCOS Motion on page 37
Get axis information
36
To get information about an axis: •
Use the Quick View pane to see the state and faults of an axis.
•
Use a Get System Value (GSV) instruction or Set System Value (SSV) instruction to read or change the configuration at run-time.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 37
Configure SERCOS motion
Chapter 1
•
Configure an axis for Configure SERCOS Motion
Use the tag of the axis for status and faults.
Use these instructions to configure the axis of a SERCOS interface drive. The steps may differ depending on the type of drive. To configure an axis for Configure SERCOS Motion: 1. In the Controller Organizer, double-click the axis. 2. On the General tab, verify that the assigned motion group and module information is correct. Make any necessary changes.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
37
Page 38
Chapter 1
Configure SERCOS motion
3. Select the Units tab, and in Position Units and Average Velocity Timebase, enter the values.
4. Select the Drive/Motor tab. 5. Select Change Catalog, and on the Change Catalog Number dialog box, choose the related motor catalog numbers, and select OK.
These conditions apply for the Integrated Drive Motor (IDM).
38
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 39
Configure SERCOS motion
Chapter 1
•
The Amplifier Catalog Number appears dimmed and cannot be edited when the axis is associated to an IDM.
•
The Motor Catalog Number is automatically set to the catalog number of the only motor available from the Motion Database for the IDM module when it is associated to the axis.
•
The Catalog Number for the IDM appears dimmed and is read-only. It is automatically set to the compatible motor from the motion database for each IDM.
•
An IDM does not support Auxiliary Axis loop configurations. When the Axis Configuration on the General tab is set to Servo, the selections for Loop Configuration for the IDM are: • •
Position Servo Dual Command Servo (does not use the Auxiliary Port)
• •
Velocity Servo Torque Servo
When the Axis Configuration on the General tab is set to Feedback Only, the selection for Loop Configuration for the IDM is Motor Feedback Only. •
Real-time attributes for the IDM are: • •
Position Command Position Feedback
• •
Position Error Position Int. Error
• •
Velocity Command Velocity Feedback
•
Velocity Error
•
Velocity Int. Error
•
Accel Command
• •
Accel Feedback Marker Distance
•
Torque Command
•
Torque Feedback
• •
Positive Dynamic Torque Limit Negative Dynamic Torque Limit
•
Motor Capacity
• •
Drive Capacity Power Capacity
•
Bus Regulator Capacity
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
39
Page 40
Chapter 1
Configure SERCOS motion
• •
Motor Electrical Angle Torque Limit Source
•
DC Bus Voltage
6. In Drive Resolution, type the resolution, and in Drive Counts /, select the units. 7. Select Calculate. 8. On the Calculate Position Parameters dialog box, select Calculate, review the values and adjust as needed until finding the desired calculated values, then select Update and Close.
See also Axis properties on page 119
Set the homing sequence for Configure SERCOS Motion
40
Use the Homing tab in the Axis Properties dialog box to set up the homing mode and sequence for the module.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018